Texmate, Inc. Tel. (760) 598-9899
Page 6
3/31/00 DI-45U Data Sheet (DI2)
SET AND ADJUST HYSTERESIS
AND HYSTERESIS WITH LATCHING
P
P
P
P
P
P
P
P
TIME DELAY
SET AND ADJUST TIME DELAY
AND TIME DELAY WITH LATCHING
TIME DELAY WITH LATCHING
P
P
P
P
P
P
P
P
HYSTERESIS WITH LATCHING
HYSTERESIS
Change existing number in Digit 3 to a 1 for
Hysteresis or to a 4 for Hysteresis with Latching
Start at Code 2 (see pages 4 and 5)
Enter the desired number of counts (up to 127
counts for Hysteresis.)
Press Prog. button to move through Code 3
Press Prog. button to move through Code 4
and press Prog. again to return to operational
display.
Change existing number in Digit 3 to a 2 for
Time Delay or to a 5 for Time Delay with
Latching
Start at Code 2 (see pages 4 and 5)
Enter the desired number of counts (up to 127
counts for Time Delay.)
Press Prog. button to move through Code 3
Press Prog. button to move through Code 4 and
press Prog. again to return to operational display.