background image

Page 17

Apr-18-2016  DI-60A 320 DS (NZ302)_UL April 2016

Texmate, Inc. Tel. (760) 598-9899  •  www.texmate.com

CODE 1 – Display Configuration

Setpoint

Annunciators

Mode

First Digit

Update

Display Mode

Second Digit

Manual

Loader Mode

Second Digit

Display Functions

Mode

Second & Third Digits

Data

Source

Sub-menu

[X5X]

Display

Format

Sub-menu

[X6X]

Last Digit

Text Character

Sub-menu

[X7X]

Setpoint Annunciators Mode

The setpoint annunciators mode is configured by changing the 
first digit in Code 1. The setpoint annunciators can be configured 
to operate as follows:
•  On when the setpoint activates.
•  All annunciators are permanently on and each one only goes 

off when its setpoint activates.

•  All annunciators are always off (See Note 1 on Code 1 diagram 

on Page 18).

•  Setpoint 

1

 annunciator comes 

on

 indicating a 

rising

 

signal

Setpoint 

2

 annunciator comes 

on

 indicating a 

falling

 

signal

.

The example procedure on Page 22 shows how to select the 
setpoint annunciators to come ON when the setpoints are OFF 
(not active).

Update Display at Selected Sample Rate

The meter’s default display update rate is 0.5 seconds and is 
set in the 2nd digit of Code 1 as [X0X].
The display can be configured to update at the analog sample 
rate selected in Code 2. 
The example procedure on Page 22 shows how to configure 
the display to update at 50 samples per second by setting Code 
1 to [X2X].
For these settings to take effect, the analog sample rate must 
be set at [2XX] in Code 2.

See Code 2 – Channel 1 Measurement Task and Sampling Rate on Page 

23 for an example.

Manual Loader Mode

The meter can be configured to function exclusively as a man-
ual loader by setting Code 1 to [X1X].

See Analog Output Module Supplement (NZ200) for full details on 
manual loader mode functions.

CODE 1 – Display Configuration Modes

All meter display modes, except the display brightness mode, 
are configured in Code 1 (See diagram below). See Code 1 
diagram on Page 18 for a breakdown of 1st, 2nd, and 3rd digits 
settings.

Display Functions Mode

The display functions mode is configured by changing the 2nd 
and 3rd digits in Code 1:
•  Selecting [X5X] enters the 

Data Source

 sub-menu.

•  Selecting [X6X] enters the 

Display Format

 sub-menu.

•  Selecting [X7X] enters the 

Last Digit Text Character

 sub-

menu.

Data Source – 2nd Digit [X5X]

The data source for the primary display is configured by selecting 

5

 in the 2nd digit and 

0

 in the 3rd digit.

Note:

[XX1] Second Display is the bargraph display on models DI-50B51 

and FI-B101D50. The [XX1] Second Display and [XX2] Third 

Display only apply to DI-503 meters with three displays.

The 2nd digit in Code 1 can also be used to configure the data 
source for the remaining functions in the 3rd digit:
•  [X53] = Peak and Valley.
•  [X54] = Analog Output 1.
•  [X55] = Analog Output 2.
•  [X56] = Totalizer 1.
•  [X57] = Totalizer 2.
Selecting 

5

 in the 2nd digit enters a sub-menu and allows you 

to select the data from one of a number of meter registers as 
the data source for the displays or functions selected in the 
third digit.
The example procedure on Page 19 shows how to select the 
data source for the 

primary

 display. The three digits are set to 

[

X50

].

Display Format – 2nd Digit [X6X]

Selecting 

6

 in the 2nd digit enters the Display Format sub-

menu where the following display format settings can all be 
configured:
•  Last digit rounding.
•  Display units (Decimal, octal, or optional 12 or 24-hour clock).
•  Decimal point placement.
The example procedure on Page 20 shows how to configure 
the three display format modes for the 3rd digit selection.

Text Character – 2nd Digit [X7X]

Selecting 

7

 in the 2nd digit allows you to select one of 54 

characters and apply it to the last digit when the meter is in the 
operational display.
For example, if the meter was measuring a temperature, the 
display could be configured to display the reading with a C or 
an F in the last digit for °C or °F.
The example procedure on Page 21 shows how to configure 
the last digit text character as “C” for centigrade (°C) for the 3rd 
digit selection.

Note:

After setting any or all the above three modes [X5X], [X6X], [X7X], 

the Code 1 display must set back to [X0X] to leave Code 1 and 

carry on programming.

Initial Setup Procedures

[CodE_1] - Display Configuration

Summary of Contents for DI-60AE

Page 1: ...dback and PID output Scalable from 1 count to full scale Dual independent totalizers to integrate input signals 6 super smart independently programmable setpoints with 8 selectable functions including...

Page 2: ...smart setpoints with fully configurable hysteresis on and off delays one shot pulse and repeat timers latching dual PID setpoint tracking resetting of registers initiat ing of logging and printing Sig...

