T-100 Series UPS User Manual
8
The safety earth cable must be connected to the earth bus bar and bonded to each cabinet in the system.
All cabinets should be earthed in accordance with local regulations.
The UPS itself has no effect on the earthing quality i.e. it doesn’t change the unwanted voltage difference
between the earth and neutral lines.
Once the equipment has been finally positioned and secured, connect the power cables as described in
the following section.
It is recommended that the UPS should be connected to the line voltage protected by a circuit breaker.
1.
Before connecting AC and DC power to the UPS make sure that the On-Off Switch PK1 and Main
Switch on the rear panel are in the "
0
" position "OFF".
2.
Connect the AC and/or DC input power to the UPS according to the label on the rear panel. Perform
the load connections according to the same label too..
3.
Check if the connections are correct. (battery polarity, ac voltage ratings etc.)
3.3.1 2-3 kVA :
After plugging in the loads and the UPS, check the reverse line polarity indicator on the rear panel (for 2-
3kVA only). If it lights, you should reverse the AC input plug.
3.3.2 5-6-7,5-10-15 kVA :
Figure 3.1 2-3 kVA
Figure 3.2 5 - 6 - 7,5 - 10 - 15 kVA
a)
5-6-7,5 kVA
b)
10 kVA KGK
c) 15 kVA
Summary of Contents for T-100 Series
Page 2: ......
Page 4: ......
Page 19: ...T 100 Series UPS User Manual 16...
Page 20: ...T 100 Series UPS User Manual 17 Connection Diagram Of The RMP COM1 T MON...
Page 23: ...AGKK3772 02 2011...