background image

The 

Premier Elite OH-W

 is designed to detect the presence of fire and activate an alarm control panel. As the 

Premier 

Elite OH-W 

is not a complete alarm system, but only a part therof, Texecom cannot accept responsibility or liability 

for any damages whatsoever based on a claim that the 

Premier Elite OH-W

 failed to function correctly. These 

instructions are intended as a guide only, always consult Local and National Standards where applicable. 
Due to our policy of continuous improvement Texecom reserves the right to change specification without prior notice.

Standards

Alarm Systems:

EN14604, EN50131-5-3, EN50131-1, PD6662:2010, Grade 2 Class II

EMC:

EN50130-4:

ETSI EN301 

R&TTE:

 ETSI  EN300-220

Environmental:

 EN50130-5

Frequency Band:

(See product label)

868.0 - 868.6 MHz 

866.0 - 866.6 MHz

433.05 - 434.79 MHz 

Receiver:

Category 1, Class 2

Receiver LBT 

(Listen Before Talk)

Yes

Transmitter Duty Cycle

868MHz<1%, 866MHz<1%, 433MHz<10%

Low Voltage Signal

2.85V

Operating Voltage

3V

Certificate Number: FM 35285

Specifications

Unique ID codes

Over 1 billion

Supervisory Interval

15 minutes

Spacing rating

21m

Audible Signal

85dBA min. in alarm

Sensitivity

5 - 3.5%/foot

Max current 

50mA

Alarm Current

20mA

Supervisory Current

25 uA

Battery Life

Up to 1.5 years

Operating temp.

4.4˚C to 37.8˚C

Dimensions

125mm x 63mm high

Relative humidity

Max. 90%

Weight (Inc Batteries)

243g   

Warranty 

2 years (excluding batteries)