10
ALARM
DESCRIPTION
A28
P.FAILURE 21
Parallel controller board failure
A29
P.TEST MODE
Paralel controller is in test mode
A30 P FAILURE 23
Parallel controller board failure
A31
DUBL UPS NR.
Same UPS number is used in parallel system.
Possible Causes:
1) Change from settings menu
A39 PSP FAILURE
Power supply is not functioning possibly because either of a wrong phase
sequence or rectifier fault.
A40 CANT FIND PR
One of parallel modes is selected but there is no parallel control board on UPS
Change mode from settings menu
A41 P.BAL.FAILURE
In parallel operation current sharing is not okay
A42 BATTERY TEST
Performing battery test
A43 P.SYNC.FAIL
In parallel system SLAVE UPS is not synchronized to MASTER UPS
A44 BT.OPERATION
UPS is operating from batteries
Possible Causes:
1) Central system is black-out
2) Distribution problems upfront of the UPS
A45 MAINS OK
After mains failure, mains voltage restored again. This message appears on
screen for 15 seconds after mains restored.
A46 BOOST CH.END
Boost charge mode is finished, normal charge is valid.
A47 CANNOT START
Analog start system in UPS is failed.
Status messages:
This message group simply shows the UPS STATUS at the upper line of LCD PANEL.
RECTIFIER START !
:
UPS started the rectifier
INVERTER START !
:
UPS started the inverter
MAINT SWITCH ON !
:
Maintenance bypass switch is on
MANUEL BYPASS !
:
Load is transferred to mains manually
STATUS ALARM !
:
Alarm status
STATUS NORMAL !
:
UPS is operating
EMERGENCY STOP !
:
External emergency signal is detected.
WAITING SYNC !
:
Inverter started waiting for syncronization
STATUS FAULT !
:
Fault status
CLOSE BATT.CB !
:
UPS is waiting for battery CB close
STATUS WARNING !
:
Warning message is valid on LCD panel
RECTIFIER START :
At start up the UPS controller board check for input voltage, frequency, battery voltage for starting, if these
parameters normal UPS starts.
INVERTER START :
If the inverter stops controller board tries to start again, during inverter start this message appears on first line of
LCD PANEL.
MAINT SWITCH ON:
Maintenance bypass switch is connected from input to the output of UPS directly, controller stops inverter for
accidental short circuits between mains voltage and inverter output. If the user turn off maintenance switch
inverter starts again.
EMERGENCY STOP :
If an external EPO switch is installed to system (connected to interface board), to stop all UPS parts (rectifier,
static bypass, inverter, etc….) is possible. After pressing EPO switch all parts of the UPS stops, for restart turn
off S1 (inverter input) switch and turn on again.
FAULT STATUS :
In some cases controller checks events but can not find solutions, in this case controller decide to stop system
,for restart user must be turn off S1 (inverter input) switch and turn on again.