KRB-5404
97
6-2-9. Auxiliary switches
The following describes how to replace auxiliary switches.
1) Make preparations for parts replacement. Refer to section 6-2-1, 1) and 2).
2) If the ACB is equipped with the control terminal block cover, loosen both the cover fixing screws and remove the cover.
3) Remove the auxiliary switch mounting screws shown in Fig. 95.
Fig. 95 Auxiliary switches and related parts
4) Depressing the AUX lock lever shown in Fig. 96, raise the operation lever till a shaft lever (see Fig. 97) appears in the top of
draw-out cradle.
Fig. 96 AUX lock lever and operation lever
AUX lock lever
Operation lever
Auxiliary switches
Auxiliary switch mounting
screw,
Pan head M4 x 10 (4 - 6)
with spring and flat washers
Tightening torque: 1.3 - 1.7 N·m
Cover fixing screw