Low Pressure Fault. After the compressor is
turned on, the control has a 15 second buffer for
the low pressure fault. If a low pressure condition
occurs within the first 15 seconds, the control
waits the amount of time specified by the “LP
TIME” potentiometer before indicating an fault
and turning off the compressor. If the condition is
corrected before the time expires, no fault occurs.
If a low pressure condition occurs 15 seconds
after the compressor turns on, the instrument
waits 20 seconds before indicating a fault and
turning off the compressor.
Note: refer to section 4.4 of this manual for additional Low Refrigerant Pressure
troubleshooting.
E.
TEMPERATURE DISPLAY
1.
A three digit display window indicates the appropriate temperature. The window
also displays the numeric value for the setpoint temperature.
2.
The To Process temperature is always displayed unless a button has been
pressed. If there is a probe error, the display will show three dashes “---”.
3.
When the water temperature in the chiller is above approximately 100°F the
display will show three dashes “---”.
F.
PRESSURE GAUGES
1.
PROCESS PRESSURE GAUGE: Indicates process pump pressure.
2.
REFRIGERANT HEAD PRESSURE GAUGE: Indicates refrigerant pressure on
the discharge side of the compressor. The refrigerant head pressure is also the
condensing pressure which is critical to equipment efficiency.
3.
LOW PRESSURE GAUGE: Indicates refrigerant pressure on the suction side of
the compressor. This pressure will fluctuate with the process temperature.
Low Pressure Potentiometer.
Pressure
gauges
15 ton air-cooled portable chiller
shown.
10 ton air-cooled portable
chiller shown.
Pressure
gauges