The interlock is enabled in the connected position. When the ACB is in the TEST, ISOLATED or DRAW-OUT
Position the interlock is disabled.
If all the ACBs in the interlock system are open and receive a close (on) signal, none will turn on. However,
if this occurs there will be momentary continuity between the main circuit and the auxiliary switch A-contact in
all the ACBs.
The body of the other ACB(s), as long as they are off (open) can be drawn out or inserted, irrespective of the state
of the other ACB(s). NOTE: Do not draw out or insert an ACB body during cable installation, adjustment or
operation check.
Specifications
ACB front cover centre line
.
There should be a minimum of 200mm-gap left between the interlock mechanism and the cabinet wall, this is
to enable cable installation, adjustment or operation check.