Observe the motor shaft. When the ON/
OFF SWITCH is on, the motor shaft
will rotate. When switched off, the shaft
will slowly “coast” to a stop. As the
shaft slows, the operator can identify
the rotation of the motor shaft. Correct
rotation (correct phase) is “clockwise”,
when viewed from the rear of the motor.
Incorrect rotation is “counter-clockwise”
(incorrect phase) when viewed from the
rear of the motor. If the shaft does not
rotate when the ON/OFF SWITCH is on,
the operator must identify the cause as outlined in the troubleshooting
and repair section of this manual.
f.
If the motor shaft is phased correctly (shaft turns in a clockwise direction),
continue with step C. If the motor shaft is NOT phased correctly (shaft turns in a
counter-clockwise direction), correct as outlined in step 2.
2.
If the unit is phased incorrectly, the operator must:
a.
Disengage the electrical power supply to the unit at the unit’s disconnect
switch. Follow all facility proper lock-out tag-out procedures before
proceeding.
b.
Once the electrical power supply is disengaged the operator can change
rotation by switching any two power conductors at the terminal block or
customer supplied main power disconnect.
Correct shaft rotation is clockwise.
Power Entry Terminal Block
Switch power wires at
this terminal block only.
Typical electrical panel