Air in the system will adversely affect the unit’s ability to control process temperature and
can cause heater failure when the heating elements are exposed to this air.
C.
Autovent Time.
This is the time duration of the autovent.
1.
Press the Select button to select Autovent Time item.
2.
Use the Up or Down arrow buttons to select the duration of the autovent. The
range is 0 - 300 seconds. The factory default is 45 seconds.
3.
Press the Select button to save the Autovent time and confirm success.
D.
Autovent Temp.
This is the process temperature when an autovent can be initiated. On
start up, the controller checks the Autovent Temp. If the process temperature is below this
value, the autovent will occur. If above this value the autovent will not occur.
1.
Press the Select button to select Autovent Temp item.
2.
Use the Up or Down arrow buttons to select the temperature of the autovent.
This is the temperature which, if the process temperature is below, will initiate an
autovent on startup. The range is 0°F - 250°F. The factory default is 100°F.
3.
Press the Select button to save the Autovent temp and confirm success.
E.
What is Pump Seal Cooling.
Pump seal cooling is a feature that automatically cools the
unit to a preselected temperature when the stop button is pressed.
It is a good shut down practice to cool the unit prior to turning the unit off. The pump seal
cooling feature automates this process. It is believed that pump seal life can be extended
by cooling the unit prior to shutdown. This features opens the cooling valve to discharge
hot process water to drain to cool the unit.
When activated, the pump seal cooling features is engaged by pressing the stop button
once. The cooling valve will open and the pump will continue to run until the pump seal
cooling temperature or time limit is met. To stop the unit at any time during this sequence
press the stop button again.
WARNING:
When the pump seal cooling feature is activated, pressing the stop button will not
turn off the unit. To completely shut down the unit, press the Stop button twice.
Summary of Contents for Veteran VT LXG Series
Page 2: ......
Page 6: ...Page 6 THIS PAGE INTENTIONALLY BLANK ...
Page 20: ...Page 20 THIS PAGE INTENTIONALLY BLANK ...
Page 42: ...Page 42 THIS PAGE INTENTIONALLY BLANK ...
Page 48: ...Page 48 THIS PAGE INTENTIONALLY BLANK ...
Page 68: ...Page 68 THIS PAGE INTENTIONALLY BLANK ...
Page 95: ...END 2021 TEMPTEK INC RE 20210323 ...
Page 96: ......