background image

Page 8

CL-B101D40-TCRTD Manual (d0099)

Operational Display

SETPOINT SETTING  

AND RELAY 

CONFIGURATION MODE

STEP A

STEP B

STEP C

STEP D

No [doM] or [dob]

No [doM] or [dob]

STEP E

STEP F

STEP G

STEP H

STEP I

STEP J

STEP K

STEP L

To Step M of Setpoint

Setting and Relay

Configuration Page 9

The following programming steps are required to enter the setpoint values and configure the relay functions 

in a meter with four relays using four setpoints� Generally if less than four relays are installed, the setpoints 

without relays are operational in software for tri-color control or display only purposes�  To remove unwanted 

setpoint indications, set them to 9999 or -1999 depending on the relay activation mode selected�

STEP A  Enter the Setpoint Mode

 

1)  Press the 

P

 and   buttons at the same time� Display toggles between [SP1] and the previous 

SP1 setting�

STEP B  Set Setpoint 1 [SP1]

 

1)  Using the   and   buttons, adjust the display to the desired SP1 value�

 

2)  Press the 

P

 button� Display toggles between [doM] and the previous [doM] setting�

STEP C  Set the SP1 Delay-on-Make [doM] Delay Time Setting

 

1)  Using the   and   buttons, adjust the display to the desired [doM] value (0 to 9999 seconds)� 

The reading must continuously remain in an alarm condition until this delay time has elapsed before 

the relay will make contact (energize)�

 

2)  Press the 

P

 button� Display toggles between [dob] and the previous [dob] setting�

STEP D  Set the SP1 Delay-on-Break [dob] Delay Time Setting

 

1)  Using the   and   buttons, adjust the display to the desired [dob] value (0 to 9999 seconds)� 

The reading must continuously remain in a non-alarm   condition  until  this  delay  time  has  elapsed 

before the relay will break contact (de-energize)�

 

2)  Press the 

P

 button� Display toggles between [hYSt] and the previous [hYSt] setting�

STEP E  Select the Hysteresis [hYSt]

 

1)  Using the   and   buttons, select the Hysteresis to be ON or OFF� 

 

2)  Press the 

P

 button� Display toggles between PUM and (on) or (oFF)�

STEP F  Select Pump [PUM] (on) or (oFF)

 

1)  Using the   and   buttons, select the Pump to be ON or OFF�  When PUM is selected ON, and 

SP2 is set at a value higher than SP1, the SP1 relay will operate in a special "pump on pump off" mode�  

SP2 acts as the upper limit and SP1 acts as the lower limit of the Hysteresis Band on the SP1 relay�

For filling applications: 

[rLYS] should be set to [LhXX] (see step M)�  The SP1 relay and SP1 LED Annunciator will then activate for inputs 

less than the SP1 setpoint, and remain ON until the SP2 setpoint is reached�

For emptying applications: 

[rLYS] should be set to [hhXX] (see step M)�  The SP1 relay and SP1 LED Annunciator will then activate for inputs 

greater than the SP2 setpoint, and remain ON until the SP1 setpoint is reached�

 

2)  Press the 

P

 button� Display toggles between [SP2] and the previous SP2 setting�  

 

STEP G  Set Setpoint 2 (SP2)

 

1)  Using the   and   buttons, adjust the display to the desired SP2 value�

 

2)  Press the 

P

 button� Display toggles between [hySt] and the previous [hySt] setting�

STEP H  Select the Hysteresis [hYSt]

 

1)  Using the   and   buttons, select the Hysteresis to be ON or OFF� 

 

2)  Press the 

P

 

button. Display toggles between [SP3] and the previous [SP3] setting.

STEP I  Set Setpoint 3 (SP3) (No [doM] or [dob])

 

1)  Using the   and   

buttons, adjust the display to the desired SP3 value.

 

2)  Press the 

P

 button� Display toggles between [hySt] and the previous [hySt] setting�

STEP J  Select the Hysteresis [hYSt]

 

1)  Using the   and   buttons, select the Hysteresis to be ON or OFF� 

 

2)  Press the 

P

 button� Display toggles between [SP4] and the previous [SP4] setting�

STEP K  Set Setpoint 4 (SP4) (No [doM] or [dob])

 

1)  Using the   and   buttons, adjust the display to the desired SP4 value�

 

2)  Press the 

P

 button� Display toggles between [hySt] and the previous [hySt] setting�

STEP L  Select the Hysteresis [hYSt]

 1) 

Using the   and   buttons, select the Hysteresis to be ON or OFF� 

 

2)  Press the 

P

 button� Display toggles between [rLYS] and the previous relay setting�

Please Continue On Next Page.

Setpoint Setting and Relay Configuration Mode 

Summary of Contents for CL-B101D40-TCRTD

Page 1: ...or below Lo each setpoint Digital display blanking Decimal point setting Four level brightness control LEOPARD FAMILY Input Specs Depends on Input signal conditioner A D Converter 14 bit single slope...

Page 2: ...direction indicated by the arrow When an alternative dotted line is shown this indicates that an alternative logic branch will be followed when a particular option is present When two buttons are sho...

Page 3: ...999 seconds Pump PUM Hysteresis hYSt Hysteresis hYSt Hysteresis hYSt Setpoint 3 SP3 Setpoint 4 SP4 Operational Display MAIN MENU BRIGHTNESS AND SETPOINT VIEW MODE Bargraph Center Point Display Selecti...

Page 4: ...E STEP A Calibration Mode STEP B Calibration Mode To Digital Span Selection for Bargraph Display Page 5 cAL out iP branch will only appear if the analog output option is installed otherwise cAL on goe...

Page 5: ...between Cto and oFF the software is detecting that the optional analog output hardware is NOT installed Digital Span Selection For Bargraph Display Bargraph does not light up for Input Signals up to...

Page 6: ...igh and AnLo analog low can be reversed to provide a 20 to 4mA output The digital span selected can be as small as two counts when using the analog output to function as a Control or Alarm Driver Smal...

Page 7: ...nd 18 see Rear Panel Pinouts on page 10 Using the and buttons adjust the analog output to the desired low value as measured on the multimeter cLo may be adjusted to any value from 0 3 mA to 18 mA mA o...

Page 8: ...Press the P button Display toggles between PUM and on or oFF STEP F Select Pump PUM on or oFF 1 Using the and buttons select the Pump to be ON or OFF When PUM is selected ON and SP2 is set at a value...

Page 9: ...Bargraph Color when the bar is ABOVE SP2 Setpoint 1 Using the and buttons select the desired bargraph color grn oran or red 2 Press the P button Display toggles between CSP3 and the previous color se...

Page 10: ...p Form A relays An analog output module is also shown as installed The CL B101D40 TCRTD uses plug in type screw terminal con nectors for all input and output connections The power supply connections p...

Page 11: ...5A SP4 SP3 SP2 SP1 SP1 SP2 SP3 SP4 Relay Modules with 4 Isolated 5A Form A Relays Output Carrier Board Output Carrier Board Relay Module Relay Module Input Signal Conditioner Analog Output Module Mai...

Page 12: ...the back panel back into the case Apply power to the meter 4 Enter the program mode and select the type of thermocouple J K R T the resolution 0 1 or 1 and the display units C or F See Page 4 of the d...

Page 13: ...10 72VDC Input Modules Partial List See www texmate com IT10 Thermocouple J K R T Selectable C F 1 0 1 IT11 RTD 100 Pt Selectable 3 4 wire C F 1 0 1 385 392 IT15 RTD 1000 Pt Selectable 3 4 wire C F 1...

Reviews: