KRB-5404
30
Table 14 Ratings of auxiliary and position switches
Voltage (V)
Auxiliary switches *1 *2
Position switches
For general feeder
For microload *3
Resistive load (A)
Inductive load (A)
*4
Resistive load (A)
Inductive load (A)
*5
Resistive load (A)
Inductive load (A)
*5
AC100 - 250
5
5
0.1
0.1
11
6
AC251 - 500
5
5
-
-
-
-
DC8
-
-
-
-
10
6
DC30
1
1
0.1
0.1
6
5
DC125
-
-
-
-
0.6
0.6
DC250
-
-
-
-
0.3
0.3
DC125 - 250
1
1
-
-
-
-
*1 Using b-contact results in contact chatter of 20 ms or less when the ACB opens or closes.
*2 Do not apply different voltages to contacts of a switch.
*3 Min. applicable load: DC5V/1 mA
*4 AC cosø
0.3, DC L/R
0.01
*5 AC cosø
0.6, DC L/R
0.007
Table 15 Ratings of operation indication contacts
Voltage (V)
Rated contact current (A)
Individual indication
Long-time delay trip, short-time delay trip,
instantaneous trip, pretrip alarm, ground fault trip,
system alarm
Spring charging/tripping operation
Resistive load (A)
Inductive load (A) *1
Resistive load (A)
Inductive load (A) *1
AC250
0.5
0.2
3
3
DC30
2
0.7
3
2
DC125
0.5
0.2
0.5
0.5
DC250
0.27
0.04
0.1
0.1
*1 AC cosø
0.6, DC L/R
0.007
Table 16 Ratings of N-phase CT
Type of ACB
Type of N-phase CT
Ratings (A)
AR208S, AR212S, AR216S
AR212H, AR216H, AR316H
AR208D, AR212D, AR216D
CW80-40LS
200/5A
400/5A
800/5A
1250/5A
1600/5A
AR220S, AR325S, AR332S, AR440S
AR220H, AR320H, AR325H, AR332H
AR440SB,AR420H,AR440H
EC160-40LS
1600/5A
2000/5A
2500/5A
3200/5A
4000/5A