A51 MAINTENANCE
Alarm
A52 MANU.BYPASS
Alarm
A63 INV.FAILURE
Alarm
A65 MAINS HIGH
Warning
A66 +DC BUS TOL
Alarm
A72 AV.BATT.HIGH
Warning
A76 –DC BUS TOL
Alarm
A77 BYP. FREQ. BAD
Warning
A7 BATTERY LOW warning
Battery voltage is less than the minimum allowed warning value. During this alarm inverter continues its
operation.
A7 BAT.LOW SHUT.
Battery voltage is less than the minimum allowed shutdown level value. During this alarm inverter stops.
A8 OUTPUT HIGH
Inverter output voltage is higher than the maximum allowed AC voltage value.
A9 OVLD.SHUTDOWN
The output load current is higher than 100% capacity of the UPS
•
The load is higher than 150%
•
Or, during the last 60 seconds (adjustable) the load is higher than 125%
•
Or, during the last 600 seconds (adjustable) the load is higher than 100%
A10 LINE FAILURE
Mains voltage is lower than the allowed minimum AC voltage level or a blackout occurred on mains voltage.
A11 OVERTEMP.
Cabinet inside temperature of the UPS is higher than the allowed temperature. (default 48 C)
A12 OVERCURRENT
Internal or external overcurrent sensed in power drive system.
A13 OUTPUT LOW
UPS tries to regulate the output voltage but the AC output voltage is less than the allowed minimum level.
A14 BATTERY HIGH
The battery voltage is higher than the allowed value.
A16 BYP INP.BAD
The bypass input of the UPS is out of tolerance.
A17 BAT.CB OPEN
The battery fuse is off or blown.
A19 BATT.FAULT
During battery test battery fault occurred.
A20 BOOST CHARGE
UPS is applying boost charge.
A22 OUTPUT OFF
There is no output voltage at the output of the UPS.