3-7. Faults reference code
Fault event
Fault code
Icon
Fault event
Fault code
Icon
Bus start fail
01
Non
Inverter voltage low
13
Non
Bus over
02
Non
Inverter output short
14
SHORT
Bus under
03
Non
Battery voltage too high
27
BATT. FAULT
Bus unbalance
04
Non
Battery voltage too low
28
BATT. FAULT
Bus short
05
Non
Over temperature
41
Non
Inverter soft start fail
11
Non
Over load
43
OVER LOAD
Inverter voltage high
12
Non
3-8. Warning indicator
Warning
Icon (flassing)
Alarm
Low battery
LOW BATT.
Sounding every second
Overload
OVER LOAD
Sounding twice every second
Battery is not connected
Sounding every second
Over charge
C
Sounding every second
Over temperature
Sounding every second
Charger failure
CH
Sounding every second
Battery fault
BATT. FAULT
Sounding every second
Out of bypass voltage range
Sounding every second
Unstable bypass frequency
FU
Sounding every second
EEPROM error
EE
Sounding every second