10
1.4 Technical Specifications
MODEL
DS320-110
DS330-110
DS340-110
Output (KVA)
20 kVA
30 kVA
40 kVA
Output (KW)
18 kW
27 kW
36 kW
Output Power Factor
0,9
INPUT
Number of Phases
3 Phase + Neutral
Input Voltage
110/190, 115/200,120/208 or 127/220 Vac
Input Voltage Tolerance
+/-20% (+15%, -25% at 127/220Vac)
Input Power Factor (PF)
> 0,99 (at full load)
Input THDI
<= 4% (depending on input conditions)
Input Frequency
50 / 60 Hz
±
5%
By-pass Voltage
110/190, 115/200,120/208 or 127/220 3 Phase + Neutral
By-pass Frequency
50 Hz.
±
2%
RFI Level
EN62040-2
OUTPUT
Number of Phases
3 Phase + Neutral
Output Voltage
110/190, 115/200,120/208 or 127/220 Vac
Output Voltage Tolerance
±
1%
Output Frequency
50 or 60 Hz
Output Frequency Tolerance (Synchronous)
±
2%
Output Frequency Tolerance (Battery)
±
0,2%
Efficiency (100% Load)
up to 94%
Load Crest Factor
3:1
Output Voltage THD (linear load)
<3%
Overload
125% Load 10min. , 150% Load 1min.
BATTERY
Total Number
32 blocks 12V (2x16 serial 32 batteries)
Float Charge Voltage (25
0
C)
±
216V DC
End of Discharge Voltage
±
160V DC
Battery Test
Automatic and Manual
Boost Charge
Available
COMMUNICATION INTERFACES
RS232 Com Port
2 each standard (COM1 and COM2)
External Temperature Measurement Input
Available (standard)
RS485 Comm. Port
Optional
Remote Monitoring Panel
Optional
SNMP Adapter
Optional
Modbus Adapter
Optional
Alarm Relay Contacts
4 each dry contacts (function programmable) 8 optional
Digital Inputs
2 each optional
Emergency Power-Off Input
Available (standard)
ENVIRONMENT
Operating Temperature
0 – 40
0
C
Operating Humidity
<= %90 (non-condensing)
Acoustic Noise
<62dB
Dimensions (WxDxH) (mm)
515 x 855 x 1450
Device Type and Protection Class
Class 1 – IP20
Weight (Without Batteries) (app. kgs)
175
180
194
Summary of Contents for DS300-110 Series
Page 1: ...DS300 110 SERIES DSP Controlled UPS 20 30 40 kVA 3 Phase In 3 Phase Out USER MANUAL...
Page 2: ......
Page 66: ......
Page 67: ...AGKK11290 11 2014...