Example Procedure:
The following procedure describes how to program setpoint
1 (SP1) for the following
Level 1
setpoint and relay functions:
• SP1 to activate from Channel 1 (CH1).
• Relay to energize above SP1 value.
• Relay to latch with manual relay reset.
Programming tip
All required setpoint activation values (SP1 to
SP6) can be adjusted before programming setpoint
and relay control function settings. See
Setpoint
Programming Mode Logic Diagram
on Page 34.
Setpoint Programming Mode continued
Level 1 - Basic Mode - Programming Procedures
See
Setpoints and Relays Supplement (NZ201)
for proce-
dures to program all setpoint and relay operational levels
(Level 1 to Level 3).
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
X
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
Prog.
SP1
SP2
SP4
SP3
SP5
SP6
To Step 6
OR
From Step 5
OR
OR
Press
6
Press
1
Press
1
Press
1
Press
at same
time
Press
at same
time
Press
at same
time
Press
at same
time
Step 1
Step 2
Step 3
Step 4
Step 5
Step 6
Step 7
Step 8
Step 9
Step 10
Enter Setpoint
Programming
Mode
Adjust setpoint 1 (SP1)
activation value to e.g.
500 counts
Reset 2nd digit to 0. If the 2nd
digit is not reset to 0, the
meter will constantly cycle
thru SPC_1
Save SP1
control settings
Operational Display
Operational Display
Exit SPC_2 and return
to operational display
Save SP1 activation
value setting
Select [CH1] as the SP1
activation source. See
diagram on Pages 34
and 35
Enter SP1
source sub-menu
Save SP1
control settings
Example
Example
OR
LEVEL 1 SETPOINT CONFIGURATION
Example
1st Digit = 0 Energize above SP1 value
2nd Digit = 1 Select source for SP1
3rd Digit = 3 Relay latching with manual reset