Texmate, Inc. Tel. (760) 598-9899 • www.texmate.com
Mar-07-2016 DI-50AN6 320 DS (NZ303)_UL_March 2016
Page 20
Enter
Brightness
Mode
Step 1
Step 2
Step 3
Operational
Display
Press
2
Press
at same
time
Press
at same
time
Step 4
Step 6
Step 7
Step 8
Step 9
From Step 5
Step 5
Select [X0X] to leave
Code 1
Pass Brightness and
Calibration Modes
and enter Code 1
OR
Example
Press
1
Press
at same
time
Press
at same
time
OR
OR
Exit
Code 2.
Return to
Operational
Display
Operational Display
X
X
X X
Press
1
Set Code 1 to [X61]:
1st Digit = X Note relevant
2nd Digit = 6 Selects display functions
3rd Digit = 1 Selects Channel 1
0 Result
1 Channel 1
2 Channel 2
3 Channel 3
4 Channel 4
5 Default Display
6 Total 1
7 Total 2
Set Display Format
Mode to [106]:
1st Digit = 1 Rounding by 2's
2nd Digit = 0 Decimal display
3rd Digit = 6 Decimal point
CONFIGURING THE DISPLAY FORMAT PROCEDURE
Save Display
Functions setting
CONFIGURE
DISPLAY
FORMAT
Press
1
0 No rounding
1 Rounding by 2’s
2 Rounding by 5’s
3 Rounding by 10’s
Configure Display Format Mode Procedure
LAST DIGIT ROUNDING
DISPLAY UNITS
0 Decimal
1 24-hour clock mode
Hours: Minutes: Seconds (6-digit ver-
sion only)
2 12-hour clock mode (12:30 am is
displayed as 12:30A. 12:30 pm is dis-
played as 12:30P)
3 24-hour clock mode
Days: Hours:Minutes (6-digit version only)
4 -
5 -
6 -
7 Octal
DECIMAL POINT PLACEMENT
0 No decimal point
1 -
2 -
3 X.XXXX
4
X.XXX
5
X.XX
6
X.X
7 Decimal Point set from the rear
(X.XXXX to XXXXX)
See Note 3 on page 18.
Also See Note 4 on page 18.
Display Format Mode
P
FIRST DIGIT
SECOND DIGIT
THIRD DIGIT
Program the three digits to the required display format mode
Note:
Selecting 1, 2, or 3
in the 2nd digit of
this Mode config-
ures the display of
the selected chan-
nel (see Step 4) as
a clock.
The following example procedure describes
how to configure the display format mode for
the 3rd digit selection and covers:
• Last Digit Rounding.
• Display Units.
• Decimal Point Placement.
Example Procedure:
Configure the display format mode for channel
1 with rounding by 2’s, decimal display units,
and the decimal point placed between display
digits 4 and 5 by setting Code 1 to [
X61
] to
enter the Display Format Mode.
START HERE
Initial Setup Procedures
[CodE_1] - Display Configuration continued