Texmate, Inc. Tel. (760) 598-9899 • www.texmate.com
FX-B101Q-DCA_DCV manual (d0103)
Page 1
• External transmitters or signal conditioners can be eliminated
by directly connecting the sensor to Plug-in Input Signal
Conditioning Modules that include:
– DCA
ID02 : DC mV ±20mV, ±50mV,
±100mV
, ±200mV
w/24V Exc.
– DCV
ID01 : DC-Volts
2V
/20V/200V
w/24V Exc.
ID05 : DC-Volts
2V
/20V/200V
w/24V Exc. and Zero offset
adjustable pot
Analog Output Scaling and Calibration
6
Case Dimensions
12
Component Layout
8
Connector Pinouts
7
Connectors
7
Controls and Indicators
2
Custom Face Plates
10
General Features
1
Glossary of Programming Symbols &
Modes of Operation
2
Hinged Clear Lockable Poly NEMA 4X
Splash Proof Cover
12
Input Module Compatibility
1
Input Module Component Glossary
9
Installation Guideline
7
One Point Quickset Rescaling and
Calibration Procedure
5
Opening the Case to Access Mode
Select Header
4
Ordering Information
13
Overview of Display Modes, Scaling
Capabilities & Operating Modes
3
Panel Adapter
11
Pin Descriptions
7
Specifications
1
Standard Display Mode Calibration
Procedure
5
Two Point Quickset Scaling and
Calibration
3,5
• A red or optional green 101 segment bargraph.
• Auto-sensing AC/DC power supply. For voltages between
85-265 V AC / 95-300 V DC (PS1) or 14-48 V AC / 10-72 V DC (PS2).
• Optional 16 Bit isolated analog output that can be used to drive
an external process device such as a chart recorder, remote
display, or for retransmission to a central control room. User or
factory scalable to 4 to 20 mA, 0 to 20 mA or 0 to 10 V across
any desired span from ± one bar to the full scale range
• Center zero setting, header selectable.
• Provision for external brightness setting switch (by connect-
ing the DIM to the GND pin on the back of the meter).
• Smart averaging (to speed up display response).
• Optional NEMA-4 front cover.
• UL Listed
Input Specs:
Single-ended, however isolated power
supply enables differential measure-
ments up to a maximum common mode
of 50V.
A/D Converter:
14 bit single slope
Accuracy:
±(0.05% of r 1segment)
Temp. Coeff.:
100 ppm/°C (Typical)
Warm up time:
2 minutes
Conversion Rate:
10 conversions per second (Typical)
Bargraph Display:
101 segment 4” vertical (std),
horizontal (optn), red (std), green (optn)
Polarity:
Selectable center zero
Positive Overrange:
Bargraph display flashes
Negative Overrange:
First segment of bargraph display flashes
Analog Output:
Isolated 16 bit user scalable mA or V
OIC (mA out)
4-20 mA @ 0 to 500Ω max loop resistance
OIV (volts out)
0-10 V DC @ 500 Ω or higher resistance
Power Supply:
AC/DC Auto sensing wide range supply
PS1 (std)
85-265 VAC, 50-400Hz / 95-300 VDC @ 1.5W
PS2
14-48 V AC, 50-400Hz / 10-72 V DC @1.5W
Operating Temp.:
0 to 50°C
Storage Temp:
–20°C to 70°C
Relative Humidity:
95% (non condensing)
Case Dimensions:
9/64 DIN Bezel: 36x144mm(1.42"x5.69")
Depth behind bezel:117.5mm(4.64").
Plus 10mm(0.39”) for Right-angled con-
nector, or plus 18.3mm(0.72") for Straight-
thru connectors.
Weight:
9.5 oz., 12 oz when packed
Index
✔
LYNX FAMILY: More than 33 different Plug-in
I-Series Input Signal Conditioners are approved for
Texmate’s Lynx Family of meters.
See www.texmate.com for an up to date listing.
LYNX
General Features
Input Module Compatibility
Specifications
FX-B101Q-DCA
20/50/100/200mV DC Full Scale
FX-B101Q-DCV
2/20/200V DC Meter
LYNX FAMILY
A Powerful Smart DCA/DCV Bargraph
with optional
Isolated 4-20mA DC or 0-10VDC output
9/64 DIN Case