Page 7
= 2 Instantaneous Contact
OUT2
is energised during the counting process and remains energised until the
Reset
signal is activated.
Start
OUT1
Reset
OUT2
=1
= 3 OUT2 Operates the same function as OUT1 but with time
OUT2
operates exactly the same function as
OUT1
but whilst
OUT1
operates to time ,
OUT2
operates to time . has the same time range as (9999h, 99h59m,
99m59s or 99.99s) and cannot be set to a value higher than .
If = 1, 4 or 5,
OUT2
operates a delay on energise function.
If = 2 or 3,
OUT2
operates a feed through function with a set time.
Start
OUT1
Reset
OUT2
= 1
Start
OUT1
Reset
OUT2
= 2
Start
OUT1
Reset
OUT2
= 3
Start
OUT1
Reset
OUT2
= 5
Start
OUT1
Reset
OUT2
= 4
= 4 OUT2 Operates the same function as OUT1 but in advance by time
OUT2
operates exactly the same function as
OUT1
but
OUT2
operates in advance of
OUT1
. has the same time range as (9999h, 99h59m, 99m59s or 99.99s) and
cannot be set to value higher than .
If = 1, 4 or 5,
OUT2
operates a delay on energise function.
If = 2 or 3,
OUT2
operates a feed through function with a set time.
Start
OUT1
Reset
OUT2
= 1
Start
OUT1
Reset
OUT2
= 2
Start
OUT1
Reset
OUT2
= 3
Start
OUT1
Reset
OUT2
= 5
Start
OUT1
Reset
OUT2
= 4
= 5
OUT2
energises when the buzzer sounds (with
= 2
) to manage an external sound/light signalling device.
OUT2 OPERATING MODES
The second output (
OUT2
) can be programmed in one of 5 different operating modes with the parameter.
.
= oF
OUT2
disabled
.
= 1
OUT2
operates exactly the same as
OUT1
to give a double output contact