Temperzone   SAT-­‐3   Installation   Setup   Guide,   Issue   2   

   

      

   

   

Page   7

   of   7   

   

3.

 

SAT-­3   Fault   Indications   

The   SAT-­‐3   indicates   some   faults   that   may   be   useful   during   installation.   Faults   are   indicated   

in   the   bottom   right   area   of   the   display.   

Wiring   changes   should   only   be   made   with   the   power   disconnected.   

Code   
displayed   

Description   

Remedy   

t1   

SAT-­‐3   internal   temperature   

sensor   error   

The   internal   temperature   sensor   of   the   SAT-­‐3   

is   damaged.   Replace   the   SAT-­‐3.   

t2   

SAT-­‐3   external   temperature   

sensor   error   

Check   the   external   temperature   sensor   

connected   to   the   Sat-­‐3.   

t3   

No   communications   between   

SAT-­‐3   and   unit   controller   

Check   the   wiring   between   the   unit   controller   

and   the   SAT-­‐3.      
Check   the   SAT-­‐3   baud   rate   is   set   at   19200   

baud   (see   section   2.1).   

   

   

Summary of Contents for SAT-3

Page 1: ...Temperzone SAT 3 Installation Setup Guide Issue 2 SAT 3 Installation Setup Guide Date 4 February 2016 Issue 2 Applies to SAT 3 room temperature controller part number 201 000 146 ...

Page 2: ...Temperzone SAT 3 Installation Setup Guide Issue 2 ...

Page 3: ...uide 2 1 1 General 2 1 1 1 Installation Settings 2 1 1 2 Clock Setting 2 1 2 Fan Setup 2 1 3 Air Conditioner Commissioning 2 2 Detailed SAT 3 Configuration 3 2 1 Installation Settings 3 2 2 Fan Settings 5 2 3 Commissioning Mode 6 2 4 Return Air Sensor Option 6 3 SAT 3 Fault Indications 8 ...

Page 4: ...nd time using the keys detailed in section 1 1 When the day and time are set correctly leave the SAT 3 for 15 seconds to return to normal operation 1 2 Fan Setup Activate fan setup mode by holding down and together for 3 seconds When fan setup mode is active the symbol on the display flashes on and off 1 Adjust the low fan control voltage to a suitable low level while monitoring the airflow 2 Adju...

Page 5: ...i SET Ht Ct to 50 0 C Steps of 0 5 C Temperature differential i td 0 5 to 1 5 C Steps of 0 5 C Indoor fan type i Ft 1 or 3 Single or three speed fan Default 3 speed Enable disable Heating mode i On or off Default on Enable disable Cooling mode i On or off Default on Enable disable Cool Heat auto mode i On or off Default on see note 1 Enable disable Fan Only mode i On or off Default on Enable disab...

Page 6: ...point from zone 1 set point i ZONE SP 2 0 to 10 0 C N A see note 6 Minimum number of zones that must be on i ZONE nn 0 1 or 2 N A see note 6 Zone 1 Size i 1 to 5 N A see note 6 Zone 2 Size i 0 to 5 N A see note 6 Zone 3 Size i 0 to 5 N A see note 6 Zone 4 Size i 0 to 5 N A see note 6 Zone 5 Size i 0 to 5 N A see note 6 Zone 6 Size i 0 to 5 N A see note 6 Programmable timer function i tF 1 or 2 Def...

Page 7: ...bol on the display flashes on and off Settings in Fan Setup Mode are as follows Setting Display Range Notes Low level fan control voltage SET Lo 2 0 to 8 0 Default 5 0 High level fan control voltage SET Hi 4 0 to 10 0 Default 8 0 Steps of 0 333 e g 2 0 2 3 2 7 3 0 etc Additional zone voltage increase SET Ad 0 to 950 Default 300 Zone 1 balance bL 10 to 100 Default 100 Zone 2 balance bL 10 to 100 De...

Page 8: ...utes 1 minute Minimum heating to cooling change over time 10 minutes 1 minute Power on delay prior to starting compressor 2 minutes 2 minutes 2 4 Return Air Sensor option To use a return air sensor with the SAT 3 the return air sensor must be connected to the SAT 3 The SAT 3 provides a socket that accepts a 2 pin JST connector of the standard type that Temperzone uses for its optional temperature ...

Page 9: ...ith the power disconnected Code displayed Description Remedy t1 SAT 3 internal temperature sensor error The internal temperature sensor of the SAT 3 is damaged Replace the SAT 3 t2 SAT 3 external temperature sensor error Check the external temperature sensor connected to the Sat 3 t3 No communications between SAT 3 and unit controller Check the wiring between the unit controller and the SAT 3 Chec...

Reviews: