11
50 /50
26
-20°C do +40 °C
80
50 /50
14
110
50 /50
4
125
50 /50
26
-20°C do +50 °C
70
50 /50
14
95
50 /50
4
100
Maksimalni mogući broj rednih
stezaljki određenog mjerama kućišta
Maximum possible number of
terminals definite by enclosure
dimensions
100
86
66
50
40
40
30
26
Širina redne stezaljke [mm]
Width of single terminal [mm]
5
6
7
10
12
12
15
18,5
Dozvoljeni priključak vodiča na rednu
stezaljku
Allowed cross-section of conductor
for single terminal
1x2.5-1 .5
mm2
1 x4-1.5
mm2
1 x6-1.5
mm2
1 x10-2.5
mm2
1 x16-2.5
mm2
1 x 25-6
mm2
1 x 35-6
mm2
1 x 50-
10 mm2
Širina PE stezaljke [mm]
Width of PE terminal [mm]
5
6
7
10
12
12
15
18,5
Širina završne stezaljke [mm]
Width of end holder
9
Prostor za stezaljke na DIN nosaču
bez završnih stezaljki
Space for terminals on DIN rail
without end holders
max. 500 mm
PE stezaljke i kratkospojne stezaljke ne ulaze u maksimalni dopušteni broj rednih stezaljki.
PE terminals and shorting links are not included in the maximum number of terminal blocks.
Na rednu stezaljku je dopušten priključak vodiča manjeg
nazivnog presjeka s time da se poštuje maksimalni broj
stezaljki i maksimalna struja za taj nazivni presjek
vodiča/stezaljki prema Tablicama dozvoljenih ugradnji.
Nije dopušten priključak dvaju ili više vodiča pod jedan
kontakt redne stezaljke bilo da se priključuju direktno,
bilo preko zajedničke krajnje stopice.
Višeredna montaža rednih stezaljki je dopuštena uz
poštivanje tablice dozvoljene ugradnje.
Dopuštena je kombinacija više različitih nazivnih
presjeka rednih stezaljki/vodiča u jednom kućištu.
Moguća kombinacija se izračunava prema tablicama
dopuštenih ugradnji na način da se izračunom
provjeravaju ukupni maksimalni gubici i fizička
mogućnost ugradnje, kako je dano u primjeru:
At each terminal is allowed connection of conductors
smaller than nominal cross section taking into account the
maximum number of terminals and the maximum current
for the nominal conductor size / terminal according to
Tables of allowed installation.
It is not allowed connection of two or more conductors
under one contact of single terminal or connection directly
with ferrules.
Installation of two or more rows of terminals is allowed
taking into account the Table of allowed installation.
A combination of several different nominal cross-section
terminal blocks / conductors in a single enclosure is
allowed. Possible combinations are calculated according to
the tables of allowed installation so that the calculation of
the total maximum power loss and the possibility of a
physical is in accordance with tables of allowed installation,
as given in the example:
Primjer: SKX 20/E -20°C < Tamb < +40°
Example: SKX 20/E -20°C < Tamb < +40°
Presjek [mm²] vodiča i stezaljke
Cross-section [mm²] of conductors
and terminals
Struja [A]
Current [A]
Broj rednih
stezaljki
Number of
terminals
Max. dopušteni br.stezaljki prema
tablici dopuštene ugradnje
Max.allowed nr. of terminals
according to table of allowed
installation
Iskorištenost
Usage
10
34
10
36
27,8 %
6
16
20
98
20,4 %
4
12
20
122
16,4 %
2,5
9
20
126
15,9 %
Ukupni gubici (Total losses):
80,5 % < 100%