Page 3: ...ngle Analog Output Fully scalable from 4 to 20mA or 0 to 20mA or reverse and selectable for 0 to 10VDC or reverse 2 Dual Analog Output Fully scalable from 0 to 10VDC or reverse Outputs continued Analo...

Page 4: ...ta source for OUTPUT PROCESSING Select data source for Setpoint 1 2 3 4 5 6 Analog output 1 2 Data logging Select data source for DISPLAY PROCESSING Select data source for Display 1 Default Display Ch...

Page 5: ...Page 5 Apr 18 2016 DI 60A 320 DS NZ302 _UL April 2016 Texmate Inc Tel 760 598 9899 www texmate com THIS PAGE INTENTIONALLY LEFT BLANK...

Page 6: ...total 2 Once into the viewing routine pressing the button moves through each displayed parameter See Display with Faceplate and Bezel diagram Annunciator LEDs The annunciator LEDs can be programmed to...

Page 7: ...have to be connected to the COMMON pin pin 11 The LOCK pin can also be configured in Code 9 to carry out the following functions see Meter Programming Codes on Page 9 Reset channel 1 XX1 Reset channel...

Page 8: ...indicates that the buttons must be pressed at the same time The only exception to this rule is when carrying out the Model and Software Code Version Check Programming procedures are graphic based with...

Page 9: ...P The Setpoint and Relay Control Settings diagram on Pages 34 and 35 shows the three digit config uration settings that are applied individually to each setpoint See Page 33 for an example proce dure...

Page 10: ...lowing selected on demand modes On Demand Modes Tare Single point calibration Two point calibration Primary input compensation Manual loader manual offset Print View Mode SP_1 SP_3 SP_5 PEAK TOT_1 CH3...

Page 11: ...eventing them from being reprogrammed Any codes that have not been blanked out are still visible and can be reprogrammed Turning code blanking OFF means all meter programming codes are visible when yo...

Page 12: ...Display Operational Display Example OR Press at same time Press at same time Press at same time Press at same time Enter Brightness Mode Adjust brightness to 7 Save brightness setting Exit Brightness...

Page 13: ...odule Note This function is not available on all input modules 5 Calibrate Analog Output requires multimeter con nected to pins 16 and 17 6 7 0 Serial Communications Properties 1 Set Auto Zero Mainten...

Page 14: ...m 1 to 255 samples The averaging window can be set to between 1 and 65535 counts See the calibration modes diagram on Page 13 showing a breakdown of 1st 2nd and 3rd digits See Input Signal Sampling Sh...

Page 15: ...the HIGH input signal Select the No Function Calibration Mode 000 Save Calibration Mode 000 setting and enter Code 1 Exit code 1 and return to operational display 5 1 Adjust display to desired readin...

Page 16: ...6 To Step 7 OR From Step 6 OR OR Press 1 Press 1 Press 1 Press 1 Press 1 Press at same time Press at same time Press at same time Press at same time Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 St...

Page 17: ...Functions Mode The display functions mode is configured by changing the 2nd and 3rd digits in Code 1 Selecting X5X enters the Data Source sub menu Selecting X6X enters the Display Format sub menu Sele...

Page 18: ...eter the values for setpoint 5 and setpoint 6 are activated as upper and lower limits See Analog Output Supplement for further details Note 1 LED annunciators are always off except when the meter is i...

Page 19: ...CONFIGURE DATA SOURCE Go to Source selection Go to the next selection Example Procedure Configure the Primary Display with the display diSP as the data source by setting Code 1 to X50 See diagram at t...

Page 20: ...ons setting Enter Brightness Mode Pass Brightness and Calibration Modes and enter Code 1 Save entered value Save Code setting 0 No rounding 1 Rounding by 2 s 2 Rounding by 5 s 3 Rounding by 10 s Confi...

Page 21: ...Operational Display Operational Display Example Press 2 Press at same time Press at same time Press 1 OR Step 4 Press at same time Press at same time Step 6 Prog SP1 SP2 SP4 SP3 SP5 SP6 Prog SP1 SP2...

Page 22: ...nciators Procedure Prog SP1 SP2 SP4 SP3 SP5 SP6 Prog SP1 SP2 SP4 SP3 SP5 SP6 Prog SP1 SP2 SP4 SP3 SP5 SP6 Prog SP1 SP2 SP4 SP3 SP5 SP6 X X Prog SP1 SP2 SP4 SP3 SP5 SP6 CONFIGURE UPDATE AT SAMPLE RATE...

Page 23: ...pe of TC 2 RTD 3 wire 3rd digit selects type of RTD 3 RTD 2 or 4 wire 3rd digit selects type of RTD 4 Frequency 5 Period 6 Counter 7 Smart Input Module CODE 2 CHANNEL 1 MEASUREMENT TASK AND SAMPLING R...

Page 24: ...ith or without a Day Month Year or Hours Minutes Seconds time stamp Time stamp settings are configured in Code 8 Post processing functions refer to functions that occur to the input after it has been...

