4.4 SHUTS OFF ON LOW PRESSURE CONTROL
A.
Low or no water flow through the evaporator. Adjust the flow per section 3.2.C
B.
Air-cooled units:
1.
Low pressure too low. Contact factory or local refrigeration technician for
assistance
C.
Low refrigerant charge. Check for adequate refrigerant charge (bubbles or misty
sight glass indicates low charge). If charge is low, have system checked for leaks and
recharged by a refrigeration serviceman.
D.
Improperly set low pressure limit. Reset setting on control instrument per factory
service recommendations.
E.
Restriction in the liquid line.
1.
Clogged filter drier. Check for pressure or temperature drop and have drier core
replaced by a refrigeration serviceman.
2.
Liquid line valve or suction valve on compressor is partially closed. Open
fully.
3.
Liquid line solenoid not opening fully or leaking during off cycle. Have the
solenoid repaired or replaced if defective by a refrigeration serviceman.
4.
Expansion valve plugged or inoperative. Check thermal bulb and capillary
tube for damage. Have repaired or replaced if defective by a refrigeration service
man.
4.5 COMPRESSOR SHUTS OFF ON INTERNAL OVERLOAD
A.
Control does not reset. Have compressor windings and internal solid state safety
control checked by a refrigeration serviceman. Have it repaired or replace if defective.
4.6 LOW OR NO PROCESS PRESSURE OR WATER FLOW
A. Valves. Check if water valves are open.
B. Pump.
Check pump for correct rotation. Check pump suction for restriction. Replace
motor if defective.
C. Filters. Check filter in the chilled water circuit and clean if necessary.
D.
Pressure switch (or flow switch). Readjust or replace if defective.
E.
Fuses and wiring. Have electrician check the fuses and wiring.
Summary of Contents for BG-N4 Series
Page 2: ......
Page 6: ...Page 6 THIS PAGE INTENTIONALLY BLANK ...
Page 12: ...Page 12 THIS PAGE INTENTIONALLY BLANK ...
Page 20: ...Page 20 THIS PAGE INTENTIONALLY BLANK ...
Page 40: ...Page 40 THIS PAGE INTENTIONALLY BLANK ...
Page 46: ...Page 46 THIS PAGE INTENTIONALLY BLANK ...
Page 54: ...Page 54 THIS PAGE INTENTIONALLY BLANK ...
Page 75: ...END 2021 Temptek Inc RE 20210218 ...
Page 76: ......