52
842 Status code
Status
Inverter warning
Description
MASTER UPS L2 phase output is not connected to load
Restart
--
841 Status code causes are valid for L2 phase
843 Status code
Status
Inverter warning
Description
MASTER UPS L3 phase output is not connected to load
Restart
--
841 Status code causes are valid for L3 phase
850 Status code
Status
Inverter warning
Description
MASTER UPS send by-pass transfer command
Restart
--
Returning to fault
--
851 Status code
Status
Inverter warning
Description
MASTER UPS send transfer the load to UPS command
Restart
--
Returning to fault
--
852 Status code
Status
Inverter warning
Description
Enter to sleep mode command received from parallel system
Restart
--
Returning to fault
--
853 Status code
Status
Inverter warning
Description
Exit from sleep mode command received from parallel system
Restart
--
Returning to fault
--
854 Status code
Status
Inverter warning
Description
REPO (remote emergency power off) command received from parallel system
Restart
--
Returning to fault
--
855 Status code
Status
Inverter warning
Description
Enter to MASTER mode command received from parallel system
Restart
--
Returning to fault
--