Page 25: ...surement task and 32 point linearization for CH2 is config ured in the 1st and 2nd digits of Code 4 The diagram opposite lists the available configuration selections in Code 4 Example Procedure Config...

Page 26: ...t X Not relevant Save CH3 setting Exit Code 6 Return to Operational Display Enter Brightness Mode FOR THERMOCOUPLE 0 Type J 1 Type K 2 Type R 3 Type S 4 Type T 5 Type B 6 Type N 7 Select user defined...

Page 27: ...Time Clock and Timer 3rd digit selects type 5 6 7 Smart Input Module 3rd digit selects register FOR SMART INPUT MODULE 0 Output Register 1 1 Output Register 2 2 Output Register 3 3 Output Register 4...

Page 28: ...sult using Table 2 See Note 5 3 32 point Linearization on Result using Table 3 See Note 5 4 32 point Linearization on Result using Table 4 See Note 5 5 125 point Linearization on Result Tables 1 to 4...

Page 29: ...S LOG OR PRINT TRIGGER 0 No trigger 1 Trigger on Demand from PROGRAM Button 2 Trigger on Demand from F1 Button 3 Trigger on Demand from F2 Button 4 Trigger on Demand from HOLD Pin 5 Trigger on Demand...

Page 30: ...y output modules support a combination of 4 5 A Form A and 9 10 A Form C relays providing 12 configuration options A solid state relay SSR output module supports 300 V 210 mA DC SSRs A 22 opto isolate...

Page 31: ...can be programmed in relay latching modes Setpoint Reset Trigger Setpoints can be programmed to reset selected registers or be manually reset They can also trigger a data print or a data log DUAL PID...

Page 32: ...N Pulsed OFF Modes These are delay modes were the relay is normally on and pulses off when the setpoint activates 1 Shot OFF mode Programmable Minimum OFF time SP ON SP OFF 1 Shot OFF Mode Prog Min OF...

Page 33: ...ly cycle thru SPC_1 Save SP1 control settings Operational Display Operational Display Exit SPC_2 and return to operational display Save SP1 activation value setting Select CH1 as the SP1 activation so...

Page 34: ...setpoint value with RISING INPUT SIGNAL INITIAL START UP INHIBIT SP Activation Source 0 Activate Setpoint Source from Selected Register 1 Select Source for Setpoint Note X1X is a register selection pr...

Page 35: ...o XX0 DOM 0 0 to 6553 5 secs Minimum on time M_on 0 0 to 6553 5 secs On time on _t 0 0 0 001 to 6553 5 65 535 secs DOB 0 0 to 6553 5 secs Off time oFF_t 0 0 0 001 to 6553 5 65 535 secs DOB 0 0 0 001 t...

Page 36: ...t hold the button down while cycling through the decades and release it when oFF or tArE appears Registers that Should Not be Used The following registers are contained within the selectable 1 to 244...

Page 37: ...r HI Voltage Fuse for LO Voltage Isolated Feed Back Isolated Switching Power Supply Controller 5 VDC 18 VDC ISO 5 VDC 5 VDC 5 VDC GND 24 VDC GND LC Filter 1 2 3 4 5 6 7 8 9 10 RELAY MODULES NO3 COM 1...

Page 38: ...29 27 26 25 Options 4A 4A Order Code OR11 OR12 OR23 OR14 4A 4A 4A 4A 10A OR15 OR16 SP2 SP4 SP1 SP3 9A 9A 9A 9A 9A 9A 9A 9A SP3 SP1 SP4 SP2 Relay Modules with up to two 4 5A Form A Relays and up to tw...

Page 39: ...and process control applications Modular construction ensures you don t have to pay for unnecessary hardware Simply order the input and output options to suit your application Input Signal Conditioni...

Page 40: ...20V 2V SPAN Increase Decrease ON OFF 24V Exc Input Signal Conditioner Main PCB Shown with optional Input Signal Conditioning Module Ordered Separately Hi Volt Order Code PS1 Lo Volt Order Code PS2 ID0...

Page 41: ...oisy components Shielding cables for input output leads is recommended with shield connection to earth ground near the meter preferred 4 A circuit breaker or disconnect switch is required to disconnec...

Page 42: ...3 Code 3 Channel 1 Post Processing and Serial Mode Functions 24 Code 4 Channel 2 Measurement Task and Sampling Rate 25 Code 5 Channel 3 Functions 26 Code 6 Channel 4 Functions 27 Code 7 Result Process...

Page 43: ...d Not Be Selected 36 Resetting and Incrementing Using Setpoints 36 Relay Logic Output Modules 38 Serial Communication Configuration 24 Pinouts 38 Setpoint Programming Mode 30 35 Data Logging 31 Data P...

Page 44: ...xmate com Texmate has facilities in Japan Taiwan and Thailand Case Dimensions Clear Lockable NEMA 4X Splash Proof Cover P N OP N4 96x48 The 96x48mm case is particularly suitable for mounting in mosaic...

Reviews: