background image

Summary of Contents for F9MXE

Page 1: ...ructions or manuals be alert to the potential for personal injury TABLE OF CONTENTS SAFETY CONSIDERATIONS 3 INTRODUCTION 4 CODES AND STANDARDS 4 ELECTROSTATIC DISCHARGE PRECAUTIONS PROCEDURE 5 DIMENSIONS 6 LOCATION 7 LOCATION RELATIVE TO COOLING EQUIPMENT 8 AIR FOR COMBUSTION AND VENTILATION 9 CONDENSATE TRAP 12 INSTALLATION 19 UPFLOW INSTALLATION 19 DOWNFLOW INSTALLATION 20 HORIZONTAL INSTALLATIO...

Page 2: ...ntally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state of local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector observes carbon monoxide detectors and s...

Page 3: ...follow all warnings or cautions included in literature and attached to the unit CUT HAZARD Failure to follow this caution may result in personal injury Sheet metal parts may have sharp edges or burrs Use care and wear appropriate protective clothing safety glasses and gloves when handling parts and servicing furnaces This is the safety alert symbol Z_ When you see this symbol on the furnace and in...

Page 4: ...oth natural and propane gas The furnace must also be installed on a factory supplied accessory combustible floor base or evaporator coil casing This furnace is designed for minimum continuous return air temperature of 60 F 15 C db or intermittent operation down to 55 F 15 C db such as when used with a night setback thermostat Return air temperature must not exceed 80 F 27 C db Failure to follow th...

Page 5: ...y putting the furnace the control and the person at the same elec trostatic potential 1 Disconnect all power to the furnace Multiple disconnects may be required DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY S ELECTROSTATIC CHARGE TO GROUND 2 Firmly touch the clean unpainted metal surface of the furnace chassis which is close to the control Tools held ...

Page 6: ...l NR_OW S 4_a _S_N laS _ 1o1111 I O_ IN 711 r_ER_rAT ENTRy _rrOM rNt_ SD5060 4 Rev F F G 9MXT FURNACE SIZE 0401410 0401714 0601412 0601714 0801716 0802120 1002120 1202422 F G 9MXE FURNACE SIZE 0401410 0401714 0601412 0601714 0801716 0802120 1002120 1202422 A CABINET WIDTH B OUTLET WIDTH AIR INTAKE 14 3 16 361 12 1 2 319 7 1 8 181 17 1 2 445 15 7 8 403 8 3 4 222 14 3 16 361 12 1 2 319 7 1 8 181 17 ...

Page 7: ...nace must be installed so the electrical components are protected from water not be installed directly on any combustible material other than wood flooring refer to SAFETY CONSIDERATIONS be located close to the chimney or vent and attached to an air distribution system Refer to Air Ducts section be provided ample space for servicing and cleaning Always comply with minimum fire protection clearance...

Page 8: ...t be installed in accordance with the NFPA 54 ANSI Z223 1 2012 or CAN CSA B149 1 2010 See Figure 4 Figure 4 1Installation in a Garage 18 1N 457 2 mm MINIMUM TO BURNERS A93044 Figure 5 _Prohibit Installations BACK POSITIONED DOWNWARD BACK POSITIONED UPWARD d IR RETURN CUT IN BACK L12F011 Location Relative to Cooling Equipment The cooling coil must be installed parallel with or on the downstream sid...

Page 9: ...ntaminants are found in aerosol sprays detergents bleaches cleaning solvents salts air fresheners and other household products CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in personal injury or death The operation of exhaust fans kitchen ventilation fans clothes dryers attic exhaust fans or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace Make up...

Page 10: ...e o40o _ 15ft3 I fan VolumeFan ACH 000 Btu hr If Iother combined input of all other than fan assisted appliances in Btuh hr Ifan combined input of all fan assisted appliances in Btuh hr ACH air changes per hour ACH shall not exceed 0 60 The following requirements apply to the Standard Method and to the Known Air Infiltration Rate Method 1 Adjoining rooms can be considered part of a space if a Ther...

Page 11: ...minimum dimension of air openings shall be not less than 3 in 80 mm Table 3 Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors TWO HORIZONTAL DUCTS SINGLE DUCT OR OPENING TWO OPENINGS OR VERTICAL DUCTS 1 SQ IN 2 000 BTUH 1 SQ IN 3 000 BTUH FURNACE 1 100 SQ MM KW 734 SQ MM KW 1 SQ IN 4 000 BTUH 550 SQ MM KW INPUT Round Round BTUH Free Area of Duct Free Area of Open Duct ...

