Mar-14-2016 DI-60 320 DS (NZ301)_UL_March 2016
Page 27
Texmate, Inc. Tel. (760) 598-9899 • www.texmate.com
CH4 POST PROCESSING
0 Direct Display of Input (no pro-
cessing)
1 Square Root of Channel 4
2 Inverse of Channel 4
3 32-point Linearization of CH4 using
Table 4
CODE 6 – CHANNEL 4 FUNCTIONS
FIRST DIGIT
SECOND DIGIT
THIRD DIGIT
FOR THERMOCOUPLE
0 Type J
1 Type K
2 Type R
3 Type S
4 Type T
5 Type B
6 Type N
7 Select User Defined Table 1 set-up
in Code 3 [X7X]. To invoke Table 1,
reset Code 3 to [00X]
FOR RTD TYPE (2-, 3-, 4- WIRE)
0 Resistance
1 RTD 385
2 RTD 392
3 RTD 120
4 Cn 10
MEASUREMENT TASK
0 No Function
1 Voltage / Current
2 TC (third digit selects type of
TC).
See Note 7
3 RTD (third digit selects type of
RTD).
See Note
7
4 Real Time Clock and Timer
(third digit selects type)
5 -
6 -
7 Smart Input Module (third digit
selects register)
FOR SMART INPUT MODULE
0 Output Register 1
1 Output Register 2
2 Output Register 3
3 Output Register 4
4 Output Register 5
5 Output Register 6
6 Output Register 7
7 Smart Input Module Register 3
Code Setup
Note:
For future development.
FOR REAL-TIME CLOCK & TIMER
0 HRS:MIN:SEC
1 HRS:MIN
2 -
3 -
4 1 Second Count UP Timer
5 1 Second Count DOWN Timer
6 -
7 -
P
Press
Use the
buttons to set the
required smart input module code
(0 to 377). See
I-Series Input
Modules Guide (Z87)
for code
details.
Code 6 is a single code that
combines all the configuration
and post processing functions
available for Channel 4.
When a
quad input
signal con-
ditioner is installed, the fourth
input signal is processed and
displayed on CH4.
Post processing and measure-
ment task functions for CH4 are
configured in the first, second,
and third digits of Code 6. The
diagram opposite lists the avail-
able configuration selections in
Code 6.
Example Procedure:
Configure CH4 for a
voltage input with the CH4
processed input signal inversed
by setting Code 6
to [
21X
].
Initial Setup Procedures
[CodE_6] - Channel 4 Functions
See
I-Series Input Modules Guide (Z87)
for pro-
cedures to set up a quad input module.
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
Press
1
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
Step 1
Step 2
Step 3
Operational Display
Operational Display
Press
6
Press
at same
time
Press
at same
time
OR
Step 4
Press
at same
time
Press
at same
time
Step 5
CONFIGURING CH4 FUNCTIONS PROCEDURE
Pass Brightness Mode,
Calibration Mode, and
Codes 1 to 5 and enter
Code 6
From Step 4
To Step 5
X
1st Digit = 2 Selects inverse of CH4
2nd Digit = 1 Selects voltage, current
3rd Digit = X Not relevant
Save CH4 setting
Exit Code 7. Return to
Operational Display
Enter Brightness Mode