CE Calculations
The CE performs the precision computations necessary to accurately measure and detect current. The compute engine
firmware implements the following:
1. Supports 6 current sensing channels
2. Each channel individually configurable for Current Transformer or Rogowski coil
3. Each channel individually configurable for x8 gain for low signal sensors (MAX out < 20 mV)
4. Channel I4 configurable for Ground Fault current with fundamental frequency band pass filter or the vectorial sum of
first current input channel data (Insqsum)
5. Channel I5 includes a band pass filter to process the components of fundamental frequency of operation only
6. Programmable accumulation interval generates interrupt on DIO6 for data collection
7. Programmable FAULT_THRESH register sets over current detection to generate FAULT_PULSE on DIO7
8. Individual channel calibration coefficients to adjust the gain for desired accuracy
CE RAM Locations
CE Front End Data (Raw Data)
Access to the raw data provided by the AFE is possible by reading addresses 0 through 7, as listed below. The table also shows
the Configuration Register location for each input channel.
Address (HEX)
Input
Channel
Configuration
Register
Description
0x00
I0
0x28
Current input 0
0x01
I1
0x29
Current input 1
0x02
I2
0x2A
Current input 2
0x03
I3
0x2B
Current input 3
0x04
I4
0x2C
Current input 4
0x05
I5
0x2D
Current input 5
0x06 TEMP -- Temperature
0x07
INEUTRAL
--
INEUTRAL monitor/compara-
tor input to power fault block
electronic components distributor