KRB-5368c
-45-
Fig. 46 Remedial actions against an overheat
An overheat occurs.
Is the ambient
temperature
as specified?
Yes
Is the load current as
specified?
Yes
Are main circuit
terminal screws loose? See
No. 5 in Table 21.
No
No
No
Yes
Correct/adjust
Retighten
Are OCR settings
correct?
Yes
Check the control circuit.
See No. 10 in Table 21.
OK
Check the tripping
operation. See No. 24
in Table 22.
OK
Check
contacts. See Nos.
7 in Table 21.
OK
Is the problem
solved?
No
Contact Terasaki.
No
NG
NG
NG
Yes
Correct/adjust
Repair
Contact Terasaki.
Repair/replace
End