Page 12: ...ot necessary to relocate the condensate trap or associated tubing Refer to Figure8 for upflow condensate trap information Refer to Condensate Drain section for information how to install the condensate drain Condensate Trap Downflow Orientation When the furnace is installed in the downflow position the condensate trap will be initially located at the upper left corner of the collector box as recei...

Page 13: ...rts of the collector box _ Connect relief tube to port on collector box _ Rotate elbow to desired position and tighten clamp to 15 lb in _ Slide tube in stand offs to adjust length Connect the new pressure switch tube from Loose Parts bag to _ Route tube through inducer port on front pressure switch _ stand offs to adjust position of the tube r___ k N Trim excess tube X J Connect Pressure switch t...

Page 14: ... between the casing side and the furnace platform for the trap to extend out of the casing in the horizontal position Allow at least 1 4 in per foot 20mm per meter of slope down and away from the furnace in horizontal sections of drain line To Relocate the Condensate Trap Remove the knockout in the casing for the condensate trap Install the grommet in the casing when required for direct vent horiz...

Page 15: ...y vary in appearance Unconverted Factory Configuration as viewed in the Horizontal Left Orientation Remove the screw that secures the condensate trap to the collector box and remove trap If alternate vent position is required loosen clamp on vent elbow inlet Remove relief tube from relief port on condensate trap Remove front pressure switch tube and discard A new tube is shipped in the Loose Parts...

Page 16: ...a which may drop below freezing This can cause improper operation or damage to the equipment If the furnace environment has the potential of freezing the drain trap and drain line must be protected A self regulating shielded and waterproof heat tape rated at 3 to 6 watt per foot 10 to 20 watt per meter at 115 volt 40 F 4 C may be used to help provide freeze protection Wrap the drain trap and drain...

Page 17: ...side of the casing and behind the inducer or gas valve Allow the Z pipe to temporarily rest on the blower shelf upflow or burner box downflow NOTE When the inducer housing has been removed to ease installation in upflow applications this step is not needed 7 After inserting the Z pipe through the casing slide a spring clamp over each end of the Z pipe 8 From inside the casing insert the short end ...

Page 18: ...bow or grommet on the outside the furnace casing 9 Open the spring clamp and insert the long end of the adapter or the 1 2 in CPVC pipe into the outlet stub on the drain elbow 10 Connect additional condensate piping to a code approved drain or to a condensate pump approved for use with acidic furnace condensate and compatible with mineral and vegetable oils such as canola oil Allow at least 1 4 in...

Page 19: ...istance or a probe can be inserted for sampling the air stream The cover attachment shall prevent leaks Connect supply air duct to flanges on furnace supply air outlet Bend flange upward to 90 with wide duct pliers See Figure 22 The supply air duct must be connected to ONLY the furnace supply outlet air duct flanges or air conditioning coil casing when used DO NOT cut main furnace casing side to a...

Page 20: ...osure panel if removed DOWN FLOW INSTALLATION NOTE The furnace must be pitched as shown in Figure 18 for proper condensate drainage Supply Air Connections NOTE For downflow applications this furnace is approved for use on combustible flooring when any one of the following two accessories are used see specification sheets for list of approved accessories Special Base NAHA01101SB Cased Coil Assembly...

Page 21: ... this warning could result in personal injury death or property damage Do not install the furnace on its back or hang furnace with control compartment facing downward Safety control operation will be adversely affected Never connect return air ducts to the back of the furnace MINOR PROPERTY HAZARD Failure to follow this caution may result in minor property damage Local codes may require a drain pa...

Page 22: ...le or Noncombustible Flooring 19 1 2 21 5 8 20 1 8 22 1 4 subbase not required 495 549 511 565 Downflow Applications on Noncombustible Flooring 19 3 8 19 20 19 5 8 21 subbase not required 492 483 508 498 533 Downflow applications on combustible flooring 18 5 8 19 20 t 4 20 5 8 subbase required 473 483 514 600 Downflow Applications on Combustible Flooring with Coil Assembly or coil 19 19 20 20 box ...

Page 23: ...d over a finished ceiling Figure 26 I Working Platform for Attic Installation COMBUSTION AIR PIPE SEE VENTING SECTION VENT A 12 1N 305 ram MIN HORIZONTAL PIPE SECTION IS RECOMMENDED WITH A SHORT 5 TO 8 FT 1 5 TO 2 4 M VENT SYSTEM TO REDUCE EXCESSIVE CONDENSATE DROPLETS FROM EXITING THE VENT PIPE 30 762 mm Min Work Area MANUAL SHUTOFF GAS VALVE INDOOR COIL ROLLOUT PROTECTION REQUIRED Install 1 2 x ...

Page 24: ...on return duct prior to entering the return air opening in any orientation See Table 6 for recommended filter size details Table 6 Filter Size Information in mm FILTERSIZE FURNACE CASING WIDTH FILTER TYPE BOTTOM RETURN 14 x 25 x 3 4 356 x 635 x 19 16 x 25 x 3 4 406 x 635 x 19 20 x 25 x 3 4 508 x 635 x 19 24 x 25 x 3 4 610 x 635 x 19 SIDE RETURN 14 3 16 16 x 25 x 3 4 Washable 360 406 x 635 x 19 17 ...

Page 25: ... 472 566 661 755 850 944 1038 Representative After Market Filter Media Fiberglass Pleated CFM 1 in 2 5 cm 2 in 5 cm 1 in 2 5 cm 2 in 5 cm 800 0 05 12 0 07 18 0 17 43 0 11 28 1000 0 06 16 0 09 24 0 22 55 0 15 37 1200 0 08 20 0 12 31 0 27 68 0 18 47 1400 0 10 24 0 15 38 0 23 58 1600 0 11 29 0 18 45 0 28 69 1800 0 13 34 0 21 53 2000 0 16 39 0 24 61 2200 0 18 45 0 28 70 Representative estimates from f...

Page 26: ...AIR i SUPPLY AIR i NOTE RESTRICTION SAME FOR HORIZONAL LEFT RETURN AIR HORIZONAL RETURN AIR RESTRICTIONS SIDE RETURN AIR NOT PERMITTED FOR 2000 CFM AND ABOVE OF AIR FLOW L10F034 External Filter Cabinet Configurations Figure 30 _Accessory Bottom Filter Rack 0 22 5 16 566 4 o o o o B A A 28 7 16 722 2 e e e e 2 3 t 6 55 5 L10F031 Table 9 Dimensional Drawing in mm FURNACE KIT NO A B WIDTH NAHB00501FF...

Page 27: ... When air conditioning is used a vapor barrier is recommended Maintain a 1 in 25 mm clearance from combustible materials to supply air ductwork for a distance of 36 in 914 mm horizontally from the furnace See NFPA 90B or local code for further requirements Return Duct Sizing Refer to the Filter Selection and Duct Sizing section for information on the proper selection of filter sizes and the associ...

Page 28: ...e FURNACE DAMAGE HAZARD Table 10 NOMINAL IRONPIPE SIZE IN aM 1 2 13 3 4 19 1 25 1 1 4 32 1 1 2 39 Maximum Capacity of Pipe INTERNAL DIA IN aM 0 622 158 0 824 20 9 1 049 26 6 1 380 35 0 1 610 40 9 LENGTH OF PIPE FT M 10 20 30 40 50 3 0 6 0 9 1 12 1 15 2 175 120 97 82 73 360 250 200 170 151 680 465 375 320 285 1400 950 770 660 580 2100 1460 1180 990 900 Cubic ft of gas per hr for gas pressures of 0 ...

Page 29: ...plications For Direct Vent Applications A1133E ELECTRICAL CONNECTIONS ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failure to follow safety warnings could result in dangerous operation serious injury death or property damage Improper servicing could result in dangerous operation serious injury death or property damage Before servicing disconnect all electrical power to furnace When servicing controls...

Page 30: ...re to follow this warning could result in personal injury death or property damage Do not connect aluminum wire between disconnect switch and furnace Use only copper wire SWITCH Al1146 Use a separate fused branch electrical circuit with a properly sized fuse or circuit breaker for this furnace See Table 11 for wire size and fuse specifications A readily accessible means of electrical disconnect mu...

Page 31: ...ZARD Failure to follow this warning could result in personal injury death or property damage If field supplied manual disconnect switch is to be mounted on furnace casing side select a location where a drill or fastener cannot damage electrical or gas components The J Box is used when field line voltage electrical connections are made to the furnace wiring harness inside the furnace casing The J B...

Page 32: ...igure 38 I Field Supplied Electrical Box on Furnace Casing GROUNU NEUTRAb A10141 Power Cord Installation in Furnace J Box NOTE Power cords must be able to handle the electrical requirements listed in Table 11 Refer to power cord manufacturer s listings 1 Install J Box mounting bracket to inside of furnace casing See Figure 37 2 Route listed power cord through 7 8 in 22 mm diameter hole in casing a...

Page 33: ...ximum and are energized during blower motor operation 2 Humidifier HUM F G 9MXT There are two humidifier outputs on the furnace control The 115 VAC HUM terminal is energized when the Induced Draft Relay closes The 24 VAC HUM terminal is energized when the low pressure switch closes during a call for heat Connect an accessory 115 VAC accessory humidifier to the HUM terminal and L2 on the furnace co...

Page 34: ...ly MINIMUM WIRE SIZE AWG 14 14 14 14 14 12 12 12 BLOWER FURNACES UNIT AMPACITY 10 3 10 3 10 4 14 3 13 5 17 3 17 7 15 9 MINIMUM WIRE SIZE AWG 14 14 14 14 14 12 12 12 MAXIMUM WIRE LENGTH FT M 36 11 0 36 11 0 35 10 7 26 7 9 27 8 2 33 10 1 32 9 8 36 11 0 MAXIMUM WIRE LENGTH FT M 36 11 0 36 11 0 35 10 7 26 7 9 27 8 2 33 10 1 32 9 8 36 11 0 MAXIMUM FUSE OR CKT BKR AMPS_ 15 15 15 15 15 20 20 20 MAXIMUM F...

Page 35: ...L_ COiNECTION 115 VAC _ _S_RMER Etf C vTAEcR M1I 0N AALM p MOTORI CONNECTION L1 BL 1 XFMR HUM s_ LO I I 115 VAC LINE L1 115 VAC RUM INPUT L12F037 Figure 41 1Example of Single Stage Furnace Control for ECM Blower Motor F G 9MXE HEAT OFF DELAY 24 V THERMOSTAT TERMINALS 3 AMPFUSE LED OPERATION DIAGNOSTIC LIGHT HEAT BLOWER SPEED _ SELECTION TERMINALS 115 VAC L2 NEUTRAL CONNECTIONS TEST TWIN TWINNING A...

Page 36: ...fiees ce standard Au Canada I appr_t et le ciment doivent _tre du m_me fabricant que le systeme d evacuation L appr_t GVS 65 Purple et le ciment solvant GVS 65 doivent _tre utilise avec les Royal Pipe Systeme IPEX 636 appr_t PVC CPVC Purple pour evacuation des gaz de combustion et systeme IPEX 636 1 t ciment PVC pour evacuation des gaz de combustion cote classe IIA 65 deg C doivent _tre utilises a...

Page 37: ...PolyPro polyproplylene venting systems are ULC S636 listed NOTE When using polypropylene venting systems all venting materials used including the vent terminations must be from the same manufacturer Venting Systems CARBON MONOXIDE POISONING HAZARD Failure to follow the instructions outlined in Locating the Vent Termination for each appliance being placed into operation could result in carbon monox...

Page 38: ...r pipe to the outdoors is not required for a single pipe vent system A 12 in 304 mm long pipe with a 2 in 50 mm Nominal Dimension ND tight radius 90 degree elbow is required to be attached to the combustion air pipe adapter on the furnace See Figure 57 This short inlet air pipe helps to ensure stable combustion as well as allow for sound attenuation To aid sound attenuation point the inlet air pip...

Page 39: ...PRIMERS Solvent Cement Solvent Cement Solvent Cement Primer Figure 43 DESCRIPTION Schedule 40 Schedule 40 For ABS SDR 21 SDR 26 Schedule 40 Schedule 40 For PVC DWV at Schedule 40 IPS sizes DWV Schedule 40 Schedule 40 SDR For CPVC Cellular Core DWV at Schedule 40 IPS sizes For PVC Cellular Core Schedule 40 DWV Vent Pipe Flush with Adaptor VENT PIPE ADAPTER WITH GASKET INSTALLED ON FURNACE VENT PIPE...

Page 40: ... operation for the structure provisions for adequate combustion ventilation and dilution air must be provided in accordance with U S A Installations Section 9 3 NFPA 54 ANSI Z223 1 1 2012 Air for Combustion and Ventilation and applicable provisions of the local building codes Canadian Installations Part 8 of CAN CSA B149 1 10 Venting Systems and Air Supply for Appliances and all authorities having...

