Figure-89
Figure-87
Figure-86
Figure-30
13.4 - RS485 RS485 Settings:
Figure-29
Figure-84
Figure-84
Figure-85
Figure-85
Figure-83
Figure-83
Esc
Set
Esc
Set
-15-
Press Menu button and enter password to enter program list. The figure-26(Voltage SET) is displayed
when you enter password and press the Menu button. The figure-27(Current SET) is displayed when you
press the up button. The figure-28(Frequency SET) is displayed when you press the up button. The figure-29
(RS485 SET) is displayed when you press the up button. You enter Rs-485 set when you press Menu button.
If you enter Rs-485 set menu, the figure-83(Pr.52) displayed. This menu have 2 different current set value.
When you press the up button to see the other Frequency set values on the display, the next data is
displayed. By using up-down buttons select the program. Press Menu to enter required program. By
up-down buttons, you can set the program. Press Menu to record your settings, if you press ESC button,
you cannot record your settings.
Press Menu button and enter password to enter program list. The figure-26(Voltage SET) is displayed
when you enter password and press the Menu button. The figure-27(Current SET) is displayed when you
press the up button. The figure-28(Frequency SET) is displayed when you press the up button. The figure-29
(RS485 SET) is displayed when you press the up button. The figure-30(General SET) is displayed when you
press the up button. You enter General set when you press Menu button. If you enter General set menu, the
figure-85(Pr.54) displayed. This menu have 6 different current set value. When you press the up button to
see the other General set values on the display, the next data is displayed. By using up-down buttons select
the program. Press Menu to enter required program. By up-down buttons, you can set the program. Press
Menu to record your settings, if you press ESC button, you cannot record your settings.
Pr.52: Modbus ID:
Determines Modbus device ID.
Default:
1,
Min:
1,
Max:
247
Note:
Stopbits: 1
,
Party: none
and
Databits:8
Pr.54: Password Change:
This menu is used for changing the user password.
Default:
0000,
Min:
0000,
Max:
9999
Pr.53: Baudrate Selection:
Determines Modbus communication speed
.
Default:
9600bps,
Min:
1200bps,
Max:
38400bps
13.5 - General Settings:
Figure-88
Figure-90
Figure-86
-16-
Pr.55: Password Protection Enable/Disable:
This menu is used for activating the user
password. After the user password is activated for entering to the menus; if the Menu
button is pressed, while the instant values are observed, user password is required.
Default:
Disable,
Min:
Disable,
Max:
Enable
Pr.56: Phase Sequence Protection Enable/Disable:
You can use device with phase
sequence or without phase sequence function. If you set device for phase sequence, when
running, it will be check phase sequence and it will display sequence error on screen.
If you set “Disable” You can see phase sequence error but device not give error.
Default:
Disable,
Min:
Disable,
Max:
Enable
Pr.57: Demand Time:
Determines demand calculate time. Demand is calculated using
average value. Device take sample for demand time and calculate average value.
Demand is maximum average value.
Default:
15min,
Min:
1min,
Max:
120min.
Pr.59: Current Transformer Cable Turn Number:
User defines the turn number, which
is the number of how much tour the current cable has rounded into the current
transformer. Numbers can be selected between 1-20. Greater the number of turn means
greater the sensitivity
Default:
1,
Min:
1,
Max:
20.
Pr.58: Demand Record Delete:
You can delete demand and average records.
If cut off device energy min,max, average and demand values are deleted.
Figure-87
Figure-88
Figure-89
Figure-90
13.6 - About:
Figure-31
Figure-92
Figure-91
Press Menu button and enter password to enter program list. The figure-26(Voltage SET) is displayed
when you enter password and press the Menu button.
The figure-27(Current SET) is displayed when you press the up button.
The figure-28(Frequency SET) is displayed when you press the up button.
The figure-29(RS485 SET) is displayed when you press the up button.
The figure-30(General SET) is displayed when you press the up button.
The figure-31(About) is displayed when you press the up button.
You enter “About” when you press Menu button. If you enter “About” menu, the figure-91(Pr.61) displayed.
When you press the up button to see the other parameter on the display, the next data is displayed.
Step 1
:
Press “SET” button for entering menu.
Step 2:
If Password is activated ,you can see “PASS” screen, you have to enter user password. There are
four digit and press “Down” button ,selected digit is chan
g
e. You can increase digit value using “Up” button.
Press “Set” button after enter the user password. If you back to home screen you press “ESC”button.
Default password is “0000”.
14- Enter Menu with Password:
Step 1
L1
L2
L3
V
A
A
A
I