CABLE SIZES / FUSES
The input/output cables can be sized to suit the UPS rating according to the table below
Cables
CL115D
Input
3x16 mm2 (phase+earth)
Output
3x16 mm2 (phase+earth)
Fuses
CL115D
Input
80A
Output
80A
Battery
80A
CONNECTIONS
CL115D Series UPS run only on 1-Phase AC power supplies with a NEUTRAL line.
The UPS unit must be grounded in accordance with electrical regulations
Before making power connections to the unit, ensure that the incoming power sources are de-energized and
insulated.
The connections of the UPS should be supplied by grounded outlets. All control cables should be screened and
run in a separate trunking to the power cables.
Terminal
Function
K1
Earth input terminal
K2
Phase input terminal
K3
Neutral input terminal
K4
Neutral output terminal
K5
Phase output terminal
K6
Earth output terminal
K7
Battery (+) terminal
K8
Battery (-) terminal
ALARM RELAY CONNECTIONS
AC INPUT AC OUTPUT BATTERY
K1- K2- K3 - K4-K5-K6 K7- K8
Phase
(+) (-)
Neutral Neutral
Phase