Page 41: ...EN BOTTOM OF COMBUSTION AIRAND BOTTOM OF VENT 12 IN 305 MM ABOVE ANTICIPATED SNOW LEVEL A13078A Sample Inlet Air Pipe Connection Figure 46 for Polypropylene Venting Systems EXAMPLE FOR UPFLOW INSTALLATIONS MAY BEAPPLIED TO OTHER CONFIGURATIONS A12220 Figure 47 _Vent Terminations OPTIONAL BRACKET _ COMBUSTION AIR ELBOW PARALLEL TO WALL COMBUSTION AIR AND BOTTOM OFVENT 305 MM CLEARANCEABOVE HIGHEST ...

Page 42: ... termination of less than 12 in SO5mm above highest snow level g14mm g14mm 12 in 3O5mm separation between bottom of corn bustion air and bottom of vent Typ Maintain 12 in 3O5mm min Clearance abo_e highest an ticipated snow level or grade whichever is greater Typ Note in A denotes O To 2 in 51 mm Between the first 2 vents Third vent and fourth vent if used must be 36 in Away g14mm L12F044 Figure 49...

Page 43: ...nnections The tee may also be connected to the intake air pipe on the side of the casing See Figure 51 In any configuration it will be necessary to add the equivalent length of the tee 15 feet 5 M to the Total Equivalent Vent Length of the venting system Figure 50 NOT IN HORIZONTAL SECTION Combustion Air and Vent Pipe Diameter Transition Location and Elbow Configuration FURNACE J TRANSITION IN SEC...

Page 44: ...gure 51 I Optional Combustion Air Inlet Moisture Trap 1 pipe chosen then that diameter of pipe selected may be used b If the Total Vent Length is I_ngerthan the Maximum Equivalent Vent Length for the diameter of pipe chosen that diameter pipe MAY NOT be used for venting the furnace Try the next larger diameter pipe NOTE If the calculated Total Equivalent Vent Lengths results in different diameter ...

Page 45: ...sult in the circulation of carbon monoxide throughout the structure The vent pipe and combustion air pipe must be a continuous pipe while passing through the blower compartment Seals supplied in this kit must be installed per the instructions provided Follow all 3rocedures outlined in these instructions Install the Vent and Combustion Air Pipes With the furnace installed in the required position r...

Page 46: ...FIGURATION Representative drawing only some models may vary in appearance Al1310 See NOTES following figures Figure 54 I Downflow Configurations _ Rotate ventelbow to DOWNFLOW LEFT VENT CONFIGURATION Representative drawing only some models may vary in appearance Alt3tt Rotate vent elbow to required position DOWNFLOW RIGHT VENT CONFIGURATION Representative drawing only some models may vary in appea...

Page 47: ...rawing only some models may vary in appearance See NOTES following figures Figure 56 1Horizontal Right Configurations COMBUSTION CONNECTDNS A11337 HORIZONTAL RIGHT VERTICAL VENT CONFIGURATION Representative drawing only some models may vary in appearance A11336 HORIZONTAL RIGHT LEFT VENT CONFIGURATION Representative drawing only some models may vary in appearance ALTERNATE COMBUSTION AIR A11335 HO...

Page 48: ...ROPYLENE VENT PIPING SYSTEMS See the polypropylene vent system manufacturer s instructions for installing polypropylene venting systems Install the remaining vent and combustion air pipes as shown below It is recommended that all pipes be cut prepared and preassembled before permanently cementing any joint 1 Working from furnace to outside cut pipe to required length s 2 De burr inside and outside...

Page 49: ...he rubber vent coupling 11 Slide the end of the coupling with notches in it over the standoffs in the vent pipe adapter 12 Tighten the clamp of the coupling over the vent pipe adapter Torque the lower clamp around the vent pipe adapter to 15 Ib in 13 Pilot drill a 1 8 in hole in the combustion air pipe adapter 14 Complete the vent and combustion air pipe as shown in Install the Vent and Combustion...

Page 50: ...embly through sidewall with rain shield positioned no more than 1 in 25 mm from wall as shown in Figure 48 5 Disassemble loose pipe fittings Clean and cement using same procedures as used for system piping DO NOT CEMENT POLYPROPYLENE FITTINGS Two Pipe and Single Pipe Vent Termination NOTE Follow the instructions of the vent terminal manufacturer These instructions are provided as a reference only ...

Page 51: ...gar Ventilated Combustion Air intake termination in crawl space 3 76 mm t 12 305 ram CRAWL SPACE Figure 59 _Attic Vent Termination t throuhgb __ _ roof flashmng Ventilated Combustion Air intake pipe 7 L11F016A ATTIC L11F016B 440 01 4001 08 Specifications subject to change without notice 51 ...

Page 52: ...r balcony Permittedonly if veranda porch deck or balcony isfully openon a minimumof two sides beneath thefloor Manufacturer sRecommendation See Notes 3 8 Clearanceto each side of the centerlineextendedabove or M below ventterminal of the furnace to adryer or water heater 12 in 305 ram 12 in 305 ram vent or other appliance svent intake or exhaust Furnace combustionair intake clearanceto awater heat...

Page 53: ...ee Note 4 L Clearanceundera veranda porch deck or balcony Permittedonly if veranda porch deck orbalcony is fully open on a minimumof two sides beneaththe floor Manufacturer sRecommendation See Notes3 8 Clearanceto each side of the centerline extendedaboveor M belowventterminal of the furnace to a dryer or waterheater 12 in 305 ram 12 in 305 ram vent orother appliance s directvent intake or exhaust...

Page 54: ... 2 228 69 5 56 17 1 150 45 7 202 61 6 224 17 5 2 94 28 7 205 62 5 229 83 25 3 217 69 21 0 146 DEDUCTIONS FROM MAXIMUM EQUIVALENT VENT LENGTH Feet Meters Pipe Diameter in 1 1 2 Mitered 90 0Elbow 8 2 4 Medium Radius 90 0Elbow 5 1 5 Long Radius 90 0Elbow 3 0 9 Mitered 45 0Elbow 4 1 2 Medium Radius 45 0Elbow 2 5 0 8 Long Radius 45 0Elbow 1 5 0 5 Tee 16 4 9 Concentric Vent Termination Standard Vent Ter...

Page 55: ...00 long radius elbows and a polypropylene concentric vent kit Also includes 20 feet 6 1 M of flexible polypropylene vent pipe included within the 100 feet 30 M of vent pipe Assume that one meter of flexible 60mm or 80mm polypropylene pipe equals 1 8 meters of PVC ABS pipe VERIFY FROM VENT MANUFACTURER S INSTRUCTIONS Can this application use 60mm o d polypropylene vent piping If not what size pipin...

Page 56: ... 1 130 39 6 60 000 I 7 2 1 I 82 25 0 1 152 46 3 168 51 2 8001 to 9000 80 000 35 10 7 I 111 33 8 148 45 1 156 47 5 2438 to 2743 100 000 67 20 4 157 47 9 170 51 8 120 000 56 17 1 164 50 0 140 0004 23 7 0 42 12 8 40 000 I 5 1 5 I 110 33 5 I 115 35 1 60 000 76 23 2 I 142 43 3 156 47 5 9001 to 10 000 80 000 31 9 4 I 103 31 4 137 41 8 142 43 3 2743 to 3048 100 000 62 18 9 147 44 8 157 47 9 120 000 51 15...

Page 57: ... 21 3 47 9 40 5 32 6 80 000 Ft 20 25 23 14 1 20 70 94 77 57 20 70 113 94 71 20 30 M 6 1 7 6 7 0 4 3 0 3 6 1 21 3 28 7 23 5 17 4 6 1 21 3 34 4 28 7 21 6 Ft 20 14 12 3 0 20 70 71 56 38 20 70 86 70 50 40 40 M 6 1 4 3 3 7 0 9 0 0 6 1 21 3 21 6 17 1 11 6 6 1 21 3 26 2 21 3 15 2 Ft N A 25 99 89 78 N A 25 110 233 265 N A 25 110 235 229 20 10 M N A 7 6 30 2 27 1 23 8 N A 7 6 33 5 71 0 80 8 N A 7 6 33 5 71...

Page 58: ...147 0 20 10 M 6 1 19 5 19 5 17 1 14 3 6 1 21 3 52 7 45 7 38 1 6 1 21 3 53 3 53 9 44 8 Ft 20 0 32 0 30 0 22 0 11 0 20 0 70 0 104 0 87 0 67 0 20 0 70 0 124 0 104 0 82 0 0 20 M 6 1 9 8 9 1 6 7 3 4 6 1 21 3 31 7 26 5 20 4 6 1 21 3 37 8 31 7 25 0 80 000 Ft 20 0 17 0 14 0 6 0 0 0 20 0 70 0 71 0 57 0 40 0 20 0 70 0 86 0 71 0 52 0 20 30 M 6 1 5 2 4 3 1 8 0 0 6 1 21 3 21 6 17 4 12 2 6 1 21 3 26 2 21 6 15 8...

Reviews: