background image

 

  

 

30

 
 
 
 
 
 
 

 

INV L1-L2-L3 phase status codes 

178 

Inverter stopped but on inverter L1 phase output still DC voltage sensed 

278 

Inverter stopped but on inverter L2 phase output still DC voltage sensed 

378 

Inverter stopped but on inverter L3 phase output still DC voltage sensed 

179 

During inverter run at last 25 milliseconds the L1 phase output alternance is not changed 

279 

During inverter run at last 25 milliseconds the L2 phase output alternance is not changed 

379 

During inverter run at last 25 milliseconds the L3 phase output alternance is not changed 

180 

At  the  end  of  4  times  retry  During  soft  start  after  4  seconds  still  the  L1  phase  output  voltage  is 
less then 30 volts AC 

280 

At  the  end  of  4  times  retry  During  soft  start  after  4  seconds  still  the  L2  phase  output  voltage  is 
less then 30 volts AC 

380 

At  the  end  of  4  times  retry  During  soft  start  after  4  seconds  still  the  L3  phase  output  voltage  is 
less then 30 volts AC 

181 

At the end of 4 times retry During soft start at the end of 4 seconds L1 output  voltage is bigger 
then (output high/2) value 

281 

At the end of 4 times retry During soft start at the end of 4 seconds L2 output  voltage is bigger 
then (output high/2) value 

381 

At the end of 4 times retry During soft start at the end of 4 seconds L3 output  voltage is bigger 
then (output high/2) value 

182 

During  power  on  L1  phase  bypass  SCR  must  be  off  but  at  the  L1  phase  output  there  is  AC 
voltage 

282 

During  power  on  L2  phase  bypass  SCR  must  be  off  but  at  the  L2  phase  output  there  is  AC 
voltage 

382 

During  power  on  L3  phase  bypass  SCR  must  be  off  but  at  the  L3  phase  output  there  is  AC 
voltage 

183 

L1 phase by-pass SCR must be on but there is only positive alternance at the UPS output 

283 

L2 phase by-pass SCR must be on but there is only positive alternance at the UPS output 

383 

L3 phase by-pass SCR must be on but there is only positive alternance at the UPS output 

184 

L1 phase by-pass SCR must be on but there is only negative alternance at the UPS output 

284 

L2 phase by-pass SCR must be on but there is only negative alternance at the UPS output 

384 

L3 phase by-pass SCR must be on but there is only negative alternance at the UPS output 

185 

L1 phase by-pass SCR must be on but there is no output voltage at the UPS output 

285 

L2 phase by-pass SCR must be on but there is no output voltage at the UPS output 

385 

L3 phase by-pass SCR must be on but there is no output voltage at the UPS output 

186 

Output CB is energized but at the L1 phase output there is only positive alternance 

286 

Output CB is energized but at the L2 phase output there is only positive alternance 

386 

Output CB is energized but at the L3 phase output there is only positive alternance 

187 

Output CB is energized but at the L1 phase output there is only negative alternance 

287 

Output CB is energized but at the L2 phase output there is only negative alternance 

387 

Output CB is energized but at the L3 phase output there is only negative alternance 

188 

Output CB is energized but at the L1 phase output there is no AC voltage 

288 

Output CB is energized but at the L2 phase output there is no AC voltage 

388 

Output CB is energized but at the L3 phase output there is no AC voltage 

189 

During load on by-pass on the L1 output short circuit sensed 

289 

During load on by-pass on the L2 output short circuit sensed 

389 

During load on by-pass on the L3 output short circuit sensed 

190 

On L1 phase output reverse current sensed 

290 

On L2 phase output reverse current sensed 

390 

On L3 phase output reverse current sensed 

191 

During load on inverter ,on L1 phase by-pass line leakage current sensed 

291 

During load on inverter ,on L2 phase by-pass line leakage current sensed 

391 

During load on inverter ,on L3 phase by-pass line leakage current sensed 

 

Summary of Contents for DS300 HYB Series

Page 1: ...DS300 HYB SERIES DSP Controlled UPS 100 120 160 kVA 3 Phase In 3 Phase Out USER MANUAL...

Page 2: ......

Page 3: ...Cables 10 2 5 Safety Earth 10 2 6 Cable Connection Procedure 10 2 6 1 UPS Power Cable Connection Terminals 11 2 7 Battery Installation 12 III FRONT PANEL 14 3 1 Introduction 14 3 2 Front Panel Menu D...

Page 4: ...5 4 Annual Maintenance 44 5 5 Storage conditions and transportation of ups 44 VI FAULTS AND TROUBLESHOOTING 45 6 1 General Procedure for fault checking and troubleshooting 45 6 2 Before calling servic...

Page 5: ...C power is disconnected To reduce the risk of electric shock disconnect the UPS from the mains supply before installing a computer interface signal cable Reconnect the power cables only after signalin...

Page 6: ...own internal voltage and frequency regulating software which ensures that its output to the critical load is maintained within close tolerances independent of voltage and frequency variations on the m...

Page 7: ...ble polarity battery with common terminal Automatic and manual battery test and battery temperature compensation features 3 separate maintenance clock counters Battery charge with current limiting Aut...

Page 8: ...7 F8 F9 Output Switch Fuse S5 F10 F11 F12 Battery Switch Fuse K1 Rectifier Input Contactor K2 Inverter Output Contactor SB Rectifier Charger 3 PHASE MAINS I P Battery Dual Polarity Maintenance Bypass...

Page 9: ...nd black outs when it is connected to either static or maintenance bypass supply 1 2 2 OPERATING CONDITIONS OF UPS UPS may be in one of the following operating conditions A Normal Operation If Mains s...

Page 10: ...Communation Socket DB9 female Relay Output contacts Batt circuit breaker output and input Generator input Temperature sensor Relay 2 S7 On off switch S1 AC input F1 F2 F3 S3 Maintenance by pass S4 AC...

Page 11: ...Efficiency 100 Load up to 94 Load Crest Factor 3 1 Output Voltage THD linear load 3 Overload 125 Load 10min 150 Load 1min BATTERY Total Number 60 blocks 12V 2x30 serial 60 batteries external Float Cha...

Page 12: ...is noted call the shipper immediately and retain the shipping carton and the UPS 2 Carefully open the carton and take the UPS out 3 Retain the carton and packing material for future use Unit package...

Page 13: ...ductor should be sized for 1 5 times the output bypass phase current These recommendations are for guideline purposes only and are superceded by local regulations and codes of practice 2 5 Safety Eart...

Page 14: ...nect the copper earth bus to the safety earth of the mains distribution panel NOTE The earth and the neutral connections must be in accordance with the local rules WARNING Note that the Input Neutral...

Page 15: ...ment at reasonable temperatures to obtain efficient battery operation In general a minimum space of 10 mm must be left on all vertical sides of the battery block A minimum clearance of 20 mm should be...

Page 16: ...13 30x12V Batteries 30x12V Batteries 0 360V 360V 0 K1 K2 K3 K2 Figure 2 3 External Battery Connections 60x12V...

Page 17: ...oad on bypass indicator lamp L3 Input voltage indicator lamp L4 Rectifier run pilot lamp L5 Battery operation indicator lamp L6 Load on UPS indicator lamp L7 Output switch on indicator lamp There are...

Page 18: ...l measurements ENTER EXIT ALARM LOGS UPS LOG RECORD Page1 ENTER CLEAR LOG Page1 ENTER EXIT INFORMATION RS232 Comm 1 2 Page1 Maximum UPS power Page1 Nominal voltage and frequency Page1 Inverter firmwar...

Page 19: ...ut command Page3 ENTER EXIT PASSWORD Getting service code Page1 Type service password Page1 Type user password Page1 ENTER EXIT ADJUST in English Group adjustments Automatic settings Inverter factory...

Page 20: ...alarm messages Up previous page down next page MEASUREMENTS INPUT Page 3 Level 3 ENTER EXIT ENTER exit to upper menu Current alarm messages Up previous page down next page MEASUREMENTS BYPASS Level 2...

Page 21: ...1 222 223 V Phase to neutral measured AC UPS output voltages Iout 00 0 00 0 00 0 A Measured AC RMS load currents Current alarm messages Up previous page down next page MEASUREMENTS OUTPUT Page 2 Level...

Page 22: ...n next page MEASUREMENTS DC Page 3 Level 3 Backup time 0000 min Calculated remaining time Current alarm messages Up previous page down next page MEASUREMENTS DC Page 4 Level 3 ENTER EXIT ENTER exit to...

Page 23: ...32 activity indicator for com1 and com2 MAX Power 60000 VA Maximum ups output power as VA Nom 220 050 220 050 Nominal input output voltage and frequency Current alarm messages Up previous page down ne...

Page 24: ...adjust BL DELAY CLOSED Backlight delay BL DIM CLOSED Back light half option selection Current alarm messages Up upper line down next line or options ENTER select an option OPTIONS LCD OPTIONS Page 3 L...

Page 25: ...PTIONS COMMUNICATION OPTIONS Page 4 Level 3 RELAY 7 Left and right buton relay function selection option RELAY 8 Left and right buton relay function selection option RELAY 9 Left and right buton relay...

Page 26: ...PTIONS Page 3 Level 3 ENTER EXIT ENTER exit to upper menu Current alarm messages Up previous page down next page Level 3 Bypass options VAT transfer ON OFF Page1 Gen set bypass ON OFF Page1 Gen set sy...

Page 27: ...3 Level 2 ALARM SOUND ON OFF Left and right disable alarm buzzer MIMIC LED TEST ENTER lamp test Current alarm messages Up upper line down next line or options ENTER apply command COMMAND MENU Page 4 L...

Page 28: ...020 025 From power on recorded maximum power ENTER FAULT RESET ENTER fault reset Current alarm messages Up upper line down next line SERV CE MENU Page 2 Level 2 FAN MAINT 01000 Remaining hours to FAN...

