•  This meter has  been designed specifically for RPM measurements. 

Just enter the pules per revolution and the CL-B01DRPM bargraph 

will calculate and display the RPM reading.

•  Three  ranges  with  resolution  of  0.1  RPM,  1  RPM  and  10  RPM 

(99.99 x 1000 rpm max).

•  Optional isolated 16 bit analog output. User or factory scalable 

to 4 to 20 mA, 0 to 20 mA or 0 to 10 V across any desired digital 

span from ± one count to the full scale range of 0 to 9999.

•  Standard 101 segment Red Bar and Red 4-digit LED display with 

a range of 0 to 9999. Optional Green Bar and Green Digital dis-

play. Also Optional Programmable Tricolor (Red-Green-Orange) 

Bar is available.

•  Front panel LED annunciators provide indication of setpoint status.

  Two 9 Amp Form C, and two 4 Amp Form A or 4 x 4 Amp Form A 

relays available.

•  Provision to connect an external programming lockout switch. 
•  Provision for external DIM switch to reduce the brightest 

display setting by 50%.

•  Automatic intelligent averaging, smooths noisy signals while  

providing a fast display response to real level changes.

•  24V excitation is available to power encoders or prox switches.

General Features

Specifications

Index

Software Features

Bargraph Center Point Display Mode Selection  . . . 6

Bargraph Color Programming Mode  . . . . . . . . 9

Case Dimensions . . . . . . . . . . . . . . . . . . . . . . . 7

Component Layout. . . . . . . . . . . . . . . . . . . . . 10

Connector Pinouts and Pin Descriptions. .10-11

Controls and Indicators  . . . . . . . . . . . . . . . . . . 2

Setpoint Setting & Relay Configuration Mode. . . .8-9

Software Features  . . . . . . . . . . . . . . . . . . . . . . 1

Software Logic Tree . . . . . . . . . . . . . . . . . . . . . 3

Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . 1

Two Point Analog Output Range  Calibration  . . . . . 7

Digital Span Selection for Bargraph Display  . . 5

Digital Span Selection for Analog Range Output. . . 6

General Features  . . . . . . . . . . . . . . . . . . . . . . . 1

I-Series Input Signal Conditioning Modules  . . . . . 11

Ordering Information  . . . . . . . . . . . . . . . . . . . 13

Programming Conventions. . . . . . . . . . . . . . . . 2

Input Specs: ..................Depends on Input signal conditioner 
A/D Converter: ..............14 bit single slope
Accuracy: ......................±(0.05% of r 2 counts)
Temp. Coeff.: .................100 ppm/°C (Typical)
Warm up time: ...............2 minutes
Conversion Rate: ..........10 conversions per second (Typical)
Digital Display: ..............4 digit 0.56" LED red (std), green (optn) 

Range 0 to 9999 counts. 

Bargraph Display: .........101 segment 235º circular bar red (std)

green (optn)or tricolor (optn),

Polarity: .........................Assumed positive. Displays – negative
Decimal Selection: ........Front panel button selectable, X•X•X•X• 
Positive Overrange: ......Bargraph and top segments of digital display 

flash.

Negative Overrange: ....First segment of bargraph and bottom seg-

ments of digital display flash.

Relay Output: ................Two 9 Amp Form C relays, two 4 Amp Form 

A relays or 

4 x 4 Amp Form A relays.

Analog Output: .............Isolated 16 bit user scalable mA or V
  OIC (mA out) ..............4-20 mA @ 0 to 500Ω max loop resistance
  OIV (volts out) .............. 0-10 V DC @ 500 Ω or higher resistance
Power Supply: ...............AC/DC Auto sensing wide range supply
  PS1 (std) ....................85-265 VAC / 95-300 VDC, 50-400Hz 4.2W
  PS2 .............................18-48 VAC / 10-72 VDC, 50-400Hz 4.2W
Operating Temp.: ..........0 to 50°C
Storage Temp: ...............–20°C to 70°C
Relative Humidity: ........95% (non condensing)

Case Dimensions: ........Bezel (4.48"x4.48") 113.8x113.8mm 

Depth behind bezel (4.23") 107.46 mm 

Plus (0.48”) 12.24 mm for connectors

Weight: ...........................16 oz., 1lb 4 oz when packed

CL-B101D40RPM 

Smart 101 segment, 4 digit LED Tricolor or  

Mono-color digital bargraph controller 

with four fully programmable set points 

in a switchboard style case for 

RPM Measurement.

0.56” 
LEDs 

LEOPARD  

FAMILY

•  The bargraph can display, full 

scale, any desired portion of 

the digital reading.

•  Setpoint 1 has delay-on-make 

and delay-on-break plus 

a special “pump on pump 

off” mode that creates a 

Hysteresis Band between SP1 

and SP2.

•  Four programmable setpoints 

with adjustable Hysteresis.• 

Bargraph center zero function.

•  Relay activation can be select-

ed to occur above (hi) or below 

(Lo) each setpoint.

•  Decimal point setting.
•  Digital display blanking.
•  Four-level brightness control

Summary of Contents for CL-B101D40RPM

Page 1: ...Conventions 2 Input Specs Depends on Input signal conditioner A D Converter 14 bit single slope Accuracy 0 05 of reading 2 counts Temp Coeff 100 ppm C Typical Warm up time 2 minutes Conversion Rate 10 conversions per second Typical Digital Display 4 digit 0 56 LED red std green optn Range 0 to 9999 counts Bargraph Display 101 segment 235º circular bar red std green optn or tricolor optn Polarity A...

Page 2: ...xplain software programming procedures logic diagrams are used to visually assist in following the programming steps The following symbols are used throughout the logic diagrams to represent the buttons and indicators on the meter Programming Conventions X XXX XX XX XXX X XXXX XXXX Front Panel Buttons Program Button The P button is used to move from one program step to the next When pressed at the...

Page 3: ...INT VIEW MODE Bargraph Center Point Display Selection cto This branch will only appear if the analog output option is installed Back to Operational Display Digital Display ON OFF Selection diSP Sub menu MODE Calibration Mode Calibration Input Calibration Output Calibrate Analog Output Low cLo Calibrate Analog Output High chi Select the Digital Reading at which the Analog Output Hi chi will occur S...

Page 4: ...lution PPR 1 Using the and buttons enter the number of pulese per revolution Any number between 1 and 9999 may be enterd 2 Press the P button Display toggles between rg and the previous range setting STEP D Select the Range 1 Using the and buttons selete the required range There are three ranges with resolutions of 0 1 max 999 9 RPM 1 max 9999 RPM and 10 RPM max 99 99 x 10000 RPM 2 Press the P but...

Page 5: ...p for Input Signals up to 3999 counts Bargraph lights up for Input Signals above 4000 counts Bar High Bar Low Bar High Bar Low 0 25 75 100 50 0 25 75 100 50 No bargraph display Digital display No bargraph display Digital display An example of setting the digital span of the bargraph display to be different than the digital display range The bargraph can be set to display full scale 0 101 bars any ...

Page 6: ... is off If the digital display is selected to be off pressing any button to make programming changes or to view setpoints activates the digital display When the procedure is complete the digital display will then automatically switch off The Display Bargraph settings are now complete Operational Display STEP E STEP F See Example of Bargraph Center Point Display Mode Selection Above From Digital Sp...

Page 7: ...any value from 0 3 mA to 18 mA mA output selected or from 0 6 V to 8 V volt output selected However the output of cLo must always be less than the value selected for chi If a reversed analog output is desired the values selected to establish the Digital Span can be reversed see top of page 6 For digital readings outside the Digital Span selected the analog output will not go any lower than the cal...

Page 8: ...to the desired hysteresis hYSt value 2 Press the P button Display toggles between SP2 and the previous SP2 setting STEP F Set Setpoint 2 SP2 1 Using the and buttons adjust the display to the desired SP2 value 2 Press the P button Display toggles between hySt and the previous hySt setting STEP G Set the Hysteresis hYSt Setting for Setpoint 2 1 Using the and buttons adjust the display to the desired...

Page 9: ...Bargraph Color when the bar is ABOVE SP2 Setpoint 1 Using the and buttons select the desired bargraph color grn oran or red 2 Press the P button Display toggles between CSP3 and the previous color setting STEP T Select Bargraph Color when the bar is ABOVE SP3 Setpoint 1 Using the and buttons select the desired bargraph color grn oran or red 2 Press the P button Display toggles between CSP4 and the...

Page 10: ...rminal plugs and do not insert remove or handle screw terminal plugs with live wires connected 17 16 14 15 8 9 10 11 See Leopard Family Input Signal Conditioning Modules 1 2 3 4 5 6 21 20 19 Relay Outputs Reserved for RS 485 LOCK COMMON No Function DIM ANALOG OUTPUT AC Neutral DC AC Line DC ANALOG OUTPUT 29 28 27 26 25 24 23 22 Standard plug in screw terminal connectors provided by Texmate Connect...

Page 11: ...SP4 SP2 Relay Modules with 2 Non Isolated 4A Form A Relays and 2 Non Isolated 9A Form C Relays 29 28 27 25 26 24 23 22 DL Series Options Order Code OR51 OR52 OR53 OR54 210mA 210mA 210mA 210mA 210mA 210mA 210mA 210mA 210mA 210mA SP4 SP3 SP2 SP1 SP4 SP3 SP2 SP1 Relay Modules with 4 Independent 300V 210mA DC only 29 28 27 25 26 24 23 22 DL Series Options Order Code OR31 OR32 OR33 OR34 5A 5A 5A 5A 5A ...

Page 12: ...s for input output leads is recommended with shield connection to earth ground near the meter preferred 4 A circuit breaker or disconnect switch is required to disconnect power to the meter The breaker switch should be in close proximity to the meter and marked as the disconnecting device for the meter or meter circuit The circuit breaker or wall switch must be rated for the applied voltage e g 12...

Page 13: ...en LED Bargraph w 4 Digit Red DPM Horizontal 20 HRG Red LED Bargraph w 4 Digit Green DPM Horizontal 15 HTG Tri Color Bargraph w 4 Digit Green DPM Horizontal 60 HTR Tri Color Bargraph w 4 Digit Red DPM Horizontal 50 DSGG Dual Scale Green LED Vertical Bargraph w 4 Digit Green DPM 30 DSGR Dual Scale Green LED Vertical Bargraph w 4 Digit Red DPM 20 DSRG Dual Scale Red LED Vertical Bargraph w 4 Digit G...