10 

 
 
 
 

 

INV CODE = 0XXX 

 

Status code of inverter module at that moment. 

A00 INV ERROR =   XXXX 

Error 

System error in inverter module XXXX value indicates the occurring error, service code is required to 
start the device 

-call the service

 

A01 OVER CURRENT 

Alarm 

Over loading occurred in the inverter module 

A02 OVER HEAT BREAK 

Alarm 

Over heat occurred in the inverter module 

A03 ACCUMULATOR HIGH 

Alarm 

Accumulator voltage found high 

A04 LOW OUTPUT  

Alarm 

UPS Output voltage found low 

A05 OUTPUTN HIGH 

Alarm 

UPS Output voltage found high 

A02 OVER LOAD BREAK 

Alarm 

Over loading occurred at device output stop the device 

A07 SHORT CIRCUIT 

Alarm 

Short circuit occurred at UPS output device blocked 

A08 IN MAINTENANCE 

Alarm 

Device maintenance switch is on 

A09 MANUAL BYPASS 

Alarm 

Device taken to manual by-pass position from the front panel 

A10 ACCUMULATOR LOW BREAK 

Alarm 

Accumulator voltage found low 

A11 EMERGENCY SHUT-OFF 

Alarm 

External emergency shut-off signal detected 

A12 DC BALANCE 

Alarm 

DC available at INV output before inverter starts 

A13 PEAK HIGH 

Alarm 

Short period over load drawn from UPS output 

A14 INV FAILED TO START 

Alarm 

Inverter module failed to create voltage at output during start 

A17 BYPASS INTERRUPTED 

Warning 

By-pass input voltage interrupted 

A18 BYPASS VOLT 

Warning 

By-pass input voltage out of tolerance 

A19 BYPASS FREQUENCY 

Warning 

By-pass voltage frequency is out-of-tolerance 

A20 OVER LOAD 

Warning 

Over loading available at device output device will stop 

A21 OVER HEAT 

Warning 

Over heating available at device output device will stop 

A22 OUTPUT INTERRUPTED 

Warning 

No voltage at UPS output 

A23 BYPASS 

Warning 

Device transferred the load to by-pass input 

A24 REVERSE CURRENT 

Warning 

Regenerative load applied voltage to device output 

A25 INV RESET 

Warning 

Inverter module supply applied recently (only seen when the device is started for the first time) 

A26 ACCUMULATOR LOW 

Warning 

Accumulator low warning, device will stop soon and electricity of connected loads will be interrupted.  

A27 GENERATOR MODE 

Warning 

Device operates at generator position 

A28 PHASE LOSS 

Warning 

Interruption in any of phases at UPS output 

A29 NO SYNCHRON 

Warning 

Inverter is not synchronous to by-pass input 

A30 SHORT CIRCUIT 

Warning 

Short circuit occurred and passed at UPS output 

A31 OUTPUT SWITCH 

Warning 

Device output switch is closed 

A32 SERVICE LOGIN 

Warning 

Device logged in with service authorizations 

A34 BYP.PHASE ROTATE 

Warning 

Order of 3 phases applied to device by-pass input is reverse 

A35 INV STOP 

Warning 

Inverter module stopped for any reason 

 

 
 
 
 
 
 

 
 

 
 
 
 

L03 TH1 LOW HEAT 

Warning 

TH1 heat sensor heat is lower than the adjusted alarm level 

L04 TH2 LOW HEAT 

Warning 

TH2 heat sensor heat is lower than the adjusted alarm level 

L05 FAN MAINTENANCE 

Warning 

FAN maintenance period expired warning 

L06 ACCUMULATOR 
MAINTENANCE 

Warning 

ACCUMULATOR maintenance period expired warning 

L07 OPT MAINTENANCE 

Warning 

Allocated for future 

L08 TH1 SENSOR ERROR 

Warning 

TH1 temperature sensor broken or short circuit 

L09 TH2 SENSOR ERROR 

Warning 

TH2 temperature sensor broken or short circuit 

L10 ERROR RESET 

Warning 

Not recorded in logs 

L11 ACCUMULATOR OUT-OF-
SERVICE 

Warning 

External accumulator switch is off 

L12 GENERAL MAINTENANCE 

Warning 

General maintenance period expired warning 

L13 PFC CAN COMM ERR 

Warning 

PFC module CAN communication broken warning 

L14 INV CAN COMM ERR 

Warning 

INV module CAN communication broken warning 

L17 SLEEP WAIT 

Warning 

Wait warning before the sleep mode  

L18 WAKE-UP WAIT 

Warning 

Wait warning before transition from sleep to wake-up mode 

A36 INV DC LOW 

Warning 

DC Busbar voltage is below 120 volt DC value 

A37 AC CURRENT LIMIT 

Warning 

UPS output current is over RXXXX value 

A38 FUSE BLOWN 

Warning 

Any fuse blown in the device 

A39 SUPPLY TOL. 

Alarm 

Inverter card supply values out-of-tolerance 

A41 SLEEP MODE  

Warning  

Inverter module in sleep mode  

A43 USER LOGIN 

Warning 

Device logged in with user authorizations 

A45 ENTER PASSWORD 

Error 

Error occurred at device inverter module service code required 

-call the service

 

Summary of Contents for RM2020

Page 1: ...0 UPS REMOTE MONITORING PANEL RMP X1 INSTALLATION AND USER S GUIDE ...

