background image

 

  

 

42

 
 
 

A36 INV DC DOWN

  

Call service 
 

A37 AC CURR LIMIT

  

Alarm shows us the output current is very high (higher then 150%) the UPS limited the output current. This 
status is temporary but if continues call service. 
 

A38 FUSE FAILURE

  

Call service 
 

A39 PSP FAILURE

  

Call service 
 

A43 USER LOGIN

  

User logged in to UPS this is only warning 
 

A45 SERV.PASSWORD

  

Call service , UPS start impossible 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for DS300-110 Series

Page 1: ...DS300 110 SERIES DSP Controlled UPS 20 30 40 kVA 3 Phase In 3 Phase Out USER MANUAL...

Page 2: ......

Page 3: ...tion of Connection Terminals of the UPS 13 2 7 Battery Installation 14 III FRONT PANEL 17 3 1 Introduction 17 3 2 Front Panel Menu Descriptions 17 3 2 1 MEASUREMENTS menu 20 3 2 2 ALARM LOGS menu 23 3...

Page 4: ...Maintenance Bypass Condition to Normal Operation 56 6 2 UPS Behavior During Mains Outage 56 VII MAINTENANCE 57 7 1 Scheduled maintenance 57 7 2 Daily checks 57 7 3 Weekly checks 57 7 4 Annual Mainten...

Page 5: ...C power is disconnected To reduce the risk of electric shock disconnect the UPS from the mains supply before installing a computer interface signal cable Reconnect the power cables only after signalin...

Page 6: ...own internal voltage and frequency regulating software which ensures that its output to the critical load is maintained within close tolerances independent of voltage and frequency variations on the m...

Page 7: ...ble polarity battery with common terminal Automatic and manual battery test and battery temperature compensation features 3 separate maintenance clock counters Battery charge with current limiting Aut...

Page 8: ...Switch S4 F7 F8 F9 Output Switch Fuse S5 F10 F11 F12 Battery Switch Fuse K1 Rectifier Input Contactor K2 Inverter Output Contactor Rectifier Charger 3 PHASE MAINS I P Battery Dual Polarity Maintenanc...

Page 9: ...nd black outs when it is connected to either static or maintenance bypass supply 1 2 2 Operating Conditions of UPS UPS may be in one of the following operating conditions A Normal Operation If Mains s...

Page 10: ...ket DB9 female Relay Output contacts Batt circuit breaker output and input Generator input Temperature sensor Relay 2 S7 On off switch S5 Ak input F10 F11 F12 S1 AC input F1 F2 F3 S3 maintenance by pa...

Page 11: ...top Relay 4 COM1 RS232 Communation Socket DB9 female SNMP COM2 RS232 Communation Socket DB9 female Figure 1 3 b 40 kVA switches fuses and interface connections PARALLEL PORT 2 PARALLEL PORT 1 S7 On of...

Page 12: ...Battery 0 2 Efficiency 100 Load up to 94 Load Crest Factor 3 1 Output Voltage THD linear load 3 Overload 125 Load 10min 150 Load 1min BATTERY Total Number 32 blocks 12V 2x16 serial 32 batteries Float...

Page 13: ...age is noted call the shipper immediately and retain the shipping carton and the UPS 2 Carefully open the carton and take the UPS out 3 Retain the carton and packing material for future use Unit packa...

Page 14: ...2 terminal block NOTES The neutral conductor should be sized for 1 5 times the output bypass phase current These recommendations are for guideline purposes only and are superceded by local regulation...

Page 15: ...r earth bus to the safety earth of the mains distribution panel NOTE The earth and the neutral connections must be in accordance with the local rules WARNING Note that the Input Neutral N1 MUST also b...

Page 16: ...o obtain efficient battery operation In general a minimum space of 10 mm must be left on all vertical sides of the battery block A minimum clearance of 20 mm should be allowed between the cell surface...

Page 17: ...15 Figure 2 3 External Battery Connections 32x12V 16x12V Batteries 16x12V Batteries 0 192V 192V 0 K1 K2 K3 K2...

Page 18: ...16 Figure 2 3b DS300 110 Series 20 30 40 KVA Internal Battery Connections 2x16 32x12V 18Ah two groups of batteries with common point in parallel...

Page 19: ...2 Load on bypass indicator lamp L3 Input voltage indicator lamp L4 Rectifier run pilot lamp L5 Battery operation indicator lamp L6 Load on UPS indicator lamp L7 Output switch on indicator lamp There a...

Page 20: ...l measurements ENTER EXIT ALARM LOGS UPS LOG RECORD Page1 ENTER CLEAR LOG Page1 ENTER EXIT INFORMATION RS232 Comm 1 2 Page1 Maximum UPS power Page1 Nominal voltage and frequency Page1 Inverter firmwar...

