background image

to enter sub menus

shows output power strength

compensation amplifier

shows sensitivity of receiver 

to exit sub menus

shows temperature at beam head

screen used by The Fire Beam 

help desk

screen used by The Fire Beam 

help desk

software versions for the head 

and controller

shows (

*

) when updating

to increase

to decrease

shows (

*

) when updating

to increase

to decrease

shows (

*

) when updating

to increase

to decrease

15

Summary of Contents for firebeam

Page 1: ...user guide issue 0025 05...

Page 2: ...flector kit 5 40 metres the standard firebeam The standard firebeam comes boxed with the head unit low level controller one reflector 3mm allen key test filter and quick start installation guide this...

Page 3: ...r side of the beam If the roof is considered to have an apex place thefirebeam system 0 3m to 0 6m down from the top of the apex up to a maximum height of 40m from the floor The maximum protected area...

Page 4: ...first plugging in the connector step one mounting the head screw the head backing plate to the wall always try to use as sturdy location as possible such as brick or major structural steels avoid moun...

Page 5: ...WN supply 10 2 30 Vdc BLUE supply return BLACK zone GREY zone GREEN earth screen Supply Voltage 12Vdc to 24 Vdc 25 15 Quiescent Current 3mA Alarm Current 3mA Aligning Current 3mA Fault Fire relay cont...

Page 6: ...en the screen will default to 3 access the menu system by pressing enter 4 scroll through the menus until you get to commissioning 5 enter commissioning and enter pre alignment pre alignment is probab...

Page 7: ...picking up a reflection from something other than the target blank wall By moving the beam looking at the wall left x right x up y and down y you can move the beam away any obstacles to achieve highe...

Page 8: ...eing the reflector You will need to move the beam head until you receive an AQ reading of above 40 ideally over 100 If you are presented with the screen below AQ air quality could be any number up to...

Page 9: ...greater air quality Wait for x y values to finish moving to asses your AQ result beam head reflector Press enter to exit manual mode and enter Auto Alignment Try and achieve as good a result as possi...

Page 10: ...irebeam will automatically move its X and Y axis until it is positioned on the reflector This operation could take 30 minutes or more step four testing to test that the firebeam is aligned correctly y...

Page 11: ...enter again to reset and return to the normal screen if in fire you will need to press back to go back to the main menu If set to auto reset it will reset to normal automatically no comms beam head i...

Page 12: ...ss enter the power will slowly drop as can be seen in the dropping air quality When the air quality drops past the pre set threshold the beam will fall into fire remember that there is a delay time se...

Page 13: ...in these directions across the face of the reflector with your back to the beam make adjustments by using the left right up and down keys this moves the beam in these directions across the face of the...

Page 14: ...during auto alignment the alignment will be aborted press back to return to auto alignment and enter to resume auto alignment once alignment is complete you will see the screen below press back to ret...

Page 15: ...xit sub menus shows temperature at beam head screen used by The Fire Beam help desk screen used by The Fire Beam help desk software versions for the head and controller shows when updating to increase...

Page 16: ...n Controller Status FIRE Controller Red Flashing LED 0 5 Second Head Red Flashing LED 1 Second Alarm Relay Change Over CO Contact Rating 2A 30 VDC Test Reset Features Beam test function by controller...

Reviews: