23
EOS-EWS_42-53_U161600
6.1 INSTALLATION
WARNING
Only suitably trained personnel can carry out installation and
maintenance on the extractor.
Failure to observe these instructions could cause product
malfunction, equipment damage and serious personal injury.
CAUTION
The extractor must be fitted in a perfectly vertical position.
Ensure an open area on the air inlet side, without obstacles
and/or buildings, up to a distance of 10 m.
Do not obstruct in any way, even partially, the air inlet section
of the extractor.
WARNING
The lifting of the machine for installation purposes to an elevated
position must be carried out in safe conditions. Therefore, these
operations should be entrusted to professionals.
Given its weight, the extractor will be lifted by self-propelled
aerial platforms or forklift with sufficient elevation capacity.
The lifting means must have performance characteristics
greatly exceeding what is required for the lifting of the extractor.
In the case of using ropes for lifting, these must have a bearing
capacity of at least three times the weight of the extractor.
The use of individual safety devices is required, particularly:
- protective gloves and clothing resistant to cutting due to the
presence of sharp materials such as metal profiles;
- Safety belts for high installation in case you do not have a self-
propelled aerial work platform with safety railing.
WARNING
Given the presence of risks arising from moving parts and the
air processed by the extractors, the user is obliged to protect
the fan evacuation area through the enclosure preventing
access to unauthorized persons. Indicate the forbidden area
with appropriate signs and signals.
It is still possible to buy a net for protective use of each fan
(SK optional).
If installing at a height above ground of more than 2.7 meters, it
is not necessary to provide any additional protection.
WARNING
That precautions must be taken to avoid the back-flow of gases
into the room from the open flue of gas or other fuel-burning
appliances.
6.2 PRELIMINARY INSTALLATION
NOTE
The following operations are performed only before
installation on the wall or frame of the extractor.
1. In the case of preassembled machine, remove the cable cover
(pos.28) from the envelope of the User Instructions Manual
and insert it manually in the hole on the side panel as shown
in figure.
2. Open the air inlet side safety nets by loosening the screws
present on the net fastening devices (pos.30) and rotating each
mechanism to a vertical position.