Page 21: ...ut command Page3 ENTER EXIT PASSWORD Getting service code Page1 Type service password Page1 Type user password Page1 ENTER EXIT ADJUST in English Group adjustments Automatic settings Inverter factory...

Page 22: ...t alarm messages Up previous page down next page MEASUREMENTS INPUT Page 3 Level 3 ENTER EXIT ENTER exit to upper menu Current alarm messages Up previous page down next page MEASUREMENTS BYPASS Level...

Page 23: ...10 110 110 V Phase to neutral measured AC UPS output voltages Iout 00 0 00 0 00 0 A Measured AC RMS load currents Current alarm messages Up previous page down next page MEASUREMENTS OUTPUT Page 2 Leve...

Page 24: ...n next page MEASUREMENTS DC Page 3 Level 3 Backup time 0000 min Calculated remaining time Current alarm messages Up previous page down next page MEASUREMENTS DC Page 4 Level 3 ENTER EXIT ENTER exit to...

Page 25: ...activity indicator for com1 and com2 MAX Power 30000 VA Maximum ups output power as VA Nom 110 050 110 050 Nominal input output voltage and frequency Current alarm messages Up previous page down next...

Page 26: ...adjust BL DELAY CLOSED Backlight delay BL DIM CLOSED Back light half option selection Current alarm messages Up upper line down next line or options ENTER select an option OPTIONS LCD OPTIONS Page 3 L...

Page 27: ...PTIONS COMMUNICATION OPTIONS Page 4 Level 3 RELAY 7 Left and right buton relay function selection option RELAY 8 Left and right buton relay function selection option RELAY 9 Left and right buton relay...

Page 28: ...PTIONS Page 3 Level 3 ENTER EXIT ENTER exit to upper menu Current alarm messages Up previous page down next page Level 3 Bypass options VAT transfer ON OFF Page1 Gen set bypass ON OFF Page1 Gen set sy...

Page 29: ...ND ON OFF Left and right disable alarm buzzer MIMIC LED TEST ENTER lamp test Current alarm messages Up upper line down next line or options ENTER apply command COMMAND MENU Page 4 Level 2 ENTER EXIT E...

Page 30: ...on recorded maximum power ENTER FAULT RESET ENTER fault reset Current alarm messages Up upper line down next line SERV CE MENU Page 2 Level 2 FAN MAINT 01000 Remaining hours to FAN maintenance BAT MAI...

Page 31: ...A00 or R00 Alarm is shown on the LCD panel we understand that there is a system fault at the related module We saw the message in the A00 INV FAULT XXXX or R00 PFC FAULT XXXX format Numbers shown in X...

Page 32: ...s INV CODE 0XXX Current inverter mod le status code A00 INV FAULT XXXX Hata XXXX fault occured at the inverter module CALL SERVICE A01 O P OVERCURRENT Alarm IGBT saturation alarm on inverter module A0...

Page 33: ...upted A36 INV DC DOWN Warning DC BUS voltage is less then 120 volts DC A37 AC CURR LIMIT Warning Inverter output current limited A38 FUSE FAILURE Warning Any fuse in UPS is blowned A39 PSP FAILURE Ala...

Page 34: ...time 369 Overcurrent occured on L3 phase longer then allowed time 170 On L1 phase momentary short circuit conditions occured but now inverter is running 270 On L2 phase momentary short circuit conditi...

Page 35: ...ce at the UPS output 383 L3 phase by pass SCR must be on but there is only positive alternance at the UPS output 184 L1 phase by pass SCR must be on but there is only negative alternance at the UPS ou...

Page 36: ...t at the UPS output there is no 3 phase AC voltage INV Control activity status codes 612 INV Over RS232 interface battery quantity updated 613 INV Over CAN1 interface battery quantity updated 614 INV...

Page 37: ...eived 651 INV Over CAN1 interface generator mode start command received 652 INV Over RS232 interface start sleep mode command received 653 INV Over CAN1 interface start sleep mode command received 654...

Page 38: ...ge is higher then R2131 adjustment 1401 PFC DC bus voltage is higher the R2131 adjustment 1402 PFC DC LEM current sensor error 1403 PFC module DC BUS voltage high alarm repeated 4 times within R2166 t...

Page 39: ...received 1643 PFC over CAN1 interface cancel battery test command received 1644 PFC over RS232 interface start boost charge mode command received 1645 PFC over CAN1 interface start boost charge mode...

Page 40: ...frequency is normal R06 OVERTEMPERATURE Overtemperature at rectifier module call service R07 BLACKOUT There is a short blackout at the AC input voltage of the UPS this is temporary wait until the AC...

Page 41: ...if hot use air cooling system If batteries are internal check the UPS ambient temperature if normal call service L02 TH2 TEMP HIGH L04 TH2 TEMP LOW UPS TH2 cabinet inside temperature is out of tolera...

Page 42: ...nt is normal A07 SHORT CIRCUIT There is short circuit at the output of the UPS check installation and loads A08 ON MAINTENANCE The maintenance by pas switch of the UPS is ON 1 position there is a lock...

Page 43: ...ds the mesage will be cleared A26 BATTERY LOW The DC BUS or battery voltage of the UPS is low still UPS is running but DC voltage is going down If this alarm occures during mains failure it means that...

Page 44: ...very high higher then 150 the UPS limited the output current This status is temporary but if continues call service A38 FUSE FAILURE Call service A39 PSP FAILURE Call service A43 USER LOGIN User logg...

Page 45: ...arallel therefore provides increased reliability for the critical load connected to the parallel system output If power demand increases in a certain UPS application exceeding the power rating of an a...

Page 46: ...RALLEL mode This mode is used for operation of at least two 1 1 configuration UPS units connected in parallel for increased reliability If this mode is selected the load is shared equally by each UPS...

Page 47: ...t 2 Parallel Port 1 Parallel Port 2 Parallel Port 1 Parallel Port 2 Figure 4 2 c 4 units in parallel All the units must be set for the same operation mode and must have a different UPS number Figure 4...

Page 48: ...ibution board Figure 4 3 DS300 110 Series Parallel UPS Power Connections BATTERIES U V W N LOAD FUSES AC BYPASS AC INPUT MAIN AC INPUT AC DISTRIBUTION U1 V1 W1 N1 U2 V2 W2 N2 UPS1 K3 K2 K2 K4 K5 K6 K7...

Page 49: ...m Restart Change operating mode and Restart UPS again Returning to fault Directly fault In parallel UPS system master and slave UPS operating modes must be same 803 Status code Status Inverter system...

Page 50: ...allel system and restart again If the code is still showned call service 820 Status code Status Inverter alarm Description In parallel system while in slave mode MASTER communication lost for 8 period...

Page 51: ...ystem if the same A H rating batteries are used at each UPS the battery discharge timebe same for each UPS If the other UPS is continue to run check the batteries of this UPS Call service 825 Status c...

Page 52: ...E UPS L2 phase output is not connected to load Restart 831 Status code causes are valid for L2 phase 833 Status code Status Inverter warning Description SLAVE UPS L3 phase output is not connected to l...

Page 53: ...verter warning Description MASTER UPS send transfer the load to UPS command Restart Returning to fault 852 Status code Status Inverter warning Description Enter to sleep mode command received from par...

Page 54: ...kages output switch turned on after 2 seconds MASTER mode started Restart Returning to fault 858 Status code Status Inverter warning Description In parallel system there is no MASTER communication pac...

Page 55: ...3 Turn on S7 On Off switch to 1 position LCD panel activates and INV RESET or PFC RESET message appears on the display meaning that the rectifier starts to operate 4 Turn ON S4 AC Output switch switc...

Page 56: ...this case bypass voltage is connected directly to the output of UPSs and the critical load is supplied via maintenance bypass switch No AC or DC supply is connected to the inside and the circuits of U...

Page 57: ...urn off S7 On Off switch to 0 position 3 Turn off S5 Battery switch to 0 position 4 Turn off S2 Bypass switch to 0 position 5 Turn off S1 AC Input switch to 0 position After performing the above proce...

Page 58: ...nt But do not turn on these loads again during battery operation After a short period of time when the line voltage is available again UPS returns to normal operation automatically and the alarm messa...

Page 59: ...ANCE counter BATTERY MAINTENANCE counter GENERAL MAINTENANCE counter This type of protective maintenance prevents small problems turning up to big failures DS300 110 Series UPS has been designed to re...

Page 60: ...one at least two times a year in order to provide safe and efficient operation your UPS and battery group UPS generates a warning message when the maintenance time has expired 7 5 Storage Conditions a...

Page 61: ...wed while trying to indicate the error Fault determination First step is to record the messages indicator panel LEDs operating parameter values and last status of switches This must be done before Fix...

Page 62: ...TTERY TEST until battery low alarm CANCEL battery test Turn off UPS output voltage immediately SHUTDOWN Turn off UPS output voltage after delay WAITING SHUTDOWN Turn off UPS output voltage SHUTDOWN an...

Page 63: ...r phone and listen the modem sound NOTE Not all the modems are compatible with the command set on UPS In such a case modem should be set by connecting a PC 9 3 2 Functioning Principle The remote opera...

Page 64: ...emperature sensor input 11 12 Function programmable relay contact output 2 13 14 Function programmable relay contact output 3 15 16 Function programmable relay contact output 4 ATTENTION Maximum 42Vac...

Page 65: ...its economically as well as supporting to create a cleaner environment and protecting our world sources 2 Every electric powered device is designed appropriate to a defined power level Device capacity...

Page 66: ......

Page 67: ...AGKK11290 11 2014...

Reviews: