AZ3s USER MANUAL
ST.TEC.054
50 / 60
Variable
Type
Code
Unit
Default
Range
Can open
address
Modbus logical
address
Feed constant shaft
revolutions
UNS32
FS6
rounds
1
0÷400000
INDEX
SUB
6092h
02h
HR
99
100
Position encoder
resolution motor
revolutions
UNS32
FS9
rounds
1
0÷400000
INDEX
SUB
608Fh
02h
HR
105
106
Position encoder
resolutions encoder
increments
UNS32
FS10
-
8192
0÷400000
INDEX
SUB
608Fh
01h
HR
107
108
Velocity factor
numerator
S16
FS11
-
60
0÷32767
INDEX
SUB
6094h
01h
HR
109
Velocity factor
denominator
S16
FS12
-
1
0÷32767
INDEX
SUB
6094h
02h
HR
110
Polarity
UNS16
FS13
-
0
0÷65536
INDEX
SUB
607Eh
HR
111
Control word
UNS16
CM1
-
0
0÷65535
INDEX
SUB
6040h
HR
156
Modes of operation
S8
CM2
-
3
-128÷127
INDEX
SUB
6060h
HR
157L
Feed constant shaft
revolutions
UNS32
FS6
rounds
1
0÷400000
INDEX
SUB
6092h
02h
HR
99
100
Target velocity
S32
CM4
User
units
0
-2.0E6÷2.0E6
INDEX
SUB
60FFh
HR
158
159
TDI CW mode
UNS8
SCM1
-
0
0÷255
INDEX
SUB
204Eh
01h
HR
173L
Motor type
UNS16
MTY1
-
10
0÷65535
INDEX
SUB
6402h
HR
176
Encoder phase
displacement
FLOAT
PHC3
[rad]
3.14
-6.28÷6.28
INDEX
SUB
2052h
03h
HR
185
186
Output 1 selector
UNS8
OF1
-
0
0÷255
INDEX
SUB
204Eh
02h
HR
187L
Output 2 selector
UNS8
OF2
-
0
0÷255
INDEX
SUB
204Eh
03h
HR
187H
Encoder feedback
mode
UNS8
EFM1
-
0
0÷255
INDEX
SUB
204Eh
04h
HR
188L
User range 1
FLOAT
AI1
-
1000
-1.0E9÷1.0E9
INDEX
SUB
2045h
02h
HR
249
250
Offset 1
FLOAT
AI2
-
0
-1.0E9÷1.0E9
INDEX
SUB
2045h
03h
HR
251
252
Zero threshold 1
UNS16
AI3
-
5
0÷65535
INDEX
SUB
2045h
04h
HR
253
User range 2
FLOAT
AI4
-
1000
-1.0E9÷1.0E9
INDEX
SUB
2046h
02h
HR
254
255
Offset 2
FLOAT
AI5
-
-500
-1.0E9÷1.0E9
INDEX
SUB
2046h
03h
HR
256
257
Zero threshold 2
UNS16
AI6
-
1
0÷65535
INDEX
SUB
2046h
04h
HR
258
Selector 1
UNS8
AI7
-
2
0÷255
INDEX
SUB
2045h
01h
HR
259L
Selector 2
UNS8
AI8
-
4
0÷255
INDEX
SUB
2046h
01h
HR
259H
AI Mult 1
FLOAT
AI9
-
0.1
-1.0E9÷1.0E9
INDEX
SUB
-
HR
260
261
AI Mult 2
FLOAT
AI10
-
0.9
-1.0E9÷1.0E9
INDEX
SUB
-
HR
262
263