Page 2: ...RESENTATION 2 1 1 Package Opening and Content Control 2 1 2 View of Remote Monitoring Panel 2 1 3 Functions 2 1 4 Front panel functions 3 1 5 Technical Characteristics 3 2 INSTALLATION 4 2 1 UPS and Remote Monitoring Panel connection types 4 2 2 Explanations on Cable pin between UPS Remote monitoring panel 5 2 3 Mechanical Installation 6 2 4 Before Starting 6 3 STARTING 6 3 1 LCD Menu Structure 6 ...

Page 3: ...an be connected through RS232 and RS485 communication networks It has separate input port for each communication network It has communication output port equal to UPS communication port It can transmit responses coming from UPS to other devices from this port with RS232 Device has 3 relay outputs dry contact Views and functions of ports are as given below 5V DC Supply input RS485 input Port TX TX ...

Page 4: ...ter OK button Used for entering the selected menu or confirming the selected option 1 5 Technical Features Function Parameter Value COM1 RS232 UPS Port Baud rate 2400 baud Parity No parity Stop bit 1 stop bit UPS Connection RXD TXD Gnd 3 wire Pin no Function 1 Empty 2 TXD RS232 3 RXD RS232 4 Empty 5 Signal Ground 6 Empty 7 Empty 8 Empty 9 Empty TFT Screen Enter OK button Selection buttons ...

Page 5: ...stance Connection shall be made with CC05 coded cable See the next topic for pin explanations of CC05 Cable RS485 connection This connection type is used for distances longer than 25 meters with UPS As UPS has standard RS232 communication output RSC24 model RS232 RS485 converter adapter should be used to establish communication with RMP Input of this adapter shall be established with CC05 coded ca...

Page 6: ...e max 25m CC11 RS485 communication cable distances further than 25m RMP COM1 or PC COM PORTS 4 3 5 2 1 8 7 4 1 8 7 6 2 9 6 9 5 3 UPS communication port or RMP COM2 CONNECTOR MC1 5 5 ST 3 81 RMP RS485 input PORT Tx Tx Rx Rx Gnd Gnd Tx Tx Rx Rx CONNECTOR MC1 5 5 ST 3 81 RSC24 RS485 output PORT RMP X1 ...

Page 7: ...easured parameters These menus can be roamed with the menu selection button and enter into menu content with the enter button Menu selection button is used again to monitor different parameters inside the menu Menu names and monitorable values are given at upper line on the LCD screen UPS status information and alarms are monitored on the lower line Values in the menu content vary depending on com...

Page 8: ... P P L1 3 L2 1 L3 2 V V FREQ Hz Alarm Line BYPASS VOLTAGE VALUES BETWEEN PHASE NEUTRAL BYPASS VOLTAGE VALUES BETWEEN PHASE PHASE BYPASS FREQUENCY STATUS AND VALUE LOWEST LINE IS THE ALARM INDICATOR MEASURES INVERTER P N L1 L2 L3 V V Alarm Line INDICATES THE INTERTER VOLTAGE VALUES BETWEEN PHASE NEUTRAL LOWEST LINE IS THE ALARM INDICATOR MEASURES OUTPUT P N L1 L2 L3 V V I A P P L1 3 L2 1 L3 2 V V F...

Page 9: ... setting and Button volume setting screen background illumination settings are adjusted independent from UPS Lowest line is the alarm indicator Remote control permission setting UPS communication frequency setting 2400 9600 UPS communication type setting RS232 RS485 Setting for alarm assignment to internal alarm relays Selection screen indicates the normal open or closed emergency stop button inpu...

Page 10: ...stopped R07 SHORT INTERRUPTION Alarm Short term interruption at rectifier input voltage rectifier stopped R08 IGBT ERROR Alarm Excessive load at rectifier power components rectifier stopped R09 PHASE ROTATE Alarm Rectifier AC input voltage phase line faulty rectifier stopped R14 PFC PAUSED Alarm Rectifier paused for short period R15 DC LOW Alarm DC busbar reduced while rectifier operates rectifier...

Page 11: ...ing device will stop soon and electricity of connected loads will be interrupted A27 GENERATOR MODE Warning Device operates at generator position A28 PHASE LOSS Warning Interruption in any of phases at UPS output A29 NO SYNCHRON Warning Inverter is not synchronous to by pass input A30 SHORT CIRCUIT Warning Short circuit occurred and passed at UPS output A31 OUTPUT SWITCH Warning Device output swit...

Page 12: ...pplied operation period will be short User will be warned with an audio warning once in 15 seconds when this message is seen A19 BATT FAULT Accumulators are detected as faulty as the result of accumulator test Message may be deleted by the user by pressing the enter button for 3 seconds User will be warned with an audio warning once in 15 seconds when this message is seen A20 BOOST CHARGE Accumula...

Page 13: ... a different alarm occurs panel voice will be opened automatically 4 POSSIBLE FAILURES If electricity is not supplied to panel when the supply cable is plugged supply cable may be failed The socket which the cable is plugged in may be failed Main card transformer of remote monitoring panel may be failed All connections made with UPS but if communication interrupted alarm is given on the remote mon...

Page 14: ...13 ...

Page 15: ...14 AGKK13150 08 2018 ...

Reviews: