At full load, the chiller will discharge
approximately 15,000 BTU’s per hour per
ton of cooling.
E.
On blower units, air discharge duct work
should be sized by a qualified HVAC
engineer. Sizing shall be according to
rated CFM at the static pressure of .90
inches of water. See figure at right.
F.
On blower units, a damper control
assembly is required in low ambient
temperature areas or when outdoor air
make-up is used. The assembly works
in conjunction with refrigerant head
pressure to regulate air flow to maintain
proper refrigerant head pressure when
condenser intake air temperature will be
less than 60°F. See figure to the right.
G.
All air cooled units MUST have all enclosure panels in place before operating
compressor. Air will not be drawn through the condenser coil if the panels are not in
place. Starting the unit without the enclosure panels in place will result in a refrigerant
fault.
H.
Condenser Air Filtering. Use a filter that produces very low air flow restrictions.
Generally a disposable fiberglass filter with a MERV rating of 2 - 3 provides adequate air
filtration. The purpose of the filter is to prevent large particles such as dust, lint and debris
from fouling the condenser. You should be able to see through the filter media. Using
restrictive filter media can cause loss of chiller capacity, difficulty running in warm weather
and fan motor overheating.
WARNING: Do not attempt to duct exhaust air from a portable chiller using motor driven fans.
Exhaust air can only be ducted from a portable chiller using a blower assembly.
Damper assembly
Punch hole
in top panel
1/4" Copper line
Optional
Liquid receiver
(located inside
chiller on base)
Angle valve and cap
1/4" copper line connection
Typical Filter materials.
Typical Filter shown on 10 ton air-cooled unit.
WARNING: Do not attempt to start or operate an air-cooled portable chiller without all cabinetry
panels in place. Air-cooled chillers require air to be drawn through the air-cooled condenser. This
will not occur if the panels are not in place.