15
Fig.3-3 Cable entry
3.6 Power Cables
3.6.1 Specifications
The UPS power cables are recommended in Table 3.3.
Table 3.3 Recommended cables for power cables
Contents
10kVA
15kVA
20kVA
30kVA
Main Input
Main Input Current(A)
20A
29A
39A
58A
Cable Section
(
mm²
)
A
6
6
10
16
B
6
6
10
16
C
6
6
10
16
N
6
6
10
16
Main Output
Main Output Current(A)
15A
23A
30A
45A
Cable Section
(
mm²
)
A
6
6
10
16
B
6
6
10
16
C
6
6
10
16
N
6
6
10
16
Bypass Input
(
Optional
)
Bypass Input Current(A)
15A
23A
30A
45A
Cable Section
(
mm²
)
A
6
6
10
16
B
6
6
10
16
C
6
6
10
16