background image

- 3 -

Figure 3. Pressurisation bung locations

4.   CONTROLS

4.1  Electrical Requirements

Electrical work must be done by a qualified electrician.

 DANGER! LIVE ELECTRICAL CONNECTIONS. DISCONNECT MAINS 

POWER BEFORE WORKING ON UNIT. ONLY QUALIFIED PERSONS 

WHO ARE COMPETENTLY TRAINED SHOULD PERFORM SERVICE AND 

MAINTENANCE TASKS.

The outdoor unit must be wired directly from a distribution 

board by means of a circuit breaker and a mains isolator 

provided – preferably close to the unit.
A 24 hour power supply to the compressor crank case 

heaters is required, otherwise the warranty is void.

4.2  Control options

OPA Econex units can be controlled using any of the 

following options:
• TZT-100 wall thermostat
• SAT-3 wall thermostat
• 24V AC and 0-10V signals from an external controller or 

thermostat

• Remote on/off switch and/or time clock
• Modbus RTU serial communications over RS485 

connection

• BACnet-IP serial communications over Ethernet 

connection (with optional gateway module)

Standard reverse cycle units are suitable for use with 

thermostats and controls with manual heating/cooling 

selection or automatic change-over.
A unit wiring diagram is supplied alongside the electrical 

board and in the Specifications document.

4.3  TZT-100 or SAT-3 wall thermostat

To connect the thermostat to the unit it is recommended 

to use shielded twisted pair type cable, suitable for RS485 

communications. Signals A and B should form one twisted 

pair. 

Note: The cable shield should connect to terminal ‘0V’ on 

the UC8 controller only. Do not connect at both ends. 
Connect the thermostat as follows:
TZT-100 Connection:

TB5

B1

TB6

A1

TB7

0V

TB8

12V

TB9

B

A

24C

24

W6

PCLP1

TZT-100

OPA

TB5

B1

TB6

A1

TB7

0V

TB8

12V

TB9

B

A

GRND

12V

W6

PCLP1

SAT-3

OPA

Control

- shielded

twin twisted pair

4 core

(201-000-399)

Control

- shielded

twin twisted pair

4 core

(201-000-399)

SAT-3 Connection:

TB5

B1

TB6

A1

TB7

0V

TB8

12V

TB9

B

A

24C

24

W6

PCLP1

TZT-100

OPA

TB5

B1

TB6

A1

TB7

0V

TB8

12V

TB9

B

A

GRND

12V

W6

PCLP1

SAT-3

OPA

Control

- shielded

twin twisted pair

4 core

(201-000-399)

Control

- shielded

twin twisted pair

4 core

(201-000-399)

Note: Capacity Staging. A TZT-100 or SAT-3 must be 

configured for single-stage operation, the default setting.

TZT-100 has its own DIP switches that must be set as 

follows: 

DIP switch 2

ON

Equipment type = Heat Pump

DIP switch 3

OFF Equipment stages = One

DIP switch 4

ON

Reverse cycle valve on = Heating

SAT-3:  Refer SAT-3 Installation Set-up Guide page 3.

4.4  Communications format for TZT-100 and SAT-3

Communications format must be set as per recommended 

Modbus RTU:

• Baud rate (bd or br)  19200

• Data bits 

8

• Parity 

Even

• Stop bits (Pa) 

1

• TZT-100 address (Ad)  7

• SAT-3 address (Ad)  8
TZT-100:  

The procedure to check and adjust these settings is:

1.  Press and hold the O/RIDE button until the display 

 

shows the PIN

2.  Use the UP & DOWN buttons to select PIN code 88:21, 

 

then press O/RIDE in installer mode.

3.   Use the O/RIDE and PROG buttons to cycle through the 

 

various installer settings.  

If necessary, refer TZT-100 User Manual for more detail.
SAT-3:  

The procedure to check and adjust these settings is:

1.   Press and hold the MODE and 6 button until the display 

 

shows the ‘i’ symbol.

2.   Use the UP & DOWN buttons to cycle through the 

 

various installer settings. 

3.   Press MODE button to save any new setting. 

If necessary, refer SAT-3 Installation Set-up Guide for more 

detail.

4.5  Remote on/off

The UC8 has an input for a remote on/off function on 

terminal ‘On’, signal return is terminal ‘0V’. When used the 

remote on/off terminals should connect to a voltage-free 

relay contact. When not used the remote on/off terminals 

should be shorted (‘bridged’).

4.6  Capacity control

OPA Econex units offer the following capacity control 

options:
• Automatic control when the unit connects to the TZT-100 

or SAT-3 wall thermostat.

• 0-10V compressor control signal
• 0-10V indoor fan control signal.
• Control by a building management system via Modbus 

RTU or BACnet-IP serial communications.

Drawn:

Title:

Drawing No:

 

 

23/02/2022

pchandrasekaran

A

Rev:

Date:

©temperzone Ltd 2021

OPA 560 RLTFPQ-CZ (01, 10, 23, 32)

OPA 560 RLTFPQ-CZ Combined Variants

876-056-700

Est Weight:

0 kg

Sheet 1  of 1 

*876-056-700/A*

3rd ANGLE PROJECTION

Do not scale drawing

Interpret drawing as per GD&T standard: ISO 2768-1

Unless specified all dimensions are in millimeters

Mat:

Fin:

PROPRIETARY & CONFIDENTIAL

The information contained in

this drawing is the sole 

proprietary of temperzone limited.

Unauthorised copying,

possession, discussion, publication 

& distribution prohibited

 

TOLERANCES UNLESS STATED

LINEAR:               ANGULAR:

0      = ±0.5         0    = ±1°

0.0   = ±0.1         0.0  = ±0.5°

0.00 = ±0.05       0.00 = ±0.1°

 

 

Standard hand unit

Opposite hand unit

Summary of Contents for Econex OPA 250RLTFP

Page 1: ...well ventilated space If the refrigerant gas comes into contact with fire a poisonous gas may occur Be aware that R32 does not contain an odour If indoors the appliance shall be stored in a room away...

Page 2: ...eparate drain tray beneath the unit could be used to drain condensate to a suitable drainage point Condensate drains should be U trapped outside the unit The trap should have a vertical height of at l...

Page 3: ...llows DIP switch 2 ON Equipment type Heat Pump DIP switch 3 OFF Equipment stages One DIP switch 4 ON Reverse cycle valve on Heating SAT 3 Refer SAT 3 Installation Set up Guide page 3 4 4 Communication...

Page 4: ...emperzone biz model search UC8 or com website 4 10 Setting the UC8 Modbus device address To view or change the Modbus device address of a UC8 follow these steps Power up the unit but leave the compres...

Page 5: ...er 2 Start compressor in Cooling mode 3 Check the outdoor fan motor runs smoothly Note The outdoor fan does not necessarily start rotating immediately after the compressor is started The fans may run...

Page 6: ...signals and transfers the signals to the outputs after enforcing safety timers and other protection functions If the compressor is held off or held on by a safety timer then the display shows message...

Page 7: ...door coil This usually means reversing the cycle for a few minutes during which time there is no heating and in fact a little cooling can occur 8 4 In a new building why does it take some days before...

Page 8: ...t 6K Compressor discharge line pressure kPa dLP Discharge line pressure 2447 kPa Condensing temperature C Ct Condensing temperature 42 C Compressor discharge line temperature C dLt Discharge line temp...

Page 9: ...indication that the compressor is being starved of refrigerant gas Common reasons for this could be a lack of refrigerant under charged or loss of charge or a problem with the expansion device for exa...

Page 10: ...ked out the compressor is not allowed to start Lock out is designed to protect the compressor from repeatedly starting when a serious fault exists that requires the attention of a service technician T...

Page 11: ...3 4 1 1 INPUT kW 2 5 1 5 0 5 2 0 1 0 3 0 3 5 Amps 500 1000 1500 2000 2500 0 100 200 300 AIR FLOW l s AVAILABLE EXTERNAL PRESSURE Pa 2 5 m s Face Velocity 400 500 0 NOMINAL INPUT kW 3 0 2 0 1 0 2 5 1 5...

Page 12: ...st IMPORTANT Digital compressors must be operating at 100 for at least 10 minutes when taking these readings System 1 Cool Cycle Low Pressure SLP kPa Outdoor Ambient temperature C Evap temperature Et...

Reviews: