The time intervals between measurements (measurement rate should be
smaller than the alarm delay (e.g. measurement rate = 5 minutes, alarm
delay = 15 minutes).
•
Timed control:
Define individual alarm periods for which the alarm limit
values 1 and 2, or no alarm at all, apply. To define the alarm value 1 and
2, double-click on a time point in the table or pull open the desired time
period with the mouse. In periods in which the the table is left empty, you
receive no alarm.
If you have not defined alarm periods, the alarm limits will be active 24
hours a day.
If alarm periods have been defined, the limit value alarms are active only
in the marked period.
•
Channel alarms
: alarms in the event of a defective sensor.
•
E-mail recipient
: addressees who are informed when an alarm occurs.
Click on the checkbox in front of the recipient or enter the name and e-
mail address of other recipients and click on the
+ Add
button.
•
SMS recipient
: addressees who are informed when an alarm occurs.
Click on the checkbox in front of the recipient or enter the name and
mobile phone number of other recipients and click on the
+ Add
button.
•
Save
:
click on the button to save the settings.
•
Delete
:
click on the button to delete the alarm setting.
10.4
System warnings
Creating and displaying system warnings
•
Click on the
+ New system warning
button to create a new system
warning.
Existing system warnings are displayed below the button.
•
Click on the title of a system warning to display it.
Configuring and editing a displayed system warning
The following settings can be defined and edited:
•
Title
: designation of the system warning (required field).
•
Battery almost discharged
: monitor the WiFi data logger for discharged
battery.
•
Power supply interrupted
: monitor the external power supply of the
WiFi data logger for interruptions.