36
Instructions manual |
www.grupotemper.com
KDP6
Wall presence detector
Operation and funtion
Knob setting
The default setting of each knob
before ex-factory is as following:
METER “+”, TIME:”Test”, LUX:
,
LED mode: “watch” (See FIG 17).
METER knob setting
• Set METER knob value at
the position of “-”for the
“smallest field of view”
•
Set METER knob value at the
position of “+”for the “largest
field of view”
•
Set METER knob value at the
position between “-” and
“+” for “desired field of
view”
TIME knob setting
•
Set TIME knob value at the
position of “Test”, start to walk
test, the load and LED turn on 2
sec. then turn off while detector
is triggered.
•
Set TIME knob value at the
position of “-”, the minimum
delay time will be 6 sec.
•
Set TIME knob value at the
position of “+”, the maximum
delay time will be 10 min.
•
Set TIME knob value at the
position of “
”, staircase time
switch will receive 1 sec. signal
once KDP6 is triggered, then the
light ON 1 sec., OFF 9 sec.
•
To adjust the TIME knob in
between “-”& “+” according
to users desire.
LUX knob setting
•
When setting the LUX knob to
• “
”, the detector will operate
the lighting only in the darkness.
•
When setting the LUX knob to
• “
”, the detector will operate
the lighting at any light level.
•
To adjust the LUX knob
according to users needed.
LED mode setting
LED mode features OFF/warning/
Watch under function where there
is no setting TIME knob “Test”and
standby status. The mode is selected
according to users desire and refer to
following chart for details.