19
Default: None
6
GND
Ground for Vcc
7
OUT _DRY1_NO
Output dry contact-1, 7-9(Normally open) function is settable.
Default: None
If used for BCB_DRV,6-7, p15V voltage
,
20mA drive signal
8
OUT _DRY1_NC
Output dry contact-1, 8-9(Normally closed) function is settable.
Default: None
9
OUT
_DRY1_GND
Common terminal for 7 and 8
10
OUT _DRY2_NO
Output dry contact-2, 10-12(Normally open), function is settable.
Default: None
11
OUT _DRY2_NC
Output dry contact-2, 11-12(Normally closed), function is settable.
Default: None
12
OUT
_DRY2_GND
Common terminal for 10and 11,
13
OUT _DRY3_NO
Output dry contact-3, 13-15(Normally open), function is settable.
Default: None
14
OUT _DRY3_NC
Output dry contact-3, 14-15 (Normally closed), function is settable.
Default: None
15
OUT
_DRY3_GND
Common terminal for 13 and 14
Note
The settable functions for each port can be set by the monitor software or touch
screen.
Specified temperature sensor is required for temperature detection (R25=5Kohm,
B25/50=3275), please confirm with the manufacturer, or contact the local
maintenance engineers when placing an order.
The output dry contact interface: An auxiliary dry contact signal will be activated
via the isolation of a relay.
3.7.2 Communication Interface
RS232
、
RS485 and USB port
:
Provide serial data which can be used for
commissioning and maintenance by authorized engineers or can be used for
networking or integrated monitoring system in the service room.
Optional smart cards: SNMP card, GPRS card and Wi-Fi card etc.
The smart cards are installed in the optional card slot of UPS, which support hot-plug
and feature convenient installation. Proceed as follows:
Step 1: first remove the cover plate from the intelligent slot;
Step 2: insert the required smart card into the slot;
Step 3: lock the smart card with previously removed screws.
SNMP card
is compatible with today's popular Internet software and firmware and
network operating system and provide direct the direct Internet access function for
UPS to provide instant UPS data and power supply information, and achieve
communication and management by communication network management systems,