KRB-5404
76
5-5. Operation Indication and Indication Resetting Procedure
5-5-1. Operation Indication (AGR-11B type)
The OCR has LEDs on the front panel to provide operation indications as shown in Fig. 68 and Table 38. It also outputs operation
signals to contacts.
Fig. 68 LEDs
Table 38 Operation indication
Type of OCR
Control
power
supply
Operation
LED
Contact output
Position
State
Terminal No.
See Fig. 17
State
Normal
pickup
Trip/Alarm
Normal
Trip/Alarm
AGR-11BL-AL
AGR-11BL-GL
Not required
Long time delay trip (LT)
N-phase protection (NP)
◯
1
OFF
Flash
OFF
□
05
,
□
15
OFF
Turn OFF
automatically after
ON for 40 ms or
more *1
Short time delay trip (ST)
Ground fault trip (GF)
Instantaneous trip (INST)
OFF
*1: A self-hold circuit is required.
(Red)
◯
1