KRB-5200h
-13-
4. OPERATION
4.1 Direct-Manual Operation
Warning
Never touch live terminal parts
Otherwise, electric shock may result.
ON
OFF
TRIPPED
(RESET)
Main contacts Main contacts Main contacts Main contacts
“Closed”
“Open”
“Open”
“Open”
Fig. 8
Handle Positions and Status Indication
1) ON operation
Caution
If the ACB trips open automatically, remove the cause before closing the ACB.
Otherwise, a fire could result.
To close the ACB, set the operating handle to the ON position.
Caution : When the ACB is equipped with the undervoltage trip device (UVT), the UVT coil must
be excited to permit the ON operation.
2) OFF operation
To open the breaker, set the operating handle to the OFF position.
Caution : If the main contacts are damaged (welded), the ACB cannot open. In this case, the
operating handle will return to the ON position when the handle is released at the OFF position.
Replace the ACB.
3) Tripping operation
When the overcurrent trip device (OCR), UVT, or shunt trip device (SHT) is activated, the ACB
trips open and the operating handle moves to the TRIPPED position automatically.
To check the tripping mechanism or the alarm switch, use the trip button. Pressing the trip
button will trip the ACB. The trip button operating force is as follows:
ACB type
Trip button operating force N
AME3B, AME4B
19.6
AME6B, AME8B, AME10B
4.9
RESET position
TRIPPED position
OFF position
ON position