11
Dangerous voltages capable of causing death are
sometimes present in this instrument. Before instal-
lation or beginning any troubleshooting procedures, the
power to all equipment must be switched off and isolated.
Units suspected of being faulty must be disconnected and
removed to a properly equipped workshop for testing and
repair. Component replacement and internal adjustments
must be made by a qualified maintenance person only.
To minimize the possibility of fire or shock hazards
do not expose this instrument to rain or excessive
moisture.
Do not use this instrument in areas under hazardous
conditions such as excessive shock, vibration, dirt,
moisture, corrosive gases or oil. The ambient temperature
of the area should not exceed the maximum rating specified
in chapter 6.
2–1 Unpacking
Upon receipt of the shipment, remove the unit from the car-
ton and inspect the unit for any shipping damage.
If there is any damage due to transit, report it and file a
claim with the carrier. Write down the model number, seri-
al number and date code. for future reference when corre-
sponding with our Service Department. The serial number
(SN) and date code (D/C) are labeled on the box and the
housing of the unit.
2–2 Mounting
Make the panel cutout according to the dimensions shown
in figure 2.1.
Remove the mounting clamps and screws and insert the
controller into the panel cutout. Reinstall the mounting
clamp and screws. Gently tighten the screws until the front
panel fits snugly in the cutout.
Chapter 2 Installation
53 mm
(2-1/8")
Panel
Panel Cutout
92 mm
(3-5/8")
92 mm
(3-5/8")
Figure 2.1 Mounting Diagram
2–3 Wiring Precautions
• Before wiring, verify the correct model number and
options on the label. Switch off the power while checking.
• Care must be taken to ensure that the maximum voltage rating
specified on the label is not exceeded.
• It is recommended that the power for these units be protected
by fuses or circuit breakers rated at the minimum value pos-
sible.
• All units should be installed inside a suitably grounded metal
enclosure to prevent live parts from being accessible to
human hands and metal tools.
• All wiring must conform to appropriate standards of good
practice and local codes and regulations. Wiring must be
suitable for the voltage, current, and temperature rating of
the system.
• Beware not to over-tighten the terminal screws. The torque
should not exceed 1N-m (8.9 lb-in or 10 KgF-cm)
• Unused control terminals should not be used as jumper
points as they may be internally connected, causing damage
to the unit.
• Verify that the ratings of the output devices and the inputs as
specified in chapter 6 are not exceeded.
• Except the thermocouple wiring, all wiring should use
stranded copper conductor with maximum gauge of 18
AWG.
Figure 2.2
Lead Termination
Figure 2.3
Rear Termination Connection Diagram
Notes: 50°C max. air ambient
Use copper conductors (except on T/C input)
ASTM thermocouples (USA), the red colored lead
is always negative
.
Summary of Contents for TEC-410
Page 26: ...24 ...