Page 29: ...seconds 1 message will be showed next 2 seconds 2 message will be showed etc If A00 or R00 Alarm is shown on the LCD panel we understand that there is a system fault at the related module We saw the...

Page 30: ...AN COMM ERR Warning INV module CAN communication timeout Inverter module alarm codes INV CODE 0XXX Current inverter mod le status code A00 INV FAULT XXXX Hata XXXX fault occured at the inverter module...

Page 31: ...upted A36 INV DC DOWN Warning DC BUS voltage is less then 120 volts DC A37 AC CURR LIMIT Warning Inverter output current limited A38 FUSE FAILURE Warning Any fuse in UPS is blowned A39 PSP FAILURE Ala...

Page 32: ...time 369 Overcurrent occured on L3 phase longer then allowed time 170 On L1 phase momentary short circuit conditions occured but now inverter is running 270 On L2 phase momentary short circuit conditi...

Page 33: ...ce at the UPS output 383 L3 phase by pass SCR must be on but there is only positive alternance at the UPS output 184 L1 phase by pass SCR must be on but there is only negative alternance at the UPS ou...

Page 34: ...t at the UPS output there is no 3 phase AC voltage INV Control activity status codes 612 INV Over RS232 interface battery quantity updated 613 INV Over CAN1 interface battery quantity updated 614 INV...

Page 35: ...eived 651 INV Over CAN1 interface generator mode start command received 652 INV Over RS232 interface start sleep mode command received 653 INV Over CAN1 interface start sleep mode command received 654...

Page 36: ...ge is higher then R2131 adjustment 1401 PFC DC bus voltage is higher the R2131 adjustment 1402 PFC DC LEM current sensor error 1403 PFC module DC BUS voltage high alarm repeated 4 times within R2166 t...

Page 37: ...received 1643 PFC over CAN1 interface cancel battery test command received 1644 PFC over RS232 interface start boost charge mode command received 1645 PFC over CAN1 interface start boost charge mode...

Page 38: ...ency of the UPS is out of tolerance wait until the input frequency is normal R06 OVERTEMPERATURE Overtemperature at rectifier module call service R07 BLACKOUT There is a short blackout at the AC input...

Page 39: ...ide of the UPS cabinet check battery ambient temperature if hot use air cooling system If batteries are internal check the UPS ambient temperature if normal call service L02 TH2 TEMP HIGH L04 TH2 TEMP...

Page 40: ...nt is normal A07 SHORT CIRCUIT There is short circuit at the output of the UPS check installation and loads A08 ON MAINTENANCE The maintenance by pas switch of the UPS is ON 1 position there is a lock...

Page 41: ...ds the mesage will be cleared A26 BATTERY LOW The DC BUS or battery voltage of the UPS is low still UPS is running but DC voltage is going down If this alarm occures during mains failure it means that...

Page 42: ...very high higher then 150 the UPS limited the output current This status is temporary but if continues call service A38 FUSE FAILURE Call service A39 PSP FAILURE Call service A43 USER LOGIN User logg...

Page 43: ...TTENTION BYPASS VOLTAGE WILL BE CONNECTED TO THE OUTPUT TERMINALS OF UPS WHEN THE ON OFF SWITCH S7 IS SWITCHED ON 4 Turn on S7 On Off switch to 1 position LCD panel activates and INV RESET or PFC RESE...

Page 44: ...n this case bypass voltage is connected directly to the output of UPS and the critical load is supplied via maintenance bypass switch No AC or DC supply is connected to the inside and the circuits of...

Page 45: ...the Ah capacity charge status age of the batteries actual load percentage of UPS and the ambient temperature Otherwise critical loads will be out of power at the end of battery autonomy time A26 BATT...

Page 46: ...NCE counter BATTERY MAINTENANCE counter GENERAL MAINTENANCE counter This type of protective maintenance prevents small problems turning up to big failures DS300 HYB Series UPS has been designed to req...

Page 47: ...one at least two times a year in order to provide safe and efficient operation your UPS and battery group UPS generates a warning message when the maintenance time has expired 5 5 Storage Conditions a...

Page 48: ...ed while trying to indicate the error Fault determination First step is to record the messages indicator panel LEDs operating parameter values and last status of switches This must be done before Fixi...

Page 49: ...ATTERY TEST until battery low alarm CANCEL battery test Turn off UPS output voltage immediately SHUTDOWN Turn off UPS output voltage after delay WAITING SHUTDOWN Turn off UPS output voltage SHUTDOWN a...

Page 50: ...r phone and listen the modem sound NOTE Not all the modems are compatible with the command set on UPS In such a case modem should be set by connecting a PC 7 3 2 Functioning Principle The remote opera...

Page 51: ...emperature sensor input 11 12 Function programmable relay contact output 2 13 14 Function programmable relay contact output 3 15 16 Function programmable relay contact output 4 ATTENTION Maximum 42Vac...

Page 52: ...fits economically as well as supporting to create a cleaner environment and protecting our world sources 2 Every electric powered device is designed appropriate to a defined power level Device capacit...

Page 53: ......

Page 54: ...AGKK12110 09 2016...

Reviews: