5-2. Maintenance
► The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified
maintenance personnel.
► Even after the unit is disconnected from the mains, components inside the UPS system are still
connected to the battery packs which are potentially dangerous.
► Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that
no current is present and no hazardous voltage exists in the terminals of high capability capacitor
such as BUS-capacitors.
► Only persons are adequately familiar with batteries and with the required precautionary measures
may replace batteries and supervise operations. Unauthorized persons must be kept well away from
the batteries.
► Verify that no voltage between the battery terminals and the ground is present before maintenance
or repair. In this product, the battery circuit is not isolated from the input voltage. Hazardous voltages
may occur between the battery terminals and the ground.
► Batteries may cause electric shock and have a high short-circuit current. Please remove all
wristwatches, rings and other metal personal objects before maintenance or repair, and only use
tools with insulated grips and handles for maintaining or repairing.
► When replace the batteries, install the same number and same type of batteries.
► Do not attempt to dispose of batteries by burning them. This could cause battery explosion. The
batteries must be rightly deposed according to local regulation.
► Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may
be toxic.
► Please replace the fuse only with the same type and amperage in order to avoid fire hazards.
► Do not disassemble the UPS system.
6. Technical specifications
Model
NEOLINE ST+ 1K/1KL
NEOLINE RT+ 1KR/1KRL
NEOLINE ST+ 2K/2KL
NEOLINE RT+ 2KRL
NEOLINE ST+ 3K/3KL
NEOLINE RT+ 3KRL
Capacity
1000VA / 900W (K/KR)
1000VA / 800W (KL/KRL)
2000VA / 1800W (K)
2000VA / 1600W (KL/KRL)
3000VA / 2700W (K)
3000VA / 2400W (KL/KRL)
INPUT
Input Voltage
100/110/115/120/127 VAC or 200/208/220/230/240 VAC
Voltage Range
60-150 VAC or 120-300 VAC @ 50% load
90-140 VAC or 180-280 VAC @ 100% load
Frequency Range
40Hz ~ 70 Hz
OUTPUT
Power Factor
0.9 for K/KR models / 0.8 for KL/KRL models
Output voltage
100/110/115/120/127 VAC ±1% or 200/208/220/230/240 VAC ±1%
Frequency Range (Batt. Mode)
50 Hz or 60 Hz ±0.5%
Current Crest Ratio
3:1
Harmonic Distortion
≤3 % THD (linear load) / ≤6 % THD (non-linear load)
Transfer Time
From AC to battery: 0 ms / From Inverter to bypass: 4 ms (typical)
Waveform
Pure Sinewave