14SEER AIR HANDLER SYSTEM TECHNICAL MANUAL
1. Precaution on Installation
1.1. Measure the necessary length of the connecting pipe, and make it by the following way.
a.
Connect the indoor unit at first, then the outdoor unit.
Bend the tubing in proper way. Do not harm them.
CAUTIONS:
●
Daub the surfaces of the flare pipe and the joint nuts with frozen oil, and wrench it for 3~4 rounds
●
With hands before fasten the flare nuts.
Be sure to use two wrenches simultaneously when you connect or disconnect the pipes.
Pipe gauge
Tightening torque
Flare dimension A
Min (mm) Max
Flare shape
Φ6.35
15
~
16N.m
(153
~
163 kgf.cm)
8.3
8.7
Φ9.52
25
~
26N.m
(255
~
265kgf.cm)
12.0
12.4
Φ12.7
35
~
36N.m
(357
~
367kgf.cm)
15.4
15.8
Φ15.9
45
~
47N.m
(459
~
480 kgf.cm)
18.6
19.1
Φ19.1
65
~
67N.m
(663
~
684kgf.cm)
22.9
23.3
b.
The stop value of the outdoor unit should be closed absolutely (as original state). Every time you
connect it, first loosen the nuts at the part of stop value, then connect the flare pipe immediately (in 5
minutes). If the nuts have been loosened for a long time, dusts and other impurities may enter the pipe
system and may cause malfunction later. So please expel the air out of the pipe with refrigerant before
connection.
c.
Expel the air after connecting the refrigerant pipe with the indoor unit and the outdoor unit. Then fasten
the nuts at the repair-points.
1.2. Locate The Pipe
a.
Drill a hole in the wall (suitable just for the size of the wall conduit), then set on the fittings such as the
wall conduit and its cover.
b.
Bind the connecting pipe and the cables together tightly with binding tapes. Do not let air in, which will
cause water leakage by condensation.
c.
Pass the bound connecting pipe through the wall conduit from outside. Be careful of the pipe allocation
to do no damage to the tubing.
1.3. Connect the pipes.
1.4. Then, open the stem of stop values of the outdoor unit to make the refrigerant pipe connecting
the indoor unit with the outdoor unit in fluent flow.
1.5. Be sure of no leakage by checking it with leak detector or soap water.
1.6. Cover the joint of the connecting pipe to the indoor unit with the soundproof / insulating sheath
(fittings), and bind it well with the tapes to prevent leakage.
25
Summary of Contents for CTV14CN018A
Page 1: ...Technical Manual R410A 60Hz 14 SEER Top Discharge Heat Pump Outdoor 1 ...
Page 9: ...14SEER AIR HANDLER SYSTEM TECHNICAL MANUAL 2 Dimension 9 ...
Page 11: ...14SEER AIR HANDLER SYSTEM TECHNICAL MANUAL 4 Wiring Diagrams 18K 24K 30K 36K 42K 48K 11 ...
Page 12: ...14SEER AIR HANDLER SYSTEM TECHNICAL MANUAL 60K 12 ...
Page 17: ...14SEER AIR HANDLER SYSTEM TECHNICAL MANUAL 1 Dimension 17 ...
Page 18: ...14SEER AIR HANDLER SYSTEM TECHNICAL MANUAL 2 Service Space 18 ...
Page 19: ...14SEER AIR HANDLER SYSTEM TECHNICAL MANUAL 3 Wiring Diagrams SEER 14 Cooling only 19 ...
Page 39: ...14SEER AIR HANDLER SYSTEM TECHNICAL MANUAL 3 9 High exhaust temperature protection 39 ...