14SEER AIR HANDLER SYSTEM TECHNICAL MANUAL
4. Insulation Work
4.1
Insulation material and thickness
4.1.1. Insulation material
Insulation material should adopt the material which is able to endure the pipe’s temperature: no less than
70
℃
in the high-pressure side, no less than 120
℃
in the low-pressure side(For the cooling type machine,
no requirements at the low-pressure side.)
◆
Example: Heat pump type----Heat-resistant Polyethylene foam (withstand above 120
℃
)
Cooling only type----Polyethylene foam (withstand above 100
℃
)
4.1.2. Thickness choice for insulation material
Insulation material thickness is as follows:
Pipe diameter (mm)
Adiabatic material thickness
Refrigerant pipe
Φ6.4—Φ25.4
10mm
Φ28.6—Φ38.1
15mm
Drainage pipe
Inner diameterΦ20—Φ32
6mm
4.2 Refrigerant pipe insulation
4.2.1. Work Procedure
①
Before laying the pipes, the non-jointing parts and non-connection parts should be heat insulated.
②
When the gas proof test is eligible, the jointing area, expanding area and the flange area should be heat
insulated.
4.2.2. Insulation for non-jointing parts and non-connection parts
wrong
right
Gas pipe and liquid pipe should
not be put together to insulate
Insulate the gas pipe
(cooling only)
Insulate the gas pipe and
liquid pipe
29
Summary of Contents for CTV14CN018A
Page 1: ...Technical Manual R410A 60Hz 14 SEER Top Discharge Heat Pump Outdoor 1 ...
Page 9: ...14SEER AIR HANDLER SYSTEM TECHNICAL MANUAL 2 Dimension 9 ...
Page 11: ...14SEER AIR HANDLER SYSTEM TECHNICAL MANUAL 4 Wiring Diagrams 18K 24K 30K 36K 42K 48K 11 ...
Page 12: ...14SEER AIR HANDLER SYSTEM TECHNICAL MANUAL 60K 12 ...
Page 17: ...14SEER AIR HANDLER SYSTEM TECHNICAL MANUAL 1 Dimension 17 ...
Page 18: ...14SEER AIR HANDLER SYSTEM TECHNICAL MANUAL 2 Service Space 18 ...
Page 19: ...14SEER AIR HANDLER SYSTEM TECHNICAL MANUAL 3 Wiring Diagrams SEER 14 Cooling only 19 ...
Page 39: ...14SEER AIR HANDLER SYSTEM TECHNICAL MANUAL 3 9 High exhaust temperature protection 39 ...