Specifications 

Power Supply Type 

Type A 

Mains supply 

230V (+10%/-15%) @ 50Hz 

Output voltage Range 

13V-13.9V 

Maximum Ripple Voltage 

0.5V pk-pk 

Maximum rating of Outputs 
 

Aux 12V 
Bell/Strobe 
Network 1 & 2 
Battery 

DC+/DC- 

1A 
1A 
1A 
1.6A 

0.9A 

Output current (max) 

2.5A 

Maximum available current 
 

1.5A (0.75A charge rate) 
1.6A (2 x 0.3A charge rate) 
1.9A (1 x 0.3A charge rate) 

Rated output 

See page 4. 

Current consumption 

PSU200 45mA 

PSU200XP 75mA 

Fuses 

Mains = 3.15A slow blow; F1 = 1.6A  

Battery Type 

Maximum 18Ah; 1 x 7Ah; 2 x 7Ah; 1 x 17Ah 

Maximum Recharge Time 

24h @ 0.75A charge ate, 72h @0.3A charge rate 

Battery charge current 

0.3A or 0.75A (selectable) 

Battery Low Voltage Signal 

10.5V at supply output 

Deep discharge cut-off 

9V at supply output 

Over Voltage Protection 

16V 

Operating temperature 

-10

°

C to +55

°

Maximum humidity 

95% non-condensing 

Dimensions 

310mm x 410mm x 100mm 

Packed weight 

PSU200 3.9Kg (approx) 

PSU200XP 4.1Kg (approx) 

Standards 

 

2004/108/EC (CE directive): Hereby, Texecom declares that this device is in compliance with the 
essential requirements and other relevant provisions of Directive 2004/108/EC. 

 

Weee Directive: 2002/96/EC (WEEE directive): Products marked with this symbol cannot be disposed of 

as unsorted municipal waste in the European Union. For proper recycling, return this product to your 
local supplier upon the purchase of equivalent new equipment, or dispose of it at designated collection 
points. For more information see: www.recyclethis.info. 

RoHs Directive: 2002/95/EC RoHS Compliant. Hereby, Texecom declares that this device does not contain lead, mercury, 

cadmium, hexavalent chromium, polybrominated biphenyls (PBB) or polybrominated depheny ethers (PBDE) in more than the 
percentage specified by EU directive 2002/95/EC, except exemptions stated in EU directive 2002/95/EC annex. 

This  product  is a Type B Moveable device and is suitable for use in systems designed to comply with EN 50131-1, EN50131-3, 
EN50131-6 and PD6662 at Grade 3 and Environmental Class II. 

Warranty 

All Texecom products are designed for reliable, trouble-free operation. Quality is carefully monitored by extensive computerised testing. 
As a result the 

Premier Elite PSU200

 and 

PSU200XP

 are covered by a two-year warranty against defects in material or workmanship. As 

the 

Premier Elite PSU200 

and

 PSU200XP

 are not a complete alarm system but only a part thereof, Texecom cannot accept responsibility 

or liability for any damages whatsoever based on a claim that the 

Premier Elite PSU200 

or

 PSU200XP

 failed to function correctly. Due to 

our policy of continuous improvement Texecom reserve the right to change specification without prior notice. 

Premier

 

& Premier Elite

 are trademarks of Texecom Ltd. 

Summary of Contents for Premier Elite PSU200

Page 1: ...Premier Elite PSU200 PSU200XP Installation Manual INS314 3 ...

Page 2: ...ol panels Premier Premier Elite 24 48 88 168 640 PSU200 and PSU200XP Layout 1 Texecom Power Supply 2 Spare Fuse 3 PSU200 PSU200XP PCB 4 8XP zone expander PCB only fitted on PSU200XP 5 Standby battery space 2 x 7Ah or 1 x 17Ah 6 Mains cable entry and anchor point 7 Fused terminal block connector for mains supply 8 Keyhole mounting and back tamper fixing point 9 Tamper switch assembly Figure 1 PSU20...

Page 3: ...nal block this can be found in the spares bag Secure the mains cable to the anchor point using a cable tie L E N To Power Supply Mains Fuse Supply Output Two sets of terminals are provided to allow connection to auxiliary 12V devices The output is protected by a 1 6A fuse Tamper Protection The power supply is both front and back tamper protected by the use of a tamper switch which is connected to ...

Page 4: ...ndby batteries will be electronically disconnected when the terminal voltage reaches 9 0V When powering up the power supply without a mains supply battery only the Kick Start switch must be pressed in order to bring the battery into circuit Battery Monitoring Each battery is monitored independently therefore the number of batteries connected to the PSU200 PSU200XP must be set using JP8 If JP8 is s...

Page 5: ...battery leads to the battery terminals 10 Apply mains power and check the operation of the power supply 11 Refit the front cover remembering to connect the earth lead to the front cover 12 Replace the front cover screw Wiring Diagrams PSU200XP Connected to Premier Elite Control Panel For a list of supported control panels see page 2 8XP A ux 12V PSU200 To Next E xpander Keypad To 12V Devices From ...

Page 6: ...nicipal waste in the European Union For proper recycling return this product to your local supplier upon the purchase of equivalent new equipment or dispose of it at designated collection points For more information see www recyclethis info RoHs Directive 2002 95 EC RoHS Compliant Hereby Texecom declares that this device does not contain lead mercury cadmium hexavalent chromium polybrominated biph...

Page 7: ...Premier Elite PSU200 PSU200XP Installation Manual INS314 3 7 Notes ...

Page 8: ...ngland Technical Support UK Customers Tel 08456 300 600 Calls charged at 3 36 pence per minute from a BT landline Calls from other networks may vary International Customers Tel 44 1706 233875 Email techsupport texe com Texecom Limited 2012 INS314 3 C ertific ate Number FM 35285 ...

Reviews: