ALARM 

DESCRIPTION 

A4   OUT FAILURE 

UPS output voltage is out of tolerance at 3 times in 30 min. 

 

Internal failure. Call service. 

A5   BATT AUT END

   

Batteries empty at last of line out. Wait to return of electric. 

A6   CHARGER FAULT 

Rectifier is not to produce DC bus voltage. 

A7   BATTERY LOW 

Batteries are low. 

Possible Causes: 

1) UPS wrought long time when line out  

 

2) Charger system failure 

A8   OUTPUT HIGH

 

Inverter output voltage is over than max. tolerance voltage value.  
Inverter is stopped. 

Possible Causes:

 

1) Inverter failure 

A9   OVERLOAD

 

UPS loaded over than max. %100 load level. 

Possible Causes: 

Load  on  the  UPS  output  is  over  than  max.  Load  capacity.  This  state  is  maybe 
continous or short time. When this alarm is continous to check loads.  

A10   LINE FAILURE

 

Line failure. 

Possible Causes:

 

1) Maybe line out 

 

2) There is a problem on the UPS ınput board. Please Check. 

 

3) UPS input fuses blowned. 

A11   HIGH TEMPER

 

Over temperature. (inverter or rectifier section) 

Possible Causes:

 

1) Overload for inverter 

 

2) Over temperature 

 

3) Fan failure or durty air inlets 

 

4) Bad UPS settling. There is not vantilation area. 

A12   IGBT FAILURE

 

Inverter output system failure. 

Possible Causes:

 

1) Overload. 

 

2) Short circuit. 

 

3) UPS is out of order. Call service. 

A13   OUTPUT LOW

 

Inverter output voltage is under than min. tolerance voltage value.  
Inverter is stopped. 

A14   BATTERY HIGH

 

Battery voltage is over than max. tolerance. 

A15   FUSE FAILURE 

Fuse blowned. (not used at this power range) 

A16   BYP INPUT BAD 

During transfer to bypass ,Voltage or frequency value of bypass source is incorrect 
and the UPS turn off the load power. 
During normal (inverter) operation some times you can see this message. 
During  bypass  if  the  bypass  protection  option  is  on  and  if  the  bypass  source  is 
tolerant out UPS switch off the static bypass for load protection. 

A17   BATT CB OPEN

 

Battery circuit breaker is off ,batteries are not connected to UPS 
At start up If the mains is okay you can start operation but this message is active 
At start up During Line failure UPS waits for turn on battery CB and then it starts 

A18  BATT.CAPA.LOW 

If the battery charge is low this message indicates that charge period is not 
completed. If mains failure occurs during this message battery operating time is 
not valid. 
UPS gives beep sound whitin 15 sec 

A19   BATT  FAULT

 

Battery test aborted. And batteries are not OKAY 
UPS gives beep sound whitin 15 sec 
You can clear this message by pressing 3 seconds to ENTER key 

Possible Causes: 

1) Rectifier fault 

 

2) Battery cells damaged 

 

3) PURE battery connection 

A20 BOOST CHARGE 

Boost charge is active for 10 hours. At the end of this time UPS stops the boost 
charge. 
UPS gives beep sound whitin 15 sec 

A21 ROTATE PHASE 

Phase sequence is changed on the UPS input.  Please change. 

A23 MODE FAILURE 

In parallel system, the operation mode of 1 UPS is differenf from the other 

A24   P.FAILURE 17

 

Parallel controller board failure 

A25   P.FAILURE 18

 

Parallel controller board failure 

A26   P.FAILURE 19 

Parallel controller board failure 

A27   P.FAILURE 20

 

Parallel controller board failure 

 

 

Summary of Contents for T-3250P

Page 1: ...USER MANUAL T 300P SERIES T 3250P 250 kVA T 3300P 300 kVA...

Page 2: ......

Page 3: ...n 19 3 1 1 Security 19 3 1 2 Redundancy 19 3 1 3 Power Increment 19 3 2 Parallel Operation Modes 19 3 2 1 Symetric Parallel Mode 19 3 2 2 Redundant Parallel Mode 20 3 2 3 Hot Standby Mode 21 3 3 Paral...

Page 4: ...SERVICE 34 6 1 Maintenance 34 6 2 Troubleshooting 34 6 3 Storage 34 VII REMOTE MONITORING AND CONTROL 35 7 1 Using Serial Port 35 7 2 Serial Communication Cable 35 7 3 Modem Connection 35 7 3 1 Hardwa...

Page 5: ...e personnel The output may be energized when the unit is not connected to a mains supply Risk of electric shock hazardous live parts inside this unit are energized from the battery supply even when th...

Page 6: ...e technology with pure sine wave output PWM and IGBT technology 3 Microprocessors at each UPS Microprocessor controlled main controller board Microprocessor controlled rectifier board Microprocessor c...

Page 7: ...provides this voltage and frequency being fixed STATIC TRANSFER SWITCH STATIC BY PASS Two types of bypass circuitry is available for T 300P series UPS Full static switch for parallel systems Half sta...

Page 8: ...chanical bypass circuit breaker the load is powered by the UPS Also during the normal operation battery charges This is made by the UPS s rectifier B Battery operation During this operation Inverter p...

Page 9: ...rter Rectifier Static By Pass Static Transfer Switch Maintenance Bypass Mechanic transfer switch 3 Phase Line Input Battery group S3 S2 S1 S5 S4 3 Phase By Pass Supply Input Figure 1 2 UPS Split exter...

Page 10: ...el System Analog Signals Socket DB15 Female optional Dry Relay Output Contacts Battery Circuit Breaker Input Emergency Stop Line Failure Relay Battery Low Relay By Pass Relay Figure 1 3 250 300 kVA Po...

Page 11: ...N Voltage regulation tolerance 1 Nominal Output frequency 50 Hz Output frequency tolerance line syncron 2 Output frequency tolerance free running 0 2 Efficiency 100 Load 90 Load Crest Factor 3 1 Tota...

Page 12: ...5 function keys on front panel these are ENTER UP DOWN PLUS and MINUS UP and DOWN keys help moving on menus PLUS and MINUS keys select options ENTER key means the selected option or menu is valid NOTE...

Page 13: ...at this power range A16 BYP INPUT BAD During transfer to bypass Voltage or frequency value of bypass source is incorrect and the UPS turn off the load power During normal inverter operation some time...

Page 14: ...PS STATUS at the upper line of LCD PANEL RECTIFIER START UPS started the rectifier INVERTER START UPS started the inverter MAINT SWITCH ON Maintenance bypass switch is on MANUEL BYPASS Load is transfe...

Page 15: ...us CANCEL SHUTDOWN Shutdown command is canceled Only operating system or a PC computer can send this commands If the shutdown command is performed during line failure UPS shutdowns and is the mains is...

Page 16: ...er of the UPS VERSION MC1XX Version of UPS FREQUENCY PLL XTAL Frequency generation mode ENTER EXIT Exit from submenu PASSWORD MENU password required System settings ENTER EXIT Exit from submenu SETTIN...

Page 17: ...voltages 6 IPI 022 010 030 Input currents amperes 7 BATT 430 V 22 1 A Battery voltage and charge current 8 TEMP 030 c Cabinet inside temperature 9 CHARGE LEVEL 100 BATT CAPACI 068 Battery charge level...

Page 18: ...on is valid 2 UPS No 001 By using PLUS and MINUS keys you can change number 0 to 3 In parallel operation select different number for each UPS If you select the same number DUBL UPS NUMBER message tell...

Page 19: ...ort is installed UPS sends AT command set to modem for installation If the function is completed you must hear a beep sound At the and of this function modem is ready to answer dial up connection 5 EN...

Page 20: ...8 ENTER UPDATE Enter update new date and time 9 ENTER EXIT Enter exit from submenu Goto first submenu item 2 11 PASSWORD Menu Items Only service personnel can use this menu the incorrect use of this m...

Page 21: ...s to install one more UPS to the system 3 2 Parallel Operation Modes NOTE Parallel control board and some accessories are not installed to standart T 300P series UPS but parallel operation is availabl...

Page 22: ...d power is higher than 1 UPS power but lower than the 1UPS 2UPS total power 3 2 4 Redundant Parallel Mode At this mode if one of the UPS failes the other UPS continues to feed load Assume that UPS1 on...

Page 23: ...ILURE 20 Parallel Controller Board Failure A28 P FAILURE 21 Parallel Controller Board Failure A29 P TEST MODE Parallel control board is in test position A30 P FAILURE 23 Parallel Controller Board Fail...

Page 24: ...allation it needs qualified sevice personnel You have to keep 80 cm distance between two UPS for service purposes The maximum length of digital and analog cable is 2 meters Add 20 tolerant to cables f...

Page 25: ...ns will apply power to the load equipment 1 Open the UPS doors to gain access to the main power switches 2 Make sure that S3 switch maintenance bypass is in 0 OFF position 3 Turn on the S2 static by p...

Page 26: ...Then turn off S1 inverter input S2 static bypass S4 UPS output switches and the battery circuit breaker into 0 position WARNING Inside the UPS the following points will carry hazardous voltages By pas...

Page 27: ...rrupted the L6 inverter led continuously lit also L3 battery and on the LCD A10 LINE FAILURE message appears And also an audible alarm sounds Your UPS continues to convert the battery voltage to AC vo...

Page 28: ...rton and the UPS 2 Carefully open the carton and take the UPS out 3 Retain the carton and packing material for future use Unit package contents User Manual Guarantee Certificate Battery cabinet and or...

Page 29: ...es The input output cables can be sized to suit the modules rating according to the table below WARNING This is a product for restricted sales distribution to informed partners Installation restrictio...

Page 30: ...27 Figure 5 3 250 300 kVA UPS Power Connections Split By Pass Connections Normal Connections A B A B...

Page 31: ...esult in electric shock hazard to personnel or the risk of fire 5 4 2 Cable Connections ATTENTION All the cable connections of the ups must be done by the authorized service personnel Once the equipme...

Page 32: ...29 U V W N LOAD AC INPUT 3 PHASE Neutral To be supplied by the customer Neutral Figure 5 4 POWER CONNECTIONS OF TWO UPS s FOR PARALLEL OPERATION 250kVA BATTERY GROUP BATTERY GROUP...

Page 33: ...pped via the UPS control circuitry If the batteries are cabinet mounted this circuit breaker is fitted within the cabinet however if the batteries are rack mounted or otherwise located remote to the m...

Page 34: ...31 Figure 5 5 UPS Battery Group Connection...

Page 35: ...nections there must be a dedicated serial port ATTENTION The communication cables of this option must be shielded and must install away from the voltage cables The RS232 port at RS330 board and DB9 fe...

Page 36: ...eople In case of a persistent failure or problem properly turn off the unit first Then review the following check list Be prepared to answer the questions before calling the service 1 Did you follow t...

Page 37: ...put voltage after delay WAITING SHUTDOWN Turn off UPS output voltage SHUTDOWN and turn on UPS output voltage WAITING RESTART CANCEL SHUTDOWN RENAME UPS UPS will give response to these commands if the...

Page 38: ...umber to which this is connected The dumb modem device connected to the UPS will answer the call and convert the data coming from UPS serial on the telephone line This way all measures and controls al...

Page 39: ...CY STOP input ATTENTION Max 42VAC or 60VDC voltage should be applied to the dry contact outputs 7 6 Remote Monitoring Panel Remote monitoring panel can be used from 400 meters away from UPS Up to 25 m...

Page 40: ...he product has been subjected to physical abuse improper installation unauthorized service or modification 2 The sole responsibility of corporation under this warranty shall be limited to the repair o...

Page 41: ...38...

Page 42: ...39 AGKK6221 02 2010